HomeMy WebLinkAbout5646-21ELECTRICAL NOTE5 AND SPEC I � I CATI O 5 U 1. USE OF LIQUID -TIGHT FLEXIBLE METAL CONDUIT OR LIQUID NON - GENERAL zW� NOT BE PLIN61Pr ENUMS. IN ENVIRONMENTAL AIR PLENUMS, 00 INGLUD N6 RETURN AIR GESHALL 1. CONTRACTOR SHALL PERFORM ALL WORK A5 TO CONFORM TO LOCAL, 8. EXGEPT FOR SURFACE METAL AND SURFACE NON-METALLIG, ALL STATE AND NATIONAL CODES AND THE REQUIREMENTS OF LOCAL O�t� RA( EHAY5 SHALL BE INSTALLED GONGEALED WITH THE EXCEPTION OF AUTHORITIES HAVIN6 JURI5DIGTION. l BOILER ROOMS, UTILITY ROOMS, 6ARA6E5 AND OTHER AREAS a� O Vr 5PEGIFIGALLY APPROVED BY THE ARCHITECT. 2. CONTRACTOR TO EXAMINE THE 51TE TO DETERMINE THE EXACT QU CONDITIONS EFFECTING THE ELECTRICAL WORK. CONDUCT®R5 3. PRANIN65 INDICATE THE 6ENERAL 5GHEME OF THE INSTALLATION AND ARE DIA6RAMMATIG IN SCOPE. THE ENGINEER RESERVES THE RIGHT 1. UNLESS OTHERN15E NOTED, CONDUCTOR TYPES SHALL BE A5 INDICATED TO CHANGE THE LOCATION OF OUTLETS, CONDUIT, EQUIPMENT, BELOW: APPARATUS, ETC. TO A REASONABLE EXTENT AS THE BUILDIN6 LOCATION CONDUCTORS CONDITIONS MAY DICTATE PRIOR TO THEIR INSTALLATION WITHOUT EXTRA C05T TO THE OWNER. THE EXACT LOCATION AND ARRANGEMENT I. BRANCH CIRCUITS AND FEEDERS THHN/THWN OF ALL EQUIPMENT AND PARTS SHALL BE DETERMINED AS THE WORK IN CONDUIT PRO6RE55E5. 4. DETAILS OF CONSTRUCTION AND OF WORKMAN5HIP WHERE NOT 2. CONGEALED BRANCH CIRCUITS TYPE "AG" GABLE SPECIFICALLY DESCRIBED HEREIN OR INDICATED ON THE DRAWINGS 2A. CONGEALED BRANCH CIRCUITS SHALL BE SUBJECT TO THE ENGINEER'S APPROVAL. IT 15 THE INTENT IN DWELLING UNITS ONLY: TYPE "NM" GABLE OF THESE SPECIFICATIONS TO PROVIDE COMPLETE SYSTEMS, LEFT IN GOOD WORKING ORDER, READY FOR OPERATION. 3. UNDERGROUND OUTDOORS RHW/THW/THWN 5. SCRAP AND DEBRIS, EXCEPT A5 OTHERWI5E SPECIFIED, SHALL BE 4. UNDERGROUND SERVICE ENTRANCE RHWN5E REMOVED FROM THE 51TE AND 015PO5ED OF BY THI5 CONTRACTOR. 5. FIXTURE CONNECTIONS 517-2 6. THE CONTRACTOR SHALL BE RE5PON51BLE FOR START-UP OF ALL SYSTEMS. 6. TEMPORARY LI6HT AND POWER TYPE "NM" GABLE 1. ALL WORK SHALL BE DONE WITH A MINIMUM OF DUST AND DIRT. 2. ALL WIRE AND GABLE SHALL BE COPPER GONDUGTOR5. CONDUCTORS PROVIDE SUFFICIENT FIREPROOF TARPAULINS AND COVER ALL #IOAW6 AND SMALLER MAY BE SOLID. CONDUCTORS LARGER THAN EQUIPMENT IN WORK AREA WITH SAME DURIN6 WORK OPERATIONS. #IOAW6 SHALL BE STRANDED. 8. CONTRACTOR SHALL FURNISH SHOP DRAWIN65 AND EQUIPMENT GUTS TO 3. CONDUCTORS #8AW6 AND SMALLER MAY BE SPLICED U51N6 NYLON 5ELF- THE ARCHITECT FOR APPROVAL (MINIMUM (5) COPIES). INSULATED WIRE NUTS A5 MANUFACTURED BY 3M "5GOTHLOK", IDEAL "WIRE -NUT" OR APPROVED EQUAL. q. COORDINATE CONNECTIONS TO STREET WITH LOCAL UTILITY GOMPANY(5). 4. GONDUGTOR5 LAR6ER THAN #8AW6 5HALL BE SPLICED U51N6 SPLIT BOLT CONNECTORS WITH TAPED JACKET, PREMANUFAGTURED SPLICES BY IL5GO 10. CONTRACTOR SHALL FILE, SECURE AND PAY FOR ANY NECESSARY OR MAG PRODUCTS OR BY HYDRAULICALLY APPLIED COMPRESSION APPROVALS, PERMITS AND INSPECTIONS. SPLICES. MANUFACTURERS TOOLING, DYES AND REGOMMENDATION5 SHALL 6OVERN HYDRAULICALLY APPLIED GOMPRE55ION SPLICES. 11. ALL WORK SHALL BE 6UARANTEED TO BE FREE FROM DEFECT FOR ONE YEAR AFTER ACCEPTANCE OF WORK. 5. EXCEPT WHERE EQUIPMENT, 5UGH A5 MOLDED CASE CIRCUIT BREAKERS ARE SUPPLIED WITH FACTORY INSTALLED SET SCREW LU65, ALL 12. ALL WORK BE IN STRICT CONFORMANCE WITH THE STATE OF NEW CALIFORNIA CONNECTIONS FOR GABLES 4/0 AND LARGER SHALL BE MADE U51N6 NEMA FIRE GODS, THE CALIFORNIA ELECTRIC GODS AND 2 BOLT GOMPRE55ION LU65. LU65 SHALL BE HYDRAULICALLY APPLIED THE CALIFORNIA BUILDIN6 GODS U51N6 MANUFACTURER'S TOOLING, DIES AND RECOMMENDED PROCEDURES. 13. PRIOR TO TE5TIN6, CONTRACTOR SHALL MAKE ALL SYSTEM ADJUSTMENTS 6. CONTROL WIRIN6 FOR HVAG EQUIPMENT UTILIZING CONTROL CIRCUIT REQUIRED FOR PROPER OPERATION. ADJUSTMENTS SHALL INCLUDE VOLTA5E5 OF LE55 THAN 60VAG SHALL BE #16AW6 MULTI-GONDUGTOR TRANSFORMER TAPS, CIRCUIT BREAKER MA6NETIG 5ETTIN65, GROUND NEG TYPE "GLT. WHEN INSTALLED IN ENVIRONMENTAL AIR PLENUMS, FAULT RELAY TRIP 5ETTIN65, BALLAST TAP 5ETTIN65, ETC. LOW VOLTA6E CONTROL WIRIN6 SHALL BE NEG TYPE "GL2P". LOW VOLTA6E CONTROL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH 14. CONTRACTOR TO COORDINATE TEST WITH LOCAL OFFICIALS. NEG ARTICLE #125. 15. CONTRACTOR SHALL BE RESPONSIBLE FOR D15GONNEGTIN6 AND MAKING 1. CONTROL WIRING FOR HVAC EQUIPMENT AND OTHER EQUIPMENT SAFE ALL ELECTRICAL FACILITIES IN EXI5TIN6 5TRUGTURE PRIOR TO UTILIZING 120V CONTROL SHALL BE #14AW6 TYPE THHN/THWN DEMOLITION. INSTALLED IN RAGEWAY5. 8. WHERE 150LATED GROUND RECEPTACLES ARE INDICATED ON THE RACEWAY5 DRAWINGS, IN5TALLED AN INSULATED (6REEN) 6ROUND CONDUCTOR WITH THE BRANCH CIRCUIT. IN CONGEALED LOCATIONS, TYPE "MG" GABLE I. UNLE55 OTHERN15E NOTED, RAGEWAY TYPES SHALL BE A5 INDICATED SHALL BE UTILIZED FOR SUPPLY OF 150LATED GROUND OUTLETS. BELOW: q. UNLE55 OTHERN15E INDICATED ON THE DRAWIN65, ALL BRANCH LOCATION RAGEWAY CIRCUITS AND HOME RUNS ARE 2 #12AW6. I. OUTDOORS, ABOVE GRADE GALVANIZED RI610 STEEL (6R5) 10. ADJUST BRANCH CONDUCTOR SIZES A5 REQUIRED FOR VOLTA6E DROP. MAXIMUM BRANCH CIRCUIT LENGTHS SHALL BE AS FOLLOWS UNLE55 OTHERWI5E NOTED: 2. INDOOR FEEDERS AND ELECTRICAL METALLIC TUBIN6 (EMT) 5UBFEEDER5 NOT EXP05ED #12 #10 #8 TO PHYSICAL DAMAGE 120V, I PHASE, ISA 55' 85' 125' 3. INDOOR BRANCH GIRGUIT5 ELECTRICAL METALLIG TUBIN6 (EMT) 120V, I PHASE, 20A 40' 65' q5' EXPOSED IN UTILITY 208V, I PHASE, 20A 65' 110` 115' AREAS 208V, 3 PHASE, 20A 15' 125' 200' 4. INDOOR BRANCH CIRCUITS (SEE CONDUCTORS) THE ABOVE LEN6TH5 REPRESENT "ONE-WAY" CIRCUIT LENGTH (NOT WIRE CONGEALED LEN6TH) AND INCLUDE ALL VERTICAL R15E5 AND DROPS. 5. INDOOR FIXTURE AND FLEXIBLE METALLIG CONDUIT 11. CONDUCTOR IN5ULATION5 SHALL BE COLOR CODED A5 FOLLOW5: VIBRATING EQUIPMENT CONNECTIONS 12O/ E PHASE A BLUE 6. INDOOR AND OUTDOOR LIQUID -TIGHT FLEXIBLE METAL MOTOR GONNECTION5 CONDUIT PHASE B RED 1. MOTOR CONNECTIONS IN FLEXIBLE METAL CONDUIT PHASE G BLACK ENVIRONMENTAL AIR PLENUMS NEUTRAL WHITE 8. UNDER6ROUND TYPE "DB", 5GHEDULE 40 RI611) GROUND 6REEN (PVC), NON METALLIC CONDUIT WHERE CONDUCTORS ARE NOT AVAILABLE WITH COLOR CODED q. UNDER6ROUND PENETRATION 6ALVANIZED R1610 STEEL (6R5) INSULATION, APPLY COLORED TAPES TO THE ENTIRE EXP05ED LEN6TH THRU GRADE OF GABLES IN PULL BOXES, 5WITGHBOARD5, EQUIPMENT, ETC. 2. GALVANIZED R1610 STEEL CONDUIT SHALL BE MANUFACTURED IN 12. CONTROL GABLE CONDUCTORS SHALL BE COLOR CODED IN ACCORDANCE ACCORDANCE WITH AN51 #G80.1 AND UL #6. INSTALLATION OF WITH IGEA STANDARDS. GALVANIZED RIGID STEEL CONDUIT SHALL BE IN STRICT CONFORMANCE WITH NEG ARTIGLE #346. 3. EMT SHALL BE MANUFACTURED IN ACCORDANCE WITH AN51 #G80.3 AND f3OxE5 UL #1q1. INSTALLATION OF ELECTRICAL METALLIC TUBING SHALL BE IN STRICT CONFORMANCE WITH NEG ARTICLE #348. BENDIN6 RADIUS I. BOXES FOR BRANCH CIRCUIT WIRING DEVICES AND BRANCH CIRCUIT SHALL NOT BE LE55 THAN NEC, TABLE #346-10. SUPPORT 5PAGIN6 5PLIGE5 SHALL BE A5 INDICATED BELOW: SHALL NOT EXCEED 10'-0". ALL EMT COUPLIN65 AND CONNECTORS SHALL BE OF THE GONGRETE-TIGHT AND RAIN-TI6HT TYPE. SET FLUSH WIRIN6 DEVICES RAGO #112/113/114 5GREW CONNECTORS SHALL NOT BE USED. ON METAL STUDS (4" SQUARE) 4. FLEXIBLE METAL CONDUIT SHALL BE MANUFACTURED IN ACCORDANCE FLUSH HIRING, DEVIGE5 RAGO #504/565 WITH UL #I. INSTALLATION OF FLEXIBLE CONDUIT SHALL BE IN ON WOOD STUDS 6AN6ABLE 5TRIGT CONFORMANCE WITH NEG #350 AND SHALL BE LIMITED TO 61- 0" MAXIMUM LEN6TH5 FOR CONNECTIONS TO L16HTIN6 FIXTURES AND FLUSH WIRING DEVIGE5 RAGO #6qO VIBRATING EQUIPMENT. BENDIN6 RADIUS FOR FLEXIBLE METAL IN MA50NRY WALLS (I 6AN6) CONDUIT SHALL NOT BE LESS THAN TH05E PERMITTED FOR CONDUCTOR BENDIN6 RADIUS. CONNECTORS FOR FLEXIBLE METAL CONDUIT SHALL 6AN6 BOXES RAGO #g51/g53/q55/q54/q55 BE OF SINGLE 5GREW, MALLEABLE IRON CLAMPING TYPE (THOMAS t BETTS SERIES #250). FLEXIBLE METAL CONDUIT AND CONNECTORS GEILIN6 BAR BOX RAGO #280/ql1 SHALL BE UL LISTED AND APPROVED FOR SHEATH GROUNDING FOR (HUNG GEILIN6) BRANCH CIRCUITS OF 20A OR LE55 IN LEN6TH5 NOT TO EXCEED 61- 01'. PROVIDE A 6ROUNDIN6 CONDUCTOR 51ZED TO MEET NEG TABLE GEILIN6 BAR BOX RAGO #326 250-q4 WHERE A CIRCUIT OVERGURRENT PROTECTION EXCEEDS 20A. (WOOD JOIST) 5. LIQUID-TI6HT FLEXIBLE METAL CONDUIT SHALL BE INSTALLED IN SURFACE WIRING DEVICE PAGO #Iq2 STRICT CONFORMANCE WITH NEG ARTICLE #351 AND SHALL BE LIMITED (DRY AREAS) (4" 5QUARE) TO 3'-0" LEN6TH5 FOR CONNECTIONS TO MOTORS, OUTDOOR VIBRATIN6 EQUIPMENT AND OTHER EQUIPMENT IN NET AREAS. LIQUID-TI6HT SURFACE WIRING DEVIGE5 BELL 210 -L/213 -L FLEXIBLE METAL CONDUIT AND FITTIN65 SHALL BE APPROVED FOR (WET ARE5, 16AN6) (F.5. TYPE 6ROUNDIN6 PURPOSES. PROVIDE A SEPARATE EXTERNAL BONDING GONDUGTOR WHERE ANY OF THE FOLLOWING CONDITIONS EXIST: SURFACE WIRING DEVIGE5 BELL 216-4L/ 211-4L (WET AREAS, 2 6AN6) (F.5. TYPE) A. CONDUIT 51ZE EXCEED 1 1/4" TRADE SIZE. THE ABOVE MODEL NUMBERS ARE TYPICAL OF THE PRODUCTS REQUIRED. B. 1/2" CONDUIT HOUSES A CIRCUIT PROTEGTED IN EXGE55 OF 20A. CONTRACTOR SHALL ADJUST MODEL NUMBERS A5 REQUIRED TO SUIT JOB CONDITIONS, WALL THICKNESS, DEVICE REQUIREMENTS, ETC. G. 3/4" THRU 1 1/4" CONDUIT HOUSES A CIRCUIT PROTECTED IN EX( E55 OF 60A, 2. PULL AND JUNCTION BOXES SHALL BE CODE 6AU6E ENAMELED STEEL, NEMA "I" WITH 5GREW FASTENED COVERS WHEN USED IN INDOOR, DRY FITTIN65 FOR LIQUID -TIGHT FLEXIBLE METAL GONDUIT SHALL BE AREAS. STEEL 6AU6E SHALL BE IN ACCORDANCE WITH NEG ARTICLE THOMAS $ BETTS "VER5A-6ROUND" WITH OR WITHOUT EXTERNAL GROUND #310-G. LUG AS REQUIRED ABOVE. 3. PULL AND JUNCTION BOXES UTILIZED IN INDOOR AREAS WHICH MAY 6. INTERMEDIATE METAL CONDUIT, MANUFACTURED IN ACCORDANCE WITH BECOME DAMP (BOILER ROOM, UTILITY ROOMS, CONNECTIONS TO UL # 1242 MAY BE SUBSTITUTED FOR 6ALVANIZED RI61D STEEL UNDER6ROUND RAGEWAY5, ETC) SHALL BE 6ALVANIZED TYPE NEMA "I". CONDUIT IN ABOVE 6RADE, INDOOR APPLICATIONS. IMG SHALL NOT BE PERMITTED IN OUTDOOR ABOVE OR BELOW 6RADE APPLICATIONS. 4. PULL AND .UNCTION BOXES FOR USE OUTDOORS SHALL BE GALVANIZED ALL OTHER REQUIREMENTS FOR 6ALVANIZED RIC -710 STEEL CONDUIT AND OF NEMA "31R" CONSTRUCTION. SHALL APPLY. 5. ALL PULL BOXES FASTENED TO EXTERIOR BLOCK OR MA50NRY WALLS and Service Alert SHALL BE PROVIDED WITH 11/2" CHANNEL FRAMING 5PAGER5 ORIENTED VERTICALLY AT REAR OF ENCLOSURE TO ENSURE AIR CIRCULATION at least 2 days BEHIND ENCLOSURE. 6. OUTLET, 5WITGH AND JUNCTION BOXES FOR BRANCH CIRCUIT WORK SHALL BE 51ZED IN ACCORDANCE WITH NEG #310-6. 1. PULLBOXE5 AND LARGER JUNCTION BOXES 5HALL BE 51ZED IN ACCORDANCE WITH NEG ARTICLE #310-18. 8. WHERE USE OF KNOCKOUTS 15 015GONTINUED BY GHAN6E5 IN THE WORK, INSTALL PROPERLY 51ZED KNOCKOUT 5EAL5 BY THOMAS AND BETTS, RAGOR, APPLETON OR EQUAL. WIRING DEVIGE5 I. ALL WIRING DEVICES SHALL BE SPECIFICATION 6RADE. UNLE55 OTHERN15E INDICATED. NOTE TO PREPARER: THE FOLLOWING WIRIN6 DEVIGE5 ARE RECOMMENDED. DELETE DEVICES NOT REQUIRED FOR PROJECT. MODEL NUMBERS IN PARENTHESIS DE516NATE "DECORATOR" STYLES. CH005E STANDARD OR DECORATOR. 2. UNLE55 OTHERN15E INDICATED ON THE DRAWIN65, WIRING DEVICES SHALL BE AS SPECIFIED BELOW OR APPROVED EQUAL: DEVICE MANUFACTURER 4 MODEL NUMBER DUPLEX RECEPTACLE LEVITON #5362 125V, 20A, GROUNDED NEMA #5-20R 6FG1 REGEPTAGLE LEVITON #65gq 125V, GROUNDED NEMA #5-15R T066LE 5WITGH, I POLE (TOGGLE TYPE) LEVITON #5521 120/211V, 20A (KEY TYPE) LEVITON #1221-L TO661 E 5WITGH, I POLE (TO6(2LE TYPE) LEVITON #522(b W/ PILOT LIGHT 125V, 15A T066LE 5WITGH, 2 POLE 066LE TYPE) #5522 120/211V, 20A (KEY TYPE) LEVITON #1222-1 T066LE 5WITGH, 3 WAY (T066LE TYPE) LEVITON #5523 120/211V, 20A (KEY TYPE) LEVITON #1223-L FAN SPEED CONTROL LUTRON #NTF5-12E 120V, 12A, I POLE LINEAR SLIDE 5WITGH (I POLE) LUTRON #NT-IP5 120/211V, 20A (3 WAY) LUTRON #NT -3P5 (4 WAY) LUTRON # NT -4P5 3. WHERE 51N6LE POLE, 3 -WAY OR 4 -WAY STITCHES ARE GROUPED WITH DIMMER5 OR FAN SPEED CONTROLS, PROVIDE LINEAR SLIDE 5WITGHE5 BY LUTRON A5 SPECIFIED ABOVE. PROVIDE MULTI-6AN6 GOMMON WALLPLATE BY LUTRON. INDIVIDUALLY MOUNTED CONTROLS SHALL NOT BE ACCEPTED. CONTRACTOR SHALL DERATE DIMMER5 IN ACCORDANCE WITH MANUFAGTURER'5 PROCEDURE FOR 6AN6ED INSTALLATIONS. 4. WHERE GANGED RECEPTACLES INGLUDE A 6ROUND FAULT CIRCUIT INTERRUPTER, PROVIDE DECORATOR STYLE CONVENIENCE OUTLETS AND MULTI-6AN6 DECORATOR GOVERPLATE. 5. WIRIN6 DEVICE MOUNTING HEI6HT5 SHALL BE A5 FOLLOWS: DEVICE MOUNTING HE16HT REGEPTAGLE5 (6ENERAL AREAS) 1"-5' A.F.F. TO BOTTOM RECEPTACLES (ABOVE COUNTERS) 6" ABOVE BAGK5PLA5H RECEPTACLES (UTILITY AREAS) 4'-0" A.F.F. TO TOP L16HT 5WITGHE5 (ALL AREAS) 4'-0" A.F.F. TO TDP THERM05TAT 4 HVAC CONTROLS 4'-0" TO TOP MOUNTING HE16HT5 FOR OTHER DEVICES NOT SPECIFIED ABOVE SHALL BE IN ACCORDANCE WITH NJAG #5:23-1, "BARRIER FREE 5UBGODE". 6. ALL OUTLETS INSTALLED WITHIN 6-0" OF SINKS OR LAVATORIES SHALL BE PROVIDED WITH 6ROUND FAULT PROTECTION OR 6ROUND FAULT FEED THRU. 1. ALL REGEPTAGLE5 IN TOILET ROOMS SHALL BE PROVIDED WITH 6ROUND FAULT PROTECTION OR GROUND FAULT FEED THRU. 8. ALL RECEPTACLES INSTALLED IN UNFIN15HED BASEMENTS, 6ARA6E5, GRAWL 5PAGE5 AND OUTDOORS AT 6RADE SHALL BE PROVIDED WITH GROUND FAULT PROTECTION OR GROUND FAULT FEED THRU. q. GOVERPLATE5 FOR SURFACE MOUNTED WIRING IN UTILITY AREAS SHALL BE OF THE RAISED COVER TYPE AS MANUFACTURED BY MULBERRY, RAGO OR APPROVED EQUAL.. 10. GOVERPLATE5 FOR WEATHERPROOF DUPLEX RECEPTACLES SHALL BE BELL #223-V WITH 6A5KET. GOVERPLATE5 FOR WEATHERPROOF 5WITGH SHALL BE BELL #224-V WITH 6A5KET. 11. ALL 5WITGHE5 SHALL BE MOUNTED AT THE STRIKE SIDE OF DOORS. COORDINATE FINAL DOOR 5WIN65 WITH THE ARCHITECTURAL DRAWIN65. 12. WHERE OUTLETS ARE LOCATED IN COLUMN CLOSURES, PANELED WALLS, GU5TOM CABINETS, ETC. COORDINATE WITH ARCHITECTURAL ELEVATION DRAWI N65 TO ENSURE THAT OUTLETS ARE CENTERED IN PANELS AND LOCATED ON FLAT PANELS. LIGHTING 1. COORDINATE FIXTURE LOCATIONS WITH INSTALLED DUGTWORK, SPRINKLERS, ARCHITECTURAL SOFFITS, ETC. 2. FIXTURES INSTALLED IN CLOSETS SHALL COMPLY WITH NEG ARTICLE #410-8 FOR LOGATION AND TYPE OF CONSTRUCTION. 3. ALL FIXTURES WEIGHING IN EXGE55 OF 50# SHALL BE SUPPORTED INDEPENDENTLY OF THE OUTLET BOX (NEG #410-16(A)). 4. WHERE TROFFERS ARE INSTALLED IN SUSPENDED GEILIN65, FIXTURES SHALL BE 5EGURELY FASTENED TO GRID WITH CONGEALED BOLTS, 5GREW5, RIVETS OR TEE BAR GLIP5. WHERE GEILIN6 SUPPORT 15 NOT ADEQUATE ONE WIRE IN EACH CORNER OF THE FIXTURE), SUPPORT FIXTURE HOU5IN6 INDEPENDENTLY OF THE 6RID. 5. WHERE FIXTURES ARE PENDANT MOUNTED OR CHAIN HUNG, SUPPORTS SHALL BE ADEQUATE TO HOLD THE WEIGHT OF THE FIXTURE PLUS 250#. 6. FIXTURE HOU51N6 SHALL NOT BE USED A5 RAGEWAY5, EXCEPT THOSE DE516NED FOR INSTALLATION IN CONTINUOUS ROW5. MAKE BRANCH CIRCUIT SPLICES IN 4" SQUARE BOXES WITH BLANK COVER PLATES (NEC, #410-31). 1. ALL BALLASTS FOR FLUORESCENT, BIAX AND OGTRON LAMPS SHALL BE OF THE RAPID START, GLA55 "P", THERMALLY PROTECTED, HIGH POWER FACTOR, ENER6Y SAVING TYPE AS MANUFACTURED BY GENERAL ELECTRIC, UNIVERSAL, ADVANCE OR APPROVED EQUAL. BALLA5T5 SHALL BE UL LISTED, GBM CERTIFIED AND GARRY A MINIMUM 2 YEAR WARRANTY. 8. ALL GEILIN6 PENDANT MOUNTED AND WALL BRACKET MOUNTED FIXTURES SHALL BE PROVIDED WITH DECORATIVE CANOPIES MATGHIN6 THE FIXTURE AND PENDANT FINISH. q. ALL REGE55ED INGANDE5GENT FIXTURES SHALL BE THERMALLY PROTECTED. 10. REGE55ED FIXTURES SHALL MAINTAIN A MINIMUM CLEARANCE OF 1/2" TO COMBUSTIBLE CONSTRUCTION AND 3" TO THERMAL INSULATION UNLE55 UL LISTED FOR DIRECT CONTACT WITH THESE MATERIALS (NEC, #410-66 (A) 4 (B)). II. CONNECTIONS TO FLUORE5GENT TROFFERS SHALL CONSIST of HI6H TEMPERATURE WIRING (SEE CONDUCTOR) IN FLEXIBLE METAL CONDUIT. CONNECTION SHALL NOT BE LE55 THAN 4, NOR 6REATER THAN 6' IN LENGTH. 12. ALL BALLA5T5 FOR REGE55ED HID FIXTURES SHALL BE UL L15TED AND SHALL BE THERMALLY PROTECTED. 13. PROTECT ALL LAMPS, LEN5E5 AND LOUVERS DURIN6 CONSTRUCTION. ALL LAMPS, FIXTURE HOU51N6, LENSES AND LOUVERS SHALL BE GLEANED UPON COMPLETION OF WORK BY ALL TRADES. REPLACE DEFECTIVE OR DAMAGED LAMPS, LENSES, LOUVERS AND BALLASTS AS REQUIRED AT THE TIME OF GLEANIN6. 14. WHEN 5HOWN ABOVE DOOR, EXTERIOR BUILDIN6 MOUNTED LIGHTING AT E6RE55 DOORS SHALL BE MOUNTED WITH THE BOTTOM WITH THE BOTTOM OF THE FIXTURE AT 6" ABOVE DOOR GA5TIN6. LIGHTING SHALL BE MOUNTED ON STRIKE 51DE OF DOOR WITH TOP OF FIXTURE ALIGNED WITH THE TOP OF THE DOOR. 16. ALL FLUORESCENT FIXTURES IN UNHEATED ROOMS OR AREAS SHALL BE PROVIDED WITH RAPID START LAMP/13ALLA5T GOMBINATION5 SUITABLE FOR 5TARTIN6 AT 0 DE6REE5 F. 11. BALLASTS FOR HID FIXTURES SHALL BE POWER FACTOR CORRECTED. PANELE30ARD5 AND CIRCUIT 5REAKER5 I. EQUIPMENT INTERRUPTIN6 RATINC75 5HOWN ON 5GHEDULE5 ARE BASED ON UL L15TED SERIES RATIN6 FOR 50,000A AVAILABLE SHORT CIRCUIT CURRENT AT THE 5ERVIGE. CONTRACTOR SHALL INCREASE INTERRUPTING RATIN65 A5 REQUIRED FOR NON-5ERIE5 RATED EQUIPMENT. 2. PANELBOARD5 SHALL BE OF DEAD FRONT GON5TRUGTION WITH AUTOMATIC OVERGURRENT DEVIGE5. VOLTAGE AND CURRENT RATINGS AS SHOWN. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE UNLE55 OTHERWI5E NOTED. PANELBOARD5 SHALL BE UL L15TED A5 MANUFACTURED BY SQUARE D, 6E OR WE5TIN6HOU5E. 3. ALL CIRCUIT BREAKERS 5UPPLYIN6 HVAG EQUIPMENT SHALL BE UL LISTED TYPE HAGR. 5AFETY 5WITCHE5 I. SAFETY 5WITGHE5 SHALL BE GENERAL DUTY, FUSED OR UNFUSED, RATINC75 A5 5HOWN ON THE DRAWIN65. 2. ALL 5WITGHE5 SHALL BE QUICK -MAKE, QUIGK-BREAK OPERATION AND SHALL HAVE PADLOGKING PROVISIONS. 3. ALL 5WITGHE5 SHALL BE FURNISHED IN NEMA ENGLO5URE5 SUITABLE FOR USE IN THE LOCATION SHOWN. 5WITGHE5 SHALL BE A5 MANUFACTURED BY SQUARE D, 6ENERAL ELECTRIC, WE5TIN6HOU5E OR EQUAL. ELECTRICAL (NOT ALL 5YMBOL5 ARE USED) WIRIN6 DEVIGE5 Q DUPLEX CONVENIENCE RECEPTACLE 120V, 20A, GROUNDED 67FQ, DUPLEX GONVENIENGE RECEPTACLE 120V, 20A, GROUNDED, WITH INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER, TEST AND RESET CONTROLS WP Q DUPLEX CONVENIENCE RECEPTACLE 120V, 20A, GROUNDED, WITH WEATHERPROOF BOX AND 6A5KETED COVER QUAD CONVENIENCE RECEPTACLE (TWIN DUPLEXES WITH 2 GANG BOX AND COVER PLATE) 120V, 20A, GROUNDED TOGGLE 5WITGH 120V, 20A 3W: INDIGATE5 3 WAY 5WITGH 4W: INDIGATE5 4 WAY 5WITGH 2P: INDIGATE5 2 POLE 5WITGH P: INDIGATE5 5WITGH 4 PILOT L16HT K: INDICATED KEY OPERATED 5WITGH INDICATES (ONE PER LETTER) i�AGEWAY/WIRING Q��G UAL 5WITGHE5 IN GANG BOX. JQ JUNCTION BOX ` BRANCH CIRCUIT WIRING. SMALL 5LA5HE5 INDICATE NUMBER OF PHASE CONDUCTORS. LARGE SLA5HE5 INDICATE NUMBER OF NEUTRAL CONDUCTORS. EXPOSED OR CONGEALED CONDUIT RUN BRANCH CIRCUIT HOME RUN --- EM$EDDED OR BURIED CONDUIT -o CONDUIT TURNING UP CONDUIT TURNING DOWN O WIRIN6 TROUGH WITH 5GREW COVERS, DIMENSIONS A5 5HOWN PROTEGTI VE DEVIGE5 O FLUSH PANELBOARD PP: POWER PANEL LP: LIGHTING PANEL LVGP: LOW VOLTAGE CONTROL PANEL O SURFACE PANELBOARD PP: POWER PANEL LP: 1_16HTIN6 PANEL LVGP: LOW VOLTAGE CONTROL PANEL SAFETY 5WITGH, VOLTS, AMPS, POLES, FUSED OR UNFUSED AS NOTED MEGHAN I GAL EQUIPMENT DHN. 0 DOMESTIC, WATER HEATER, VOLTAGE 4 KW AS INDICATED UNIT HEATER WITH LOCAL 015GONNEGT 5WITGH GAB I NET HEATER EF (4 EXHAUST FAN O THERM05TAT (LINE OR LOW VOLTAGE) M15G. TGE:] TIME CLOCK, 120V, 20A, THREE POLE, ASTRONOMICAL TYPE CONNECT TO EXISTING Q TRANSFORMER li�_]MOTOR JEA LINWOOD ENGINEERING ASSOCIATES, P.C. Consulting Mechanical & Electrical Engineers 151 Kalmus Drive Suite B-200 Costa Mesa, California 92626 t: 714.424.0001 f: 714.424.0004 955 Lincoln Avenue Glen Rock, New Jersey 07452 t: 201.857.3998 f: 201.857.3994 www.linwoodengineering.com W � OSA° n� W �� 0 a U CL H pp O �,c Zw z (% LU F- Cf) z W O (- �. 0 0 Q �zU J LL a Q U o U L n,*, IL F- C/) U0 wz J LJ Q Adam C. Forni, P.E. CA # E18607 I? FESS/ �fCTR�OP� 9TF CF C'k �EOEL EXP. 12/31/14 PLAN CHECK # DATE 1/10/14 JOB # 13-049 E�3 of 21 U Z zW� 00 > 0sI Z c) 03 .4� O�t� �U 00 l a� O Vr •� QU z (% LU F- Cf) z W O (- �. 0 0 Q �zU J LL a Q U o U L n,*, IL F- C/) U0 wz J LJ Q Adam C. Forni, P.E. CA # E18607 I? FESS/ �fCTR�OP� 9TF CF C'k �EOEL EXP. 12/31/14 PLAN CHECK # DATE 1/10/14 JOB # 13-049 E�3 of 21