GENERAL NOTES:
1. ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD PLANS, THE
CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION ("GREEN
BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION UNLESS OTHERWISE
NOTED.
2. WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CANNOT BE
RESOLVED `0Y REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK", THE CONTRACTOR SHALL
IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEER FOR RESOLUTION.
3. ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER.
4. CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY DEVELOPMENT
DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK. INSPECTION COORDINATION SHALL
BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE START OF ANY WORK IN PUBLIC
RIGHT-OF-WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610.
5. THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND PROCEDURES
DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST NON -METRIC
EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER.
6. IT SHALL -BE, THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS OR
OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES.
7. THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR TRENCHES
5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF INDUSTRIAL SAFETY.
8. THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH SHALL BE GUARDED
BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS PURSUANT TO THE REQUIREMENTS OF
THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET
SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND MOVEMENT.
9. NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY WITHOUT OBTAINING A
SEPARATE PERMIT FOR THAT PURPOSE.
10. THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION, HOWEVER, IT
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE, IN THE FIELD, THE TRUE LOCATION AND
ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER PRECAUTION TO AVOID DAMAGE THERETO.
THE CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT 811 TWO WORKING DAYS BEFORE
EXCAVATION.
11. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING, BUT NOT
LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE IRRIGATION,
DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND CALTRANS. ALL UTILITY
COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK AROUND THEIR FACILITIES.
12. THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT APPROPRIATE AGENCY
AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR AGENCY
AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR VALVE OPERATION
AND WATER REQUIREMENTS.
13. CURVE DATA REFERS TO THE FACE OF CURB.
14. STATIONING REFERS TO THE CENTERLINE OF STREETS EXCEPT WHERE OTHERWISE NOTED.
15. ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE THE
CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING DURING CONSTRUCTION.
16. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH
MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER.
17. REMOVAL AND REPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING SURVEY MONUMENTS, MONUMENT
TIES AND BENCHMARKS, SHALL BE DONE BY A REGISTERED CIVIL ENGINEER OR LICENSED LAND
SURVEYOR' SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS CONSTRUCTION SHALL
BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE WEEK PRIOR TO CONSTRUCTION SO
THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT.
18. THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL TIMES.
A MINIMUM 12 -FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION AREA FOR
RESIDENTS AND EMERGENCY VEHICLES.
19. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL,
INCLUDING ADEQUATE WATERING, AT ALL TIMES.
20. ALL GRADING OPERATIONS SHALL BE DISCONTINUED WHEN SUSTAINED WIND VELOCITIES EXCEED 25 MILES
PER HOUR.
21. THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE DEPOSITED
ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING CONSTRUCTION WITHOUT
CITY OF FONTANA
SIERRA AVENUE AND FONTLEE LANE
SIDEWALK IMPROVEMENTS
Randall Ave
Al
PROJECT SITE
Q
C
N
L
Athol St
Valley Blvd
VICINITY MAP
NOT TO SCALE
28. NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REIN
PRIOR WRITTEN APPROVAL.
OREMOVE
CONT. GENERAL NOTES:
Q
>
c
Q
O2
REMOVAL LIMIT. SAWCUT CONCRETE, ASPHALT, AND OTHER HARDSCAPE SURFACE
N
N
CL
PAVEMENT STRUCTURAL SECTIONS SHOWN ARE MINIMUM AND SUBJECT TO REVISION AND APPROVAL OF
23.
�C
>%
O3
U
=3
REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT
PORTION OF THE WORK UNTIL THE SPECIFIED
Valley Blvd
VICINITY MAP
NOT TO SCALE
28. NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REIN
PRIOR WRITTEN APPROVAL.
OREMOVE
CONT. GENERAL NOTES:
22.
NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR
APPROVAL OF THE CITY INSPECTOR.
PROPOSED GRIND AND OVERLAY
O2
REMOVAL LIMIT. SAWCUT CONCRETE, ASPHALT, AND OTHER HARDSCAPE SURFACE
N/A
CONCRETE PAVERS
31.
PAVEMENT STRUCTURAL SECTIONS SHOWN ARE MINIMUM AND SUBJECT TO REVISION AND APPROVAL OF
23.
A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL
COMPACTION. FAILURE TO OBTAIN THE
O3
THE CITY ENGINEER AS DETERMINED BY SOILS TESTS TAKEN AFTER COMPLETION OF ROUGH GRADING.
120 LF
REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT
PORTION OF THE WORK UNTIL THE SPECIFIED
-•-•- •
OCONSTRUCT
6" CURB AND GUTTER OVER 12" MIN 95% COMPACTED NATIVE PER CITY OF
DENSITY IS OBTAINED.
-
32.
ACTUAL THICKNESS OF A.C. PAVEMENT AND/OR BASE COURSE MATERIAL FOR STRUCTURAL STREET
O5
CONSTRUCT 6" P.C.C. COMMERCIAL DRIVEWAY OVER 12" MIN 95% COMPACTED
320 SF
EXISTING
SECTIONS SHALL BE RECOMMENDED BY A GEOTECHNICAL REPORT AND SUBMITTED TO THE CITY OF FONTANA
24.
CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES,
AND SWALES FROM UNDERMINING
460 SF
FOR APPROVAL UPON COMPLETION OF ROUGH GRADING.
TRANSITION OVER 12" MIN 959 COMPACTED NATIVE
STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE,
THE CITY ENGINEER MAY REQUIRE
CONSTRUCT 6.5" MIN AC PAVEMENT OVER 12" OF 95% COMPACTED NATIVE
540 SF
0 7
TEMPORARY NON-ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS.
33.
ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED TO FINISHED GRADE BY THE
25.
THE FINAL LOCATION AND WIDTH OF DRIVEWAY APPROACH
APRONS SHALL BE APPROVED AT THE TIME
"A", SEE SHEET 2.
PAVING CONTRACTOR UPON COMPLETION OF PAVING.
O9
OF CONSTRUCTION AND SHALL CONFORM TO THE CITY OF
FONTANA STANDARD DETAILS.
34
UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING, BARRICADES,
WITH THE NORTH AMERICAN VERTICAL DATUM OF
GREMOVE
EXISTING AND CONSTRUCT 4" ASPHALT CONCRETE
1,250 SF
AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION OF THE CITY TRAFFIC ENGINEER.
26.
ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH
11
REMOVE EXISTING AND INSTALL CONCRETE PAVERS
950 SF
EXISTING CONCRETE.
ADJUST UTILITY TO GRADE PER OWNING FACILITY REQUIREMENTS
35.
CONTRACTOR SHALL RELOCATE AND/OR REPLACE LANDSCAPING, SPRINKLERS AND SIDEWALKS AFFECTED BY
27.
THE SEWER CONTRACTOR SHALL STAMP "S" IN THE FACE
OF THE CURB AT THE LOCATION OF THE
REMOVE EXISTING POLE
THE CONSTRUCTION TO THE SATISFACTION OF THE CITY ENGINEER.
15
A SEWER LATERAL.
N/A
36.
AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF RECORD, WHO
10 LF
ORCING STEEL HAVE BEEN PLACED
SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER.
F
INSPECTED AND APPROVED.
29. ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING
OF STREETS.
30. APPROVED- SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT PRIOR TO PLACEMENT.
UNDERGROUND SERVICE ALERT (USA)
IT'S THE LAW!
DIAL BEFORE •
YOU DIG!
CALL AT LEAStVC TWO WORKING DKnow whars below.
BEFORE YOU DIG Call before you dig.
REV.
REVISION DESCRIPTION
DATE I ENGR. I CITY I DATE
SHOULD CONSTRUCTION OF THE REQUIRED
IMPROVEMENTS NOT COMMENCE WITHIN TWO
YEARS OF THE DATE OF APPROVAL SHOWN HEREON
AND CARRIED FORTH IN A DILIGENT MANNER, THE
CITY ENGINEER MAY REQUIRE REVISIONS TO THE
PLANS TO BRING THEM INTO CONFORMANCE WITH
STANDARDS IN EFFECT.
Martin Ave
Fontlee Lane
N
Q
cu
N
(n
San Bernardino Ave
N1
North
CONSTRUCTION NOTES AND OUANTMES
QTY
OREMOVE
EXISTING CONCRETE CURB AND PAVEMENT AS NEEDED FOR
LS
CONSTRUCT A.0 PAVEMENT
CONSTRUCTION.
PROPOSED GRIND AND OVERLAY
O2
REMOVAL LIMIT. SAWCUT CONCRETE, ASPHALT, AND OTHER HARDSCAPE SURFACE
N/A
CONCRETE PAVERS
AND REMOVE TO THE LIMITS SHOWN ON THIS PLAN. ALL REMOVALS SHALL BE
EXISTING RIGHT-OF-WAY
- -
DISPOSED OF BY THE CONTRACTOR, UNDER CLEARING AND GRUBBING.
O3
CONSTRUCT 8" CURB AND GUTTER OVER 12" MIN 95% COMPACTED NATIVE PER CITY OF
120 LF
- EXISTING
FONTANA STANDARD PLAN NO. 1000. VARY CURB TO MATCH DRIVEWAY.
-•-•- •
OCONSTRUCT
6" CURB AND GUTTER OVER 12" MIN 95% COMPACTED NATIVE PER CITY OF
135 LF
-
FONTANA STANDARD PLAN NO. 1000. VARY CURB TO MATCH DRIVEWAY.
- EXISTING
O5
CONSTRUCT 6" P.C.C. COMMERCIAL DRIVEWAY OVER 12" MIN 95% COMPACTED
320 SF
EXISTING
NATIVE PER CITY OF FONTANA STANDARD PLAN NO. 1002.
-
OREMOVE
EXISTING AND CONSTRUCT 6" THICK P.C.C. DRIVEWAY
460 SF
BASIS OF BEARING -
TRANSITION OVER 12" MIN 959 COMPACTED NATIVE
- EXISTING
STORM DRAIN UNE
CONSTRUCT 6.5" MIN AC PAVEMENT OVER 12" OF 95% COMPACTED NATIVE
540 SF
0 7
SUBGRADE PER CITY STD 400.
22 TON
AND OVERLAY EXISTING PAVEMENT WITH 0.10' AC MIN PER DETAIL
540 SF
OGRIND
8
"A", SEE SHEET 2.
4 TON
O9
CONSTRUCT 4" THICK P.C.C. SIDEWALK OVER 12" MIN 95% COMPACTED NATIVE
1,800 SF
PER CITY OF FONTANA STANDARD PLAN NO. 1006.
WITH THE NORTH AMERICAN VERTICAL DATUM OF
GREMOVE
EXISTING AND CONSTRUCT 4" ASPHALT CONCRETE
1,250 SF
1988 (NAVD88) BASED LOCALLY UPON THE
TRANSITION PAVEMENT
11
REMOVE EXISTING AND INSTALL CONCRETE PAVERS
950 SF
12
ADJUST UTILITY TO GRADE PER OWNING FACILITY REQUIREMENTS
5 EA
13
ADJUST EXISTING M.H. TO FINISH GRADE.
1 EA
14
REMOVE EXISTING POLE
1 EA
15
PROTECT IN PLACE.
N/A
16
CONSTRUCT CONCRETE RETAINING CURB PER CITY OF FONTANA STANDARD
10 LF
PLAN NO. 1004.
LEGEND
PROPOSED CHAIN LINK FENCE
CONSTRUCT P.C.C. SIDEWALK
CONSTRUCT A.0 PAVEMENT
X,, ` ``` X.X X\ -X "
PROPOSED GRIND AND OVERLAY
\\
ASPHALT CONCRETE TRANSITION PAVEMENT
WALL
CONCRETE PAVERS
- -
EXISTING RIGHT-OF-WAY
- -
PROPOSED RIGHT-OF-WAY
EXISTING SIDEWALK
------------------------------------------------------
REMOVE EXISTING SIDEWALK
- EXISTING
PROPOSED SIDEWALK
-•-•- •
EXISTING CHAIN LINK FENCE
•-•-•-•-•
REMOVE EXISTING CHAIN LINK FENCE
BENCHMARK NO. ELEVATION
124 1213.16'
THESE PLANS ARE BASED UPON A SURVEY CONDUCTED
ON 11/18/15 BY RMD SURVEYING CORPORATION, RIALTO,
CALIFORNIA
QRpf ESSIOH
KOA CORPORATION
ANG GV 9���y PLANNING & ENGINEERING
3190 C. Shelby Street
Na 75793 A Ontario, California 91764
Tel: (909) 890-9693 Fax: (909) 890-9694
�c EXP. 6/30/16
BENCH MARK:B.M. NO. 124 ELEVATION=1,213.16
sj MAL
OF CAI�E���P DESCRIPTION: THE BENCHMARK FOR THIS SURVEY IS OF A CITY OF FONTANA BENCHMARK 124
BEING A PK NAIL IN THE SOUTHWEST CORNER OF SIERRA AVE AND ATHOL AVENUE.
Prepared Under The Supervision Of :
DRAWN BY:
DESIGNED BY:
CHECKED BY:
oATE:2�S/ 6
PROPOSED CHAIN LINK FENCE
TREES/LANDSCAPE
EXISTING
WALL
REMOVE
WALL
STREET LIGHT
EXISTING
CURB & GUTTER
SANITARY SEWER MANHOLE
PROPOSED CURB & GUTTER
-
- - G - -
- EXISTING
GAS UNE
-
- - 'A - -
- EXISTING
WATER LINE
-
- - T - -
- EXISTING
TELEPHONE LINE
DATUM STATEMENT
MAILBOX
EXISTING
OVERHEAD ELECTRIC
-
- - -- - -
- EXISTING
SEWER LINE
BASIS OF BEARING -
- - _51 - -
- EXISTING
STORM DRAIN UNE
BEARINGS SHOWN ARE BASED UPON MB11 /12 COUNTY
STREET SIGN
EXISTING
EDGE OF PAVEMENT
OF SAN BERNARDINO.
VERTICAL CONTROL
"ELEVATIONS SHOWN HEREON ARE IN TERMS
WITH THE NORTH AMERICAN VERTICAL DATUM OF
1988 (NAVD88) BASED LOCALLY UPON THE
FOLLOWING BENCHMARK IN THE CITY OF FONTANA"
BENCHMARK NO. ELEVATION
124 1213.16'
THESE PLANS ARE BASED UPON A SURVEY CONDUCTED
ON 11/18/15 BY RMD SURVEYING CORPORATION, RIALTO,
CALIFORNIA
QRpf ESSIOH
KOA CORPORATION
ANG GV 9���y PLANNING & ENGINEERING
3190 C. Shelby Street
Na 75793 A Ontario, California 91764
Tel: (909) 890-9693 Fax: (909) 890-9694
�c EXP. 6/30/16
BENCH MARK:B.M. NO. 124 ELEVATION=1,213.16
sj MAL
OF CAI�E���P DESCRIPTION: THE BENCHMARK FOR THIS SURVEY IS OF A CITY OF FONTANA BENCHMARK 124
BEING A PK NAIL IN THE SOUTHWEST CORNER OF SIERRA AVE AND ATHOL AVENUE.
Prepared Under The Supervision Of :
DRAWN BY:
DESIGNED BY:
CHECKED BY:
oATE:2�S/ 6
a _
Ye. ;;•
REMOVE TREES/LANDSCAPE
--------------
<.: REMOVE STREET LIGHT
REMOVE POWER POLE
REMOVE TELEPHONE PEDESTAL
I REMOVE MAIL BOX
® PROPOSED MAIL BOX
PROPOSED STREET SIGN
INDEX OF SHEETS:
SHEET 1 -TITLE SHEET
SHEET 2 -STREET IMPROVEMENT PLAN
SHEET 3 -CROSS SECTIONS
CITY OF FONTANA, CALIFORNIA
STREET IMPROVEMENTS
SIERRA AVENUE SCALE:
AND As Noted
DATE:
F9NTLEE LANE
IAPPR ED�3 •% DRAWING
t� DATE: 5418 3
EX.
TREES/LANDSCAPE
EX.
STREET LIGHT
EX.
SANITARY SEWER MANHOLE
I
EX.
WATER METER
EX.
SEWER METER
EX.
WATER VALVE
i7
EX.
MAILBOX
EX.
FIRE HYDRANT
-C-
EX.
POWER POLE
C
EX.
STREET SIGN
a _
Ye. ;;•
REMOVE TREES/LANDSCAPE
--------------
<.: REMOVE STREET LIGHT
REMOVE POWER POLE
REMOVE TELEPHONE PEDESTAL
I REMOVE MAIL BOX
® PROPOSED MAIL BOX
PROPOSED STREET SIGN
INDEX OF SHEETS:
SHEET 1 -TITLE SHEET
SHEET 2 -STREET IMPROVEMENT PLAN
SHEET 3 -CROSS SECTIONS
CITY OF FONTANA, CALIFORNIA
STREET IMPROVEMENTS
SIERRA AVENUE SCALE:
AND As Noted
DATE:
F9NTLEE LANE
IAPPR ED�3 •% DRAWING
t� DATE: 5418 3