HomeMy WebLinkAbout2291-13. ■ f BALLFIELD LIGHTING GENERAL NOTES -NEW SITE A. STAKE OUT EXACT LOCATION OF POLES AND CONDUIT ROUTING WITH CITY PRIOR TO ANY WORK. ANY LOCATION NOT WITHIN 24" OF LOCATION SHOWN ON PLAN SHALL BE NOTIFIED TO ENGINEER AND LIGHTING MANUFACTURER IMMEDIATELY AND PRIOR TO WORK. B. VERIFY ALL POLE AND OUTLET LOCATIONS WITH THE CITY BEFORE COMMENCING WORK. POLE AND OUTLET LOCATIONS AND CONDUIT RUNS SHOWN DIAGRAMMATICALLY AND MAY NEED TO BE CHANGED TO SUIT FIELD CONDITIONS. (VERIFY WITH CITY) SEE NOTE "A N. C. TRENCHING NOTES 1. TRENCH AROUND PLAYING FIELDS AND NOT ACROSS INTO OUTFIELD PLAYING AREAS EXCEPT AS INDICATED OR UNAVOIDABLE. D. CONTRACTOR TO VISIT EXISTING SITE AND VERIFY ALL EXISTING CONDITIONS. E. CONTRACTOR TO OBTAIN ALL PERMITS AND INSPECTIONS AS REQUIRED AT NO ADDITIONAL COST TO CITY. F. ALL MATERIAL SHALL BE DELIVERED TO THE SITE NEW, IN THEIR ORIGINAL UNBROKEN PACKAGES BEARING APPROVAL BY U.L. NEMA, NBFU, OR ANY OTHER APPROPRIATE AGENCY. G. PROVIDE TYPE WRITTEN DIRECTORY (LAMINATED AND SEALED) INSIDE EACH PANEL DOOR. H. ALL WORK SHALL BE COMPLETED IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (1993 EDITION). AND ALL APPLICABLE STATE, COUNTY, AND LOCAL CODES APPLYING TO THE PROPOSED CONSTRUCTION. IN THE EVENT OF A CONFLICT BETWEEN THE ABOVE AND THESE PLANS AND SPECIFICATIONS, THE RESTRICTIVE SHALL GOVERN. I. CONTRACTOR SHALL MAINTAIN ONE SET OF "AS—BUILT" PLANS MARKED IN RED SHOWING EVERY CHANGE, ADDITION, DELETION OR MODIFICATION INCLUDING EXACT ROUTING OF CONDUITS. THIS "AS—BUILT" SET SHALL BE TRANSFERRED TO A REPRODUCIBLE FORM AND SUBMITTED TO THE CITY BEFORE FINAL ACCEPTANCE OF WORK. J. CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM MEETING THE LETTER AND THE INTENT OF THESE PLANS AND SPECIFICATIONS. K. POLES STORED ON SITE SHALL BE HANDLED (INCLUDING DELIVERY AND SETTING) WITH APPROVED STRAPS TO AVOID DAMAGE TO GALVANIZING. ACCEPT POLES FROM MANUFACTURER'S DELIVERY IN THE PRESENCE OF CITY VERIFYING ANY DAMAGE. POLES STORED SHALL NOT SET ON GRADE EACH POLE TO SET ON WOOD BASES AND TURNED 180 DEGREES EVERY 48 HOURS MINIMUM. TOUCH UP PAINTING (GALVANIZING) SHALL BE PER POLE MANUFACTURERS REQUIREMENTS. L SEE ELECTRICAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. UNISTRUT CHANNEL BALLAST CABINET — CIRCUIT BREAKER SCHEDULE — VOLTAGE SYSTEM PHASE FILE DOWN MAX. AMP RATING LUG SIZE WIRE SIZE 480 ROUGH EDGES 1-6 1-9 35 MUSCO POLE #3 480 7-12 10-18 60 1 #14-1/0 #3 480 13-20 19-20 109 1 14-1 0 #3 480 21-35 31-52 175 1 6-350 MCM 12/0 LEMURE 8" X 8" X 1-3 1-5 35 1 #14-1/0 •• 277 CONCRETE POLE 6" CABINET (SIMILAR 277 I';''',';; :) #3 BASE. TO 'OB' DETAIL V. 2 0 �. • •.' ' � : ) 1-3 1-4 35 1 14-1 0 #3 PROVIDE 20A. 120V, 4-8 5-9 60 1 #14-1/0 #3 240 7-10 10-15 100 1 #14-1/0 #3 DUPLEX GFI OUTLET 11-18 16-29 175 (1) #1-500 MCM OR 2 1-250 MCM #3 208 1-2 1-4 35 1 #14-1/0 #3 IN CABINET.,�:. 3-5 5-8 60 1 #14-1/0 #3 •:.I 6-8 9-13 100 1 #14-1/0 1/4" STEEL U—BOLT (LEMURE CO. 9-15 14-23 175 (1) #1-500 MCM I , OR 2 1-250 MCM #3 •� C.2 E-• W ROD. VERIFY SIZE 310-830-1144) CD O BE I;; • PRIOR TO BOX INSTALLATION. SUFFICIENT GRADE/HARDSCAPE WORK MUST BE COMPLETED TO ALLOW DETAILED REVIEW. ENCOUNTERING SOIL FORMATIONS THAT WILL REQUIRE SPECIAL DESIGN ww CONSIDERATIONS OR EXCAVATION PROCEDURES MAY EXIST. POLE FOUNDATIONS MAY N® TO BE REANALYZED ACCORDING TO THE a 1" RIGID GALV. STEEL CONDUIT SOL CONDITIONS THAT EXIST. r1••;' . ,...:•:', SET TIGHT TO POLE. ACCORDINGLY. i; ;•' ALL PIERS AND CONCRETE BACKFILL MUST BEAR ON AND AGAINST FIRM. CO UNDISTURBED SOIL ALL EXCAVATION MUST BE FREE OF LOOSE SOIL, AND DEBRIS PRIOR TO p 36" FOUNDATION INSTALLATION AND PLACEMENT OF CONCRETE BACKFILL ��' .'•'' •�� CASING MAY BE REWIRED IF CAVING OCCURS rti d 02 E" ALL EXCAVATIONS MUST BE FREE OF WATER OR CONCRETE SI-IALL BE 91 PLACED WITH A TREMLE PIPE N ACCORDANCE WITH ACI STANDARD 304, �--� m -Cq CONCRETE BACKFILL SWILL HAVE A MINIMUM ULTIMATE COMPRESSIVEO, 0 GTH STRENAT 28 DAYS OF 3.000 PSL SPECIAL INSPECTION IS NOT V p 0 REQUIRED. C 173 USE TYPE I PORTLAND CEMENT OR AS RECOMMENDED BY THE GEOTECHNICAL ENGINEER. FINISH GRADE MIX N CONFORMANCE WITH ASTM C-94.(1• MAX. AGG% SRE). AGGREGATES PER ASTM C-33. PLACE CONCRETE IMMEDIATELY AFTER COMPLETION OF EXCAVATION AND INSPECTION BY THE GEOTECHNICAL ENGINEER AND THE GOVERNING Z BUILDING AUTHORITY. NO EXCAVATIONS SHALL BE LEFT UNPROTECTED O OR OPEN OVERNIGHT. CONCRETE SHALL BE PLACED N ONE CONTINUOUS OPERATION (NO CONSTRUCTION JOINT) WITH SPECIAL EQUIPMENT WITH A MAXIMUM T'.�.;'; FREEFALL OF 3 FT AND TO PREVENT CONCRETE FROM STRIKING THE WRAPPED RIGID = I I I �T ' •' a III rI CONDUIT TO I I=I CONCRETE BACKFILL SHALL ATTAIN A MINIMUM STRENGTH OF 2.000 PSI I : `'• '• : `•%� III PULLBOX•a a I ~" •� Or II =1III�III a ' iIII POLES. FIXTURES, PRECAST BASES, ELECTRICAL ITEMS, PLATFORMS. SPECIFICATIONS, AND INSTALLATION PER MUSCO LKEMTING. INC. — L1_ POLE FOUNDATION pp., SIDE VIEW Outlet Detail Underground Service Alert OR e o Call: TOLL FREE 1-800 r= 6- 422-4133 TWO WORKING DAYS = BEFORE YOU DIG N.T.S. came Homes Assembly Wtth Qutek connectors Ballast Cabinet Wire support . E!N conn ng to fbtme i support snap hook Handhole Cover Grade Line —Conduit Adaptor Plate With Access Hole, Below Grade (2 Sides) crossarm bol Ballast boxI Ballast Q Fuss III ICapacitor t Lamp 0 Taker ® @W. ution 1—e Fixtures - 35A/2P 7-12 F•uctures - 6OA/2P 173 Pole C.B. Provided.) UM M7DCI'OBB SM P= HT Bemm umma. (sae rale McfMrATUO POLE FOUNDATION SCHEDULE BALLAST CABINET — CIRCUIT BREAKER SCHEDULE FORCES (NAXIMM VOLTAGE SYSTEM PHASE METAL HALIDE 500W IOOOW # OF # OF FIXTURES FIXTURES MAX. AMP RATING LUG SIZE WIRE SIZE 480 W In = a W W = F- tr 0 W _j Z N 1-6 1-9 35 1 #14-1/0 #3 480 7-12 10-18 60 1 #14-1/0 #3 480 13-20 19-20 109 1 14-1 0 #3 480 21-35 31-52 175 1 6-350 MCM 12/0 277 1-3 1-5 35 1 #14-1/0 3 277 4-7 6-10 60 1 #14-1/0 3 277 8-12 11-18 109 1 J14-1/0 #3 277 13-20 19-31 175 1 6-350 MCM 2 0 240 1-3 1-4 35 1 14-1 0 #3 240 4-8 5-9 60 1 #14-1/0 #3 240 7-10 10-15 100 1 #14-1/0 #3 240 11-18 16-29 175 (1) #1-500 MCM OR 2 1-250 MCM #3 208 1-2 1-4 35 1 #14-1/0 #3 208 3-5 5-8 60 1 #14-1/0 #3 208 6-8 9-13 100 1 #14-1/0 #3 208 r 9-15 14-23 175 (1) #1-500 MCM I , OR 2 1-250 MCM #3 Handhole Cover Grade Line —Conduit Adaptor Plate With Access Hole, Below Grade (2 Sides) crossarm bol Ballast boxI Ballast Q Fuss III ICapacitor t Lamp 0 Taker ® @W. ution 1—e Fixtures - 35A/2P 7-12 F•uctures - 6OA/2P 173 Pole C.B. Provided.) UM M7DCI'OBB SM P= HT Bemm umma. (sae rale McfMrATUO POLE FOUNDATION SCHEDULE TIN FORCES (NAXIMM FJn'ORB 030EURAEON mum In =MARI[) CAISSON W= m KP-." =a M M YMM ()') M IRM EKBUM FM IS70-C 107.64 2.164 2.157 30" 14'-0" LS70-D 150.53 • 2.927 3.356 36" 16'-0" POLE IDENTIFICATION LACAT10r1 II= TM FJn'ORB 030EURAEON mum In =MARI[) FIX= BPA Sl, S4, S5, S8 IS70-C 9(5+4) 36.0 S2, S3, S6, S7 IS70-D 18(5+4/5+4) 54.0 is PB&CA,4! PHS F HASH BT Y09C0 1a�fG. INC. XT FOIL DIN •7 1;OACEM RAMZ CN3S0)1 111111M POra Fouffi Wr SCI owz g olo»S1vR® 3 -ma SM I PRM DRAM Mini RM —WAVE= DIAYB'M (SBE Pura MRlDeIIaEsr ) FOUNDATION DETAIL DIINAM Fauff Not To Scale o CONCRETE VAULT BOX SCHEDULE POLE WIRING SYSTEM WIRING SCHEMATIC 9011M L (Ballast Cabinet) MUSCa5 DETAIL A/B B/C A/C A/B B/C A/B B/C A/C A/B B/C A/C 1X PULLBOX NO. 1 WITH EXTENSION (24" DEEP) — BROOKS A/C A/B A/B B/C A/B B/C A/C O O THREE FIXTURES FOUR FIXTURES FIVE FIXTURES SIX FIXTURES PHASE A = 2 FIX. PHASE A = 3 FIX. PHASE A = 3 FIX. PHASE A = 4 FIX. PHASE B = 2 FIX. PHASE B = 3 FIX. PHASE B = 4 FIX. PHASE B = 4 FIX. PHASE C = 2 FIX. PHASE C = 2 FIX. PHASE C = 3 FIX. PHASE C = 4 FIX. TYPICAL WIRING OF FIXTURES WITH 30 DISTRIBUTION NO. 3X 32" X 44" (24" X 36" I.D.) X 24" DEEP — BROOKS NO. Musco Pole Assembly Details x CONCRETE MOW STRIP (4"W ALL ROUND X 2"D) BOLT DOWN CONCRETE LID WITH ENGRAVED WORD "SIGNAL" OR "POWER" TOP OF BOX TO BE FLUSH WITH FIN. GRADE FINISH GRADE BOND TOGETHER IF METAL CONDUIT N I I-1 I S • REINFORCED CONCETE BOX WITH •� Z =II I CONCRETE EXTENSION AS REQUIRED — IIIA �. �• a a • 3/4" PVC (FOR DRAINAGE) a a piei • °aa�•`tea a•� a a •• • • • ` �' •� �' ``• FEED PER SITE PLAN BOTTOM LID 12" GRAVEL SUMP * NOTE: WHERE VAULT BOX IS ADJACENT TO CONCRETE WALK. EXTEND MOWSTRIP TO CONNECT WITH WALK, N.T.S. Pull Box Details t N.T.S. THIS DRAWING IS A COPY OF THE SIGNED STRUCTURAL ENGINEERS CALCULATIONS GENERAL NOTES o CONCRETE VAULT BOX SCHEDULE NO. 1 19" X 12" (14" X 8" I.D.) X 12" DEEP — BROOKS NO. 9011M L r.r 1 PB. riX NO. 1X PULLBOX NO. 1 WITH EXTENSION (24" DEEP) — BROOKS Gcj 0 NO. 36 PBC ElNO. 2 18" X 28" (12 1/2" X 22" I.D.) X 12" DEEP — EEd�� O rn BROOKS NO. 38 PBC 2X E NO. 2X 22" X 35" (17" X 30" I.D.) X 29" DEEP WITH BOTTOM — BROOKS NO. G6PB. 3X NO. 3X 32" X 44" (24" X 36" I.D.) X 24" DEEP — BROOKS NO. Ci Lo XD 100 FHH. 4X N0. 4X 32' X 44" (24" X 36" I.D.) X 47" DEEP WITH BOTTOM a — BROOKS NO. 100 DAH. 5X NO. 5X 38" X 60" (30" X 42" I.D.) X 48" DEEP WITH BOTTOM — BROOKS NO. 200 FPB. ALL WITH BOLT DOWN CONCRETE LID OR "TL" (STEEL TRAFFIC LID) WHERE Z SHOWN AND ENGRAVED "ELECTRICAL". TRAFFIC LIDS FOR BOXES NO. REFERENCE CHAPTER 18. SECTION 1808.8.2.1 AND TABLE 18-1-A OF THE 1997 EDITION OF THE UNIFORM BUILDING CODE. 3 AND 4 SHALL BE TWO SECTION. TRAFFIC LID FOR BOX NO. 5 SHALL I BE TWO SECTION WITH COVER HOLD ASSEMBLY. U ICD ALL BOXES TO SET IN 12" COMPACTED GRAVEL BASE WIDTH X LENGTH OF BOX. C.2 E-• W ALL BOXES TO BE SET SQUARE WITH ADJACENT FEATURES. BOX LAYOUT TO CD O BE APPROVED BY OWNER ® LANDSCAPE ARCHITECT BASED ON FIELD REVIEW PRIOR TO BOX INSTALLATION. SUFFICIENT GRADE/HARDSCAPE WORK MUST BE COMPLETED TO ALLOW DETAILED REVIEW. Pull Box Details t N.T.S. THIS DRAWING IS A COPY OF THE SIGNED STRUCTURAL ENGINEERS CALCULATIONS GENERAL NOTES o 9011M r.r W ALL CONSTRUCTION AND WORKMANSHIP SWILL CONFORM TO THE Gcj 0 UNIFORM BUILDING CODE. 1998 EDITION. MIND :80 MPH (EXPOSURE C) EEd�� O rn A REFERENCE POLE LOCATION DPIAWING FOR ACTUAL POLE PLACEMENT AND SITE LOCATKON. _ THE CONTRACTOR 15 SOLELY RESPONSIBLE FOR ALL CONSTRUCTION Ci Lo XD PROCEDURES AND SAFETY CONDITIONS AT THE JOB SITE. co a ALLOWABLE END BEARING SOIL PRESSURE: 1.000 PSF ALLOWABLE LATERAL PASSIVE SOL BEARING PRESSURE: 200 PSF/FTCq Z REFERENCE CHAPTER 18. SECTION 1808.8.2.1 AND TABLE 18-1-A OF THE 1997 EDITION OF THE UNIFORM BUILDING CODE. W I U ICD DESIGN SOL PARAMETERS ARE AS NOTED. ACTUAL ALLOWABLE SOIL PARAMETERS MUST BE VERIFIED ON SITE. C.2 E-• W A GEOTECHNICAL ENGINEER SHALL BE AVAILABLE AT THE TIME OF CD O THE FOUNDATION INSTALLATION TO VERIFY THE SOIL DESIGN PARAMETERS AND TO PROVIDE ASSISTANCE IF ANY PROBLEMS ARISE C1 O N FOUNDATION INSTALLATION.rn ENCOUNTERING SOIL FORMATIONS THAT WILL REQUIRE SPECIAL DESIGN ww CONSIDERATIONS OR EXCAVATION PROCEDURES MAY EXIST. POLE FOUNDATIONS MAY N® TO BE REANALYZED ACCORDING TO THE a SOL CONDITIONS THAT EXIST. IF ANY DISCREPANCIES OR INCONSISTENCIES ARISE NOTIFY THE ENGINEER OF SUCH DSpZEPANCES FOUNOATIONS WILL THEN BE REVISED ACCORDINGLY. ALL PIERS AND CONCRETE BACKFILL MUST BEAR ON AND AGAINST FIRM. CO UNDISTURBED SOIL ALL EXCAVATION MUST BE FREE OF LOOSE SOIL, AND DEBRIS PRIOR TO p O LO -4 FOUNDATION INSTALLATION AND PLACEMENT OF CONCRETE BACKFILL p',CO CASING MAY BE REWIRED IF CAVING OCCURS rti d 02 E" ALL EXCAVATIONS MUST BE FREE OF WATER OR CONCRETE SI-IALL BE 91 PLACED WITH A TREMLE PIPE N ACCORDANCE WITH ACI STANDARD 304, �--� m -Cq CONCRETE BACKFILL SWILL HAVE A MINIMUM ULTIMATE COMPRESSIVEO, 0 GTH STRENAT 28 DAYS OF 3.000 PSL SPECIAL INSPECTION IS NOT V p 0 REQUIRED. C 173 USE TYPE I PORTLAND CEMENT OR AS RECOMMENDED BY THE GEOTECHNICAL ENGINEER. MIX N CONFORMANCE WITH ASTM C-94.(1• MAX. AGG% SRE). AGGREGATES PER ASTM C-33. PLACE CONCRETE IMMEDIATELY AFTER COMPLETION OF EXCAVATION AND INSPECTION BY THE GEOTECHNICAL ENGINEER AND THE GOVERNING Z BUILDING AUTHORITY. NO EXCAVATIONS SHALL BE LEFT UNPROTECTED O OR OPEN OVERNIGHT. CONCRETE SHALL BE PLACED N ONE CONTINUOUS OPERATION (NO CONSTRUCTION JOINT) WITH SPECIAL EQUIPMENT WITH A MAXIMUM FREEFALL OF 3 FT AND TO PREVENT CONCRETE FROM STRIKING THE SIDES OF THE EXCAVATION. VIBRATE TOP 5 FT. CONCRETE BACKFILL SHALL ATTAIN A MINIMUM STRENGTH OF 2.000 PSI rX' PRIOR TO POLE INSTALLATION. a o A2111113ueIIEaIs FIXTURES MUST 13E LOCATED TO MAINTAIN 10'-0• MINIMUM HORIZOWAL CLEARANCE FROM ANY OBSTRUCTKK POLES. FIXTURES, PRECAST BASES, ELECTRICAL ITEMS, PLATFORMS. SPECIFICATIONS, AND INSTALLATION PER MUSCO LKEMTING. INC. FIXTURE: EPA - 4.0 WEIGHT - 25 LBS (PER MUSCO LIGHTING, NCJ pp., Musco Pole Foundations AREA LIGHT +22' (FIELD D ES -3 LLAST BINETS 1LLAST kBINETS N.T.S. E 120V OUTLET ES -3 �— FOOTING. SEE STRUCTURAL DRAWINGS (TYPICAL) POLES S1. S4. S5, S8 POLES S2. S3. S6. S7 70' POLE 70' POLE Pole Configurations N.T.S. / LEXAN LENS / f 'AREA LIGHT FIXTURE: DELTA: #FLA-250HPS 277V —LEX —BLACK / WITH CAST GUARD (WITH LEXAN LENS) / WIREWAY 2-3/8" HUB COVER 2 — 3 /8" DIA. GALV . REDUCER PLATE 0 BY CONTRACTOR (COORDINATE W/FIXTURE MF'G EXACT SIZE) MOUNTING BRACKET BY MUSCO L t6" - MOUNTING ARM BY MUSCO ---- —� AT +22' GROUNDING KIT BY MASCO I 11" MOUNTING BACK PLATE BY 1 MUSCO LIGHTING POLE HANDHOLE r:• i� ` ,_•r = ,•-r _w ENj- Area Lights -fla: EE 7=3 � 9/30�� N.T.S. F Cr C�`\E� . IJV wMC, WO. ZZ9l 5#F -E7" NO. &4F,?6