HomeMy WebLinkAbout5013-21A. ALL ELECTRICAL SHOWN IS NEN, U.D.N.
B. ALL CIRCUIT BREAKERS ARE 3—POLE, U.Q.N.
C.
VOLTAGE DESIGNATIONS: (U.O.N.)
240--I = 240/120V-1PH-31AI1RE
480— I = 460V— I PH --2I1 I RE
208Y = 208/120V -3P14-4 IAIIRE
480Y =0/277V --3 I`1— IAI I
P 4 RE
460 A = 480V --3P14-3 WIRE
D.
"KA" AT CIRCUIT T BREA
KERS
DENOTES MINI
MUM
CAPACITY IN AMPS (x 1000).
E
SPO AT BREAKER DENOTES: PROVIDE MOUNTING
FOR FUTURE 3—POLE BREAKER OF RATINGS IND
REQUIRED
SPACE
GATED.
INTERRUPTING
HARDWARE
FDR N.
SF01
SF02
SF03
SFO4
SFO5
S F0
SF 07
SF08
SFOGI
3301
5502
03
5504
5505
CONDUIT AND CONDUCTORS
2"C., 4#3/0.
GND.
2"
4#3/0. I#6) GND.
GND.
#10 GND, 2#I0
I "C., 3#8
#10 GND. 2#I0
3#10,
4#
10 GND.
1#10 GND.
#12, 1#12 GND.
3#12,
2 GND.
#10 GND.
3#10, 1#10 GND.
2#10
GEFRATO
TER t BATTERI G1AR R
GENERATOR START
NAL FAIL ALARM
TE CEPH E
NQOD
TYPE NEMA I
BUS SDA, 3
VOLT120/208
riouN-r O
MA N
GOA CB
CONNECTED LOAD
A. I mC4 10,000
FEED
KVA 4.3
12
US=
VO T A PS
A
TRIP
TING
20/1
CONTROLS
GEN. HEATER
500
1200
GEN. BATT.
800
SPACE ONLY
IPSP
500
7idIP
A
USE
20/1
540
RECEPTACLES
4
360
SPARE
12
20
540
3C
SPACE ONLY
2I'C.0
2#14
211C.i 4#14
PRESSURE TRANSDUCER
FLOAT IITCH CABLES
`E F TI E F'11 --'1E1
( 2) PBO:X PB1
I-----25KAIC. (INCLUDING
MOTOR CONTRIBUTION)
SEE 2/E2.4 FOR
CONDU I T
REQU 1 REMENTS
(N) MSB 450/277V, 3
NEMA I RATED
200
25KAIC
HET HELL
CLASS 1,
DIVISION I
L AT1ON
(N) ATS, 200A, 3;
25KAIC MINIMUM
NEMA 1
COORDINATE WITH UTILITY TO RECONNECT (N)
SWITCHBOARD WITH THE (E) UTILITY SERVICE.
2. RATE CIRCUIT BREAKERS $ IMP'S AT 25KAIC
MINIMUM.
3. MOUNTED N I TI -I I N SWITCHBOARD.
4. CORE DRILL TI-IROUGI-I FLOOR TO MAKE WAY FOR
(N) CONDUIT RUN; SEE 101E2.2.
5. HAZARDOUS DUTY RECEPTACLE N I TI -1 MATCHING
PLUG TO MOTOR CONNECTION; GOA, 480V, 3 POLE
AND EQUIPMENT GROUND; PROVIDE 2
AUXILIARY/PILOT
CONTACTS FOR SIGNAL
CONNECTION; MOUNT TO WALL BOX MITI -1 70°
INCLINED INLET/HALL BOX; CLASS I, DIVISION 2;
POLYESTER HOUSING; MELTRIC DCN SERIES OR
APPROVED EQUAL; LOCATE RECEPTACLE ADJACENT
TO PUMP CONTROLLED.
G. FLEXIBLE CABLE PART OF MOTOR; I CABLE WITH
3#6 POWER CONDUCTORS, 2#10 CONTROL
CONDUCTORS; l#8 EQUIPMENT GROUND CONDUCTOR;
1#10 "GROUND COMPLETE CONDUCTOR" IS NOT USED;
CONNECT CABLE TO (N) PLUG.
7. DIESEL FUEL POWERED EMERGENCY GENERATOR SET
IDOKN; SEE ELECTRICAL SPECIFICATION.
5. SUMP PUMP; SEE VE2.2.
9. I#4 B.C. TO GROUNDING ELECTRODE; SEE DETAIL
41E5..:.
10. TOTAL CONNECTED LOAD IS 78KVA OR P AT
480V, 30.
11. START SIGNAL; SEE DETAILS 3,1E2. I/E6.2.
4 AM
12. SCHEMATIC DIAGRAM ILLUSTRATES CONCEPTUAL
WIRING; CONTRACTOR SHALL ADHERE TO EQUIPMENT
MANUFACTURERS SPECIFIC INSTALLATION
RUCTIONS; PROVIDE HIRING DIAGRAM
MITTAL FOR REVIEW 4 APPROVAL PRIOR TO
INSTALLATION.
FANS RUN CONTINUOUSLY TO MAINTAIN AIR CHANGE
REQUIREMENTS; SEE DETAIL 11E5.0 51 M I LAR.
14. EMERGENCY OFF PUSH BUTTON; MUSI-IR M HEAD,
RED MITI -I "EMERGENCY SI-IUT OFF" ENGRAVED IN
HEAD; 4IMM DIAMETER; 2 POSITION MANUAL
PUSH/PULL SHITCI-1; TN0 N.O. CONTACTS 120V, 3
AMPS MINIMUM; NON—ILLUMINATED; MOUNTED IN 4" X
4" X 2"D. NEMA 4X STAINLESS STEEL ENCLOSURE
AT 48" AFF. LABEL SWITCH WITI-1 NAME OF PUMP
CONTROLLED; "PUMP PX" WHERE "X" IS SPECIFIC
PUMP NUMBER.
15. 1 5/8" X I /8" STAINLESS STEEL STRUT; SECURED
TO PUMP PEDESTAL.
(0. 3#8 * 1#10 GROUND CONDUCTORS PART OF POWER
CIRCUIT AND 210 CONDUCTORS PART OF CONTROL
CIRCUIT.
17. CIRCUIT TO SP1; SEE PANEL SCHEDULE.
15. CABLE SUPPORT GRIP, HEAVY DUTY STAINLESS
STEEL, OFFSET EYE SPLIT MESH. ROD CLOSING
"KELLUMS" OR APPROVED EQUAL
1. COORDINATE FS MOUNTING HEIGHT WITH CIVIL
PLANS.
20. FLOAT SWITCH; MECHANICAL TILT FLOAT SNITCH;
ENM--l0 LEVEL REGULATOR BY ITT FLYGT. PROVIDE
WITH INTRINSICALLY SAFE CONTROLS.
21. SIGNAL CIRCUIT TI-1ROUGHI NETNELL WALL;
PENETRATE HALL AS SHOWN FOR POKER CORD.
22. SUBMERSIBLE PRESSURE TRANSDUCER; GE
"PTX -12" SERIES; 4-20mA OUTPUT; PROVIDE WITH
INTRINSICALLY SAFE CONTROLS; COORDINATE CABLE
LENGTH WITH FIELD CONDITIONS; SEE CIVIL PLANS
FOR INSTALLATION REQUIREMENTS.
23. CONTROLS PULLBO; SEE DETAIL 2/E2.4.
24. COMBINATION MOTOR STARTER (NEMA 00); SEE
DETAIL VE5.0.
25. SEE CIVIL PLANS FOR WET WELL PENETRATION
REQUIREMENTS.
2. CONDUIT FOR TRANSDUCER CABLE; SEE DETAIL
11E6.2.
27. CONDUIT FOR FLOAT SNI TC I -I CAB L ; SEE DETAIL
I/E6.2.
ES
TYPICAL FOR
ALL CORDS
IN WET WELL
+24V DC
( FROM MCC
CONTROL SECTION
EMERGENCY,
GENERATOR
SECONDARY
ONTROL RELAY
SOLID STATE
STARTER CONTROL
BOARD
(N) MCC, 200A MINIMUM
480V, 3, 3W, NEMA I
TYPICAL EACH MOTOR
TRANSFORMER X5PI
15KVA; 4.8%Z (MIN.)
205Y
RESET CONTROL
RELAY
1
48OV, 3
3/4HP
6.,FLA)
4OV, 3
3/414P
(1.6FLA)
PUMP PI+
450V, 3
201—IP
(27FLA)
PUMP
480V, 3,
20HP
(27FLA)
PUMP P3
40V, 3,
201-1P
(27FLA)
E PANEL SCHEDULE
PUMP FAILURE
TO CONTROLS
N 0 IJ L3 % IPUCT OF THE REQUIRED
ry PPC)VEM El'\\1 TS 0c T COMMIENCEHITTKIN 'MO"
TEARS OF THE DATE OF APPROVAL SHOWN HEREON
Af°,ID CARIED FORTH N A D LIGEE\ T MANNER, THE
CITY E NJ G I N E E MAY REQUIRE P E `v' 1 l 2 2 S TO T I—I E
PLANS TO BRING THEM 10TO CO NEV PA1AHL E WITH
STANDARDS 1 0 EFFECT
Prepared Under The Supervision Of
Di 'L_
BEFORE
YOU D
TOLL
PSI LIC SERVICE BY UNDERGR
WORK
YB BEFORE
OW B ICS
VICE ALERT
CONSU TING CIVIL ENGINEERS
870 T, SUITE 1278
FRANCISCO, CA 94102
(415) 433 4848
Date
INC.FEHR ENGINEERING COMPANY,
62—A HANGAR WAY
WATSONVILLE, CALIFORNIA, 95076
PHONE: (831) 786-0373
FAX: (831) 786-8523
EMAIL FE FEHRINC. OM
CONSULTING ELECTRICAL ENGINEERS
FE JOB No. 11081.00
CTY C)F-- FONTANA, CALIFORNIA
DRAWN BY:
C.L.
DESIGNED BY:
T.P.
CHECKED BY:
ER puMP STATION REPAIRS
PLAN
ENTAS SHOWN
SCALE:
DATE:
411 /13
REVISION DESCRIPTION
DATE
THO
PINKERTON
T.P.