HomeMy WebLinkAbout2230-7ELECTRICAL SPECIFICATIONS SECTION 16000 1. The Electrical Drawings, which constitute an integral par; of this contract, serve as the working drawings and indicate the general layout of the electrical system. Field verification of locations of existing utilities on plan is required since actual locations, distances and mounting heights will be governed by field conditions. 2. All work and material shall be in accordance with applicable codes and governing authorities Nothing in these plans or specifications shall be deorned as permission to violate time codes or authorities. 3. As a minimum, construction shall comply with the latest adopted National Electrical Code, state and local codes. 4. Construction and inspection will be per utility issued drawings and specifications. Coordinate with mechanical, civil, landscape and irrigation site drawings. Concrete encasement per utility company requirements. Repaving is required after backfill, match existing materials. Provide yellow warning tape at I below grade. 5. Provide service conduits and structures for electrical services as shown on the drawings and as required by utilities Contractor shall base his bid on utility issued construction drawings 6. Each empty conduit shall include a pull cord as required by Utilities concerned Ali pull cords shall have a minimum diameter of 1/4' and a minimum average tensile strength of 1100 pounds it shall be yellawr In color. A contrasting tracer color may be included to identify the manufacturer. Flat braid is not acceptable. 7. All trenching, backfilling and compaction shall be in accordance with safety and building codes and per soak report recortunendations. 8. Conductors shall be 600 volt insulation type THWN/THHN copper. 9. Provide easily identifiable markers at all conduit stubs 10. Underground or underslab conduits shall be PVC schedule 40 unless noted otherwise. Conduit above grade where riot exposed to severe damage shall be EMT. All other conduit shall be IMC or rigid galvanized steel condult 11. Conduits to be minimum 24' below grade. 12. Utility services to be minimum 30' below grade to top of conduits. Coordinate with existing underground utilities. 13. Splices on conductors #8 or smaller shall be Skotchloc spring connectors and for larger size cables use solderiess connectors. 14. Splice or pull -boxes shall be NEMA 3R with MYERS HUBS where legally permitted and equal to Crouse -Hinds, Kilark, or Pyle -National. Provide plugs for spare hubs 15. Meter/Panel pedestal shall be outdoor, dead front and rear sections, of unitized construction by Meyers, Ryco or approved equal. Finish per California D.O.T. Spec 86-2.16. Color per Number 14672 of Fed Spec 595x. Meter/Panel pedestal shall be for 120/240 volt, single phase, three wire service. Pedestal shall include underground service entrance with provisions for metering, barriered fusible main disconnect switch and panelboard, photocell and relay. Metering facilities shall meet the requirements of the serving utility company. Provide housekeeping slab and bolt pedestal to slab. 16. Coordinate utilities with: A SOUTHERN CAI IFORNIA EDISON COMPANY Redwood Avenue Fontana, CA 92336 Mr, Hal Steward -(909357-6231 OR (909)357-6191 = ----- (Planning Department) - t I r. i HA0 n Np Lo6 440 WICO N N JVft Ak�e rr DoVr Cr4f0F • N hl!.oUi oil � � • - �� . A '!7� � TI � l� (0 M O.G. 40 _ rp -�o pie^ fz( • � . �J�s � �� w. waw tis, CONCRETE BASE •� (560-C-3250) TI(1yr) (MI t4) � Ta E •���� e� D POLE BASE DETAIL." NOT TO SCALE TSI O A FIXTURE SCHEDULE TYPE LAMPS VOLTS DESCRIPTION MANUFACTURER B K R C R C O �r✓L Po+-� t � 1� f� �L) �1���N �Ic�t+nrlr� �X� ISO Cp - 3 - Opel M S C R E C L T G WATTAGE LOCATION MOUNTING PANEL "h�El tl MAIN loc=o-,2f� 448 VOLTS ( PHASE 3 WIRE BUS . IOO2LIAP LOCATION WATTAGE L T G R E C M S C B K R C R C O CB R C K R M S C R E C L T G WATTAGE LOCATION OA OB OA OB W O.C. UON H N WIRING CONCEALED IN OR UNDER FLR. W 1 3 2 W. INDICATED, +96 UON ------- ca cc WIRING EXPOSED - lvl o - c cu Q c 3 4 N TO PANELBOARD CIRCUITS Z — o s-�>✓ — AS NOT AS NOTED 1 5 6 2- 2 POLE P- PILOT LIGHT — CONDUIT TURNED UP 3- 3 WAY D- DIMMER 4- 4 WAY MC- MOMENTARY CONTACT 8 CONDUIT TURNED DOWN K- KEYED M- MOTOR RATED T K WIT1101.1 PUMP - (32a MOTOR OUTLET l 30 _ 9 0 = POWER OR LIGHTING PANEL D — FIRE CONDUIT/WIRE 1, MAIN DISTRIBUTION PANEL 13,20 EXISTING CONDUIT []J DISCONNECT SWITCH 2 11 12 2412, 1/2" (3/4") CONDUIT ® MOTOR STARTER, SIZE AS NOTED — WATTS: OA= 1930 B= 1930 TOTAL WATTS= 366o AMPS= I t,.) , . + LCL= Zo.I AMPS r.0�1T�OIIt % �►�i�Jt L... -_ I -. I Fez— ..-,i .rt.r. , , - a A _ _ _ 1 . , _ J -ill: 2-i4f - PP67-r1►/IF.SjJiT�}i� Pl� 9999.......,,• ((•� •• •, M. C e 0 -moi =� • L � • P;o. 1543 *VCP 3-71-t3 =3. _; ire ,• � aieo .0 ijC1 OF I JortN GOII., Acoc�IV,,622, I WC, G,b-TfzUCTUFAL-"JC-ilM�5R �r •i FQP C�4 ADJf*�EN"r ( ME.ilf�-h1loo-0rt�O W100,A.�FL Mdi H . _ M dth-rel'ZE: I6PO I,diD�,l'7i'D p 120�2�}oV j I d7/ 3L1 � I I -- t1A SIE �" ' �" \Y - - G{izo111�b NOTES: O PROVIDE 100A METER AND 100/2P MAIN CB. 10,000 AIC. O PROVIDE PHOTOCELL. RELAY. PROVIDE 3#2 GU THWN WIRE TYPICALLY FROM METER TO SCE HANDHO�E PER PLANS UNLESS NOTED OTHERWISE SINGLE LINE DIAGRAM NOT TO SCALE 00 tj F- U U M fN40N •QWO a W JOQIp i Z p059) �Cr Ir 0 +- . I= J 127 o C.-00 J CAV y w(Tt :W SYMBOL LIST O WIRING CONCEALED IN OR ABOVE SURFACE RACEWAY WITH OUTLETS 12" Z CEILING W O.C. UON H N WIRING CONCEALED IN OR UNDER FLR. W CLOCK OUTLET WITH CLOCK TYPE --AS 3 � W. INDICATED, +96 UON ------- ca cc WIRING EXPOSED - _ c cu Q c Z TOGGLE SWITCH -SUBSCRIPT INDICATES N TO PANELBOARD CIRCUITS Z OUTLETS SWITCHED, +42" UON o 1W AS NOT AS NOTED 2- 2 POLE P- PILOT LIGHT CONDUIT TURNED UP 3- 3 WAY D- DIMMER 4- 4 WAY MC- MOMENTARY CONTACT CONDUIT TURNED DOWN K- KEYED M- MOTOR RATED T TELCO CONDUIT 3/4" UON '0' MOTOR OUTLET DATA CONDUIT 3/4" UON = POWER OR LIGHTING PANEL D FA FIRE CONDUIT/WIRE ® MAIN DISTRIBUTION PANEL --EX--- EXISTING CONDUIT []J DISCONNECT SWITCH 2412, 1/2" (3/4") CONDUIT ® MOTOR STARTER, SIZE AS NOTED 3412. 1/2" (3/4") CONDUIT COMBINATION DISCONNECT SWITCH AND MOTOR STARTER, SIZE AS NOTED 4-/12. 1/2" (3/4") CONDUIT - 0 _ TRANSFORMER 5-112. 3/4" CONDUIT Q PUSHBUTTON. +48" 6-0129 3/4" CONDUIT BELL LOCATION. +96" It PULL 7412. 3/4" CONDUIT STATION, +42" 8412, 3/4" CONDUIT © BELL LOCATION, +96" 9-/12, 1" CONDUIT QS SMOKE DETECTOR v . a o ABBREVIATIONS 3 w AFF - ABOVE FINISH FLOOR O LIGHTING OUTLET WITH FIXTURE CB - CIRCUIT BREAKER AS NOTED CO - CONDUIT ONLY EM - EMERGENCY BATTERY PACK Q FLUORESCENT FIXTURE EPO - EMERGENCY POWER OFF GFCI- GROUND FAULT CIRCUIT ® }® EXIT SIGN WITH ARROWS AS INDICATED INTERRUPTER FIXTURE TYPE GFP - GROUND FAULT PROTECTION J - JUNCTION IOb TOTAL NUMBER 'OF WATTS LV - LOW VOLTAGE NIC - NOT IN CONTRACT e a SINGLE RECEPTACLE, 120V. 15 AMP NL - NIGHT LIGHT +12 UON PC - PHOTO CONTROL ® I 1:@ ® DUPLEX RECEPTACLE, 120V, 15 AMP TS - TIMESWITCH +12 UON TTP - TYPICAL UON - UNLESS OTHERWISE NOTED �p �Y ® DOUBLE DUPLEX RECEPTACLE, 120V. WP - WEATHERPROOF 15 AMP +12" UON , 00 tj F- U U M fN40N •QWO a W JOQIp i Z p059) �Cr Ir 0 +- . I= J 127 o C.-00 J CAV y w(Tt I Q - W Z J Q CY tn N >r z W Q LL! U Z 0 U Z Q °C w� F_ W U OLL W WLU --� U (3 = .. W.. _• n ~ o • c Q d A 0 0' 15' 30' 60' o O N C71 o LL NORTH .. .. O o .. _ Z . - • 20 CONSTRUCTION SET-- o :W Q O Z W H N W 3 � W. ao H ca cc U W _ c cu Q c Z 0 %0-- 'a O Z o 1W U I Q - W Z J Q CY tn N >r z W Q LL! U Z 0 U Z Q °C w� F_ W U OLL W WLU --� U (3 = .. W.. _• n ~ o • c Q d A 0 0' 15' 30' 60' o O N C71 o LL NORTH .. .. O o .. _ Z . - • 20 CONSTRUCTION SET-- o