CONSULTING ELECTRICAL ENGINEERS
FE JOB No. 11081 00
cT
OF FONTANA, CALIFORNIA
SCALE:
AS SHOWN
A.
ALL ELECTRICAL SHONN 13 NEN, U .0.N .
ft ALL CIRCUIT BREAKERS ARE 3 -POLE, U.O.N.
C.
VOLTAGE DESIGNATIONS: (U.O.N.)
240 - 1 = 240/120V - 1 PH -31^1 I RE
450-1 = 450V - I PH -2IN I RE
205Y = 205/120V -3PI4 -4 1A1 I RE
450Y = 450/277V - 3 PH - I RE
480 A = 450V - 3 PH -3 N I RE
D. "KA" AT CIRCUIT BREAKERS DENOTES MINIMUM REQUIRED
CAPACITY IN AMPS (x 1000).
E.
SPO AT BREAKER DENOTES: PROVIDE MOUNTING SPACE *
FOR FUTURE 3 -POLE BREAKER OF RATINGS INDICATED,
INTERRUPTING
I-IARDINARE
FR No.
BFO I
13F02
B F03
CONDUIT AND C NDUCTCRS
%'c., 34110, 1#10 GN
2#14
VC., 34410, 11110 GN
2#14
3zt10, Iwo GN
2#14
REMARK
PUMP BP -2
B502
(E) UTILITY
TRANSFORMER
/2
AIN
ARBEE PEDESTAL BPI; 30A
240-1
PUMP
BP -1
240V, 30,
2.7 HP
(7.5 FLA)
PUMP
BP -2
240V, 30,
2.7 HP
(7,5 FLA)
CONTROLS
SECTION
BPI
TYPE NEMA 3R
30A, 0, 3N
LT240-1
MOUNT PEDESTAL
MA
NS
0/2 C.13.
CONNECTED LOAD
A I C 10, 000
FEED BOTTOM
KVA 7.0
A ®
USE
VOLT -AMPS
A B TRIP
P-1 VF:
560
25
560 2
BP -2 VFD
1
SPACE ONLY
560
25 AillE1
3120
1560 2 7
IPSP
I I
3120
* TANDEM CI RCU IT BREAKER 2@20/1
3
5
TRIP
VOLT -AMPS
A
B
USE
20/1
550
PEDESTAL LTS I-ITRS
4
200
CONTROLS
SPARE
10
12
14
16
TED LO
550
200
LT. SW.
L
L
LJ
r
UTIUTY
M R
PUMP
STARTERS
MAINTENANCE 4 - FLEX
RECEPTACLE.
TYPICAL
CIRCUIT BREAKERS
CONDUITS TO LOADS; SEE SITE PLAN I/64.1
FOR EXACT NUMBER REQUIRED.
1,11,111.,
1 . (E) SECONDARY SERVICE; CCX)RDI NATE IN I TH UTILITY TO RECONNECT
(N) PUMP PEDESTAL INIT1.4 (E) UTILITY SERVICE.
2. INTRUSION ALARM DEVICE AT EAG4 PEDESTAL DOOR; CLEARWATER
TECI-I 2500 SERI ES MAGNETIC POSITION SENSOR OR APPROVED EQUAL;
PROVIDE APPROPRIATE MOUNT I NG HARDWARE FOR EACH DOOR TYPE;
SEE CONTROL DIAGRAM AND MAKE APPROPRIATE CONNECT ION VIA
21:t14.
3. SEE PANELBOARD SCHEDULE FOR ALL PEDESTAL LOADS.
4. SECTION HEATER; 250N MINIMUM 120V; PROVIDE SINGLE THERMOSTAT
CONTROL CENTRALLY LOCATED IN PEDESTAL.
5. GENERATOR PLUG MOUNTED ON EXTERIOR OF PEDESTAL; PROVIDE
IA I TH ANGLE ADAPTER; 240V, 30A, 10; RUSSELLSTOLL "MAXGARII OR
EQUAL; CONFIRM COMPLIANCE WITH CITY'S GENERATOR AND PROVIDE
EQUIPMENT SUBMITTAL PRIOR TO PURCHASE.
. CONTROL PLC; SEE DETAILS 1/E60 21E6.0.
7. CONCRETE EQUIPMENT PAD PROVIDED * INSTALLED BY CONTRACTOR,
SEE CIVIL PLANS; COORDINATE EXACT REQUIREMENTS FOR
ELECTRICAL EQUIPMENT BEING INSTALLED.
5. TOTAL CONNECTED LOAD IS 7.0kVA OR 29 AMPS AT 240V, 10;
DEMAND IS 5% OR 1.6 AMPS AT 240V, 10.
. ONLY BP -1 OR BP -2 RUNS SIMULTANEOUSLY.
10. BACKUP CELLULAR AUTQDIALER; SEE ELECTRICAL SPECI FICAT ION .
1 I . CONDUIT FOR FLOAT SN ITCH CABLES; CONTRACTOR SHALL.. DETERMINE
FLOAT SW ITCH CABLE LENGTH AS REQUIRED BY F I ELD CONDITIONS.
2. FLOAT SN ITCH INTRINSICALLY SAFE CONTROLS; ONE FOR EACH FLOAT
Ski I TCH; WARRICK SERI ES 27 BY GEMS SENSORS.
13. INTERLOCKED CIRCUIT BREAKERS MANUAL LOAD TRANSFER; CIRCUIT
BREAKERS SHALL BE PERMANENTLY INTERLOCKED SO T1 -IAT ONLY
ONE CIRCUIT BREAKER MAY BE CLOSED SIMULTANEOUSLY.
14. AUTODIALER; SEE ELECTRICAL SPECIFICATION.
15. VFD INPUT 240V, 10 TO DRIVE 240V, 30 MOTOR; 3I -4P RATED VFD;
DISABLE PHASE LOSS PARAMETER.
CONDUIT FOR PRESSURE TRANSDUCER CABLE; SEE DETAIL 2/E6.0.
17. SERVICE GROUND ROD WITHIN PEDESTAL ENCLOSURE; SEE DETAIL
41E5.0 SIMILAR.
15. CABLE SPLICE; SEE 2/E4.l.
19. PUMP CABLE SUPPLIED IN ITI-4 PUMP.
20. MINI CAS UN ITS PROVIDED NITH PUMPS.
SHOULD CONSTRUCT 00 OF THE REQUIRED
IMPROVEMENTS , NOT COMMENCE WITH 0 TWO
YEARS OF THE DATE 0- ,APPROVAL SHOWN ERRON
AND CARRIED FORTH IN A DILIGENT MANNER, THE
CITY ENCIHNEEP, MAO REQUIRE REV S0HS TO THE
IDLAhlS TO BR q.\.] G THEM I \ITO CON FOR v A 1 CE 11/
STANDARDS IJ EFFECT.
DIAL
BEFO
YOU DIG
TWO WORKING
YS BEFORE
YOU DIG
TOLL FREE 180O2272600
A PUBLIC SERVICE BY UNBERGRI. 0 SERVICE ALERT
M111111111111•11111111
11111M IN
=•111
1111111111111111111
REVISION DESCRIPTION
DATE
ENGR.
CITY DATE
S h a heeler
CONSULTING CIVIL ENGINEERS
870 A T STREET, SUITE 1278
SAN FRANCISCO, CA 94102
(415) 433-4848
Prepared Under The Supervision Of
Dote',
THOMAS PINKERTON
SANITARY SE
ER PUMP STATION REPAIRS
DRAWN BY:
C.L.
DESIGNED BY:
T.P.
CHECKED BY:
T.P.
BARBEE IMPROVEMENT
DATE:
4/1 /1 3
DRNMNG NO: