HomeMy WebLinkAbout5013-31CR20-I SCADA SIGNAL "PUMP =I IN AUTOMATIC MODE" PRIMARY SCI-IEMAT IC IS DIAGRAMMATIC AND REPRESENTATIVE OF REQUIRED LOGIC; TI -IE LOGIC . I -I NN MAY BE IMPLEMENTED USING DISCRETE PARTS OR TI -4R UGI -I TI -4E USE OF PLC LOGIC; CONTRACTOR SHALL SUBMIT COMPLETE CONTROL 11 I P I NG DIAGRAM. 2 PUMP FAILURE RELAY FROM PUMP STARTER/RVSS; PUMP AS NOTED. CR21- I SCA DA SIGNAL PUMP P2 IN AUTOMATIC MODE" INTRINSICALLY SAFE RELAY SECONDARY CONTROL LOW WATER N.O. CONTACT FROM INTERLOCKED C.B. (MTS) CLOSES UPON TRANSFER TO EMERGENCY POWER SOURCE. INTRINSICALLY SAFE RELAY pETAIL I. TIME DELAY ADJUSTABLE FROM C--10 SECONDS SET AT 0 SECONDS. 2. TIME DELAY ADJUSTABLE FROM 0-180 SECONDS SET AT 160 SECONDS. . SECONDARY CONTROLS INTENDED FOR USE WI-IEN PRESSURE TRANSDUCER AND/OR PLC FAILS; USE DISCRETE COMPONENTS. . N.O. CONTACT FROM PLC CONTROLLED BY PRESSURE TRANSDUCER; CLOSE UPON WATER REACT -TING DESIGNATED LEVEL; DESIGNATED LEVELS SET PER CIVIL ENGINEERS PLAN; ELECTRICAL CONTRACTOR SHALL ADJUST LEVEL SETTINGS PER CIVIL PLANS. 5. UPON HIGH WATER ALARM; ALL PUMPING IS CALLED AND SCADA SIGNAL SENT. PRIMARY START SEQUENCE LEAD PUMP HATER LEVEL LAG PUMP IAIAT :R LEVEL. VMS 1.3.atett. SCADA SIGNAL "SECONDARY CONTROL; I ''IGT -I WATER" ® FIELD WIRING WIRING INSIDE MSB NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT TIMED CONTACT NORMALLY CLOSED TI MED OPEN TIMED CONTACT NORMALLY OPEN TIMED CLOSED TIMED CONTACT NORMALLY CLOSED TIMED CLOSED TIMED CONTACT NORMALLY OPEN TIMED OPEN RELAY; TYPE AS INDICATED; "XX" IS RELAY IDENTIFIER. ALTERNATOR, CALLS LEAD PUMP, THEN CALLS LAG PUMP; AUTOMATICALLY ROTATES START SEQUENCE, WHEN CALLED TO STOP PUMPING LEAD PUMP IS S1-IUT DOWN FIRST; LAG PUMP IS SI-IUTDOWN SECOND. 7. N.O. CONTACT FROM MAIN C.B. CLOSES UPON DETECTING POWER LOSS FROM UTILITY. SCADA SIGNAL "1-11 G -4 TATER" TIME DELAY ADJUSTABLE FROM 0 SECONDS SET AT 0 SECONDS. G1. TIME DELAY ADJUSTABLE FROM 0-180 SECONDS SET AT GO SECONDS. A SELECTOR SI I'ITCI ; INDICATES CONTACT SELECTION. PILOT LIG-IT; "X" INDICATES LENS COLOR; R=RED, G=GREEN, A=AMBER. PILOT LIG-1T IN I TH PUSH -TO -TEST; "X" INDICATES LENS COLOR; R=RED G=GREEN, A=AMBER. 10. AT LOW WATER LEVEL, PUMP CONTROLS ARE ACTIVATED AND REMAIN ACTIVATED UNTIL LOW WATER RELAY OPENS. SCADA SIGNAL LOW WATER" 11. SEE DETAIL I DETAIL NOT HIGH WATER START SEQUENCE I--IICI--1 WATER TIME DELAY RELAY 12. N.O. CONTACTS FROMINTRUSION ALARMS AT EACI-I PEDESTAL DORS NUMBER OF DEVICES PER PLANS; CONNECT EACH DEVICE IN PARALLEL; LLEL ALARMRM ISSENT UPON ANY DOOR OPENING. GH WATER TIIiiE DELAY START MOMENTARY CONTACT NORMALLY CLOSED MOMENTARY CONTACT NORMALLY OPEN I- 0A I-IANL -OFF-AUTOMATIC SWITCH. PLC PROGRAMMABLE LOGIC CONTROL. I -IP I -III -1 PRESSURE. N.O. CONTACT FROM PLC CONTROLLED BY PRESSURE TRANSDUCER; CLOSES UPON FAILURE OF TRANSDUCER. 14. N.O. CONTACTS FROM INTRUSION ALARMS AT DRYNELL DOORS OR PANEL DOORS AS APPLICABLE, NUMBER OF DEVICES PER PLANS; CONNECT EACH DEVICE I N PARALLEL; ALARM IS SENT UPON ANY DOOR OPENING; PROVIDE TERM I NAL BLOCKS TO CONNECT UP TO 10 PARALLEL DEVICES. CRS -2 I SCADA 1 "PUMP P1 SIGNAL FAI LURE'" FLOAT SWITCI-I CA LE PART OF FLOAT PULLBO/. 2. PRESSURE TRANSMITTER CAB CONTROL PU LLBOC. ITCH ASSEMBLY; C R I NATE CABLE LEN. TI -1 W I TI -I VENDOR; CABLE TERMINATES IN CONTROL E PART OF PRESSURE TRANSMITTER; COOR NATE CABLE LENc TI -1 W I TIS VENDOR; CABLE TERM I NATES I N 3. MINI CAS SIGNAL CONDUCTORS PART OF MOTOR POWER CABLE; SIGNAL CON .. CONDUCTORS FROM PUMP RECEPTACLE TO MINI CAS TRANSCEIVER.. 5. CONDUCTORS FROM CONTROL PULLBO C TO PEDESTAL CONTROL SECTION. G. INDEPENDENT REDUNDANT CONTROLS; SEE DETAIL 3/E6.0, UCTORS TERMINATE IN PUMP RECEPTACLE; SEE . ; PEDESTAL CONTROL SECTION N.O. CONTACT FROM MINI CAS UNIT FOR; CLOSES UPON FAILURE OF PUMP; PUMP AS NOTED. SCADA SIGNAL "PUMP P2 FAILURE'" SCADA SIGNAL "LOSS OF CONTROL POWER" SCADA SIGNAL "TRANSFER TO EMERGENCY POW INTRINSIC BARRI ER INTRINSIC BARRIER MINI CAS SYSTEM TO PUMP STARTERS TO PUMP STARTERS SCADA SIGNAL "PEDESTAL 1NTRUS ALARM SIGNAL" CABLE SPLICE TYPICAL SCADA SIGNAL "PRIMARY CONTROLLER FA I LURE" SCADA SIGNAL "PRI MARY POWER LOSS" OVERHEAT SENSOR FLOAT SW I TCI -1 (LOW WATER) (FS2) FLOAT SW ITCH — (I-IIGI-1 WATER) (FSI) PRESSURE TRANSMITTER 24VDC ( FROM PLC MOISTURE SENSOR OVERHEAT SENSOR MOISTURE SENSOR ENGINEERINGFEHR A INC. 62—A HANGAR WAY WATSONVILLE, CALIFORNIA, 95076 PHONE 831 786-0373 FAX (831) 786-8523 nc- EMAIL. FEC. ,FEHRINC.COM CONSULTING ELECTRICAL ENGINEERS FE JOB No. 11081.00 S OULD CONSTRUCTION 0= I E REQUIRED IMPROVEMENTS NOT COMMENCE WITHIN TWO YEARS 0= THE DATE DE APPROVAL SHOWN HEREON AND CARRIED FORTH IN A D L GENT MANNER, THE CITY E N1 C NEER MAY REQUIRE REV S 01\11 TO T H E PLANS TO 81 NC THE INTO CONFORMANCE WITH STAN DARDS N EFFECT. Prepared Under The Supervision Of SANITARY WORKING EFORE YOU DIG _227`2600 SERVICE ALERT CONSULT 870 ' { ET STREET, SUITE 1278 ..:.:. -I : , CA 94102 (415) 433 4848 0 1 No. 014906 EXP. 30 JUNE R DESIGNED BY T.P. CHECKED BY: CONTROL DIAGRAM BARGEE & L2CUST STATIONS DATE: 4/1/13 REVISION DESCRIPTION