HomeMy WebLinkAbout2769-44ND DIESEL TANK INFORMATION Q OPW MODEL 23-0033, (2") VAPOR VENT. MATERIAL: 1. 3/4" DIESEL FUEL SUPPLY LINE AND 1" DIESEL FUEL RETURN LINE SHHALL BE SCHEDULE 40 BLACK STEEL PIPE CONFORMING TO ASTM A-53 USING 150 POUND BANDED MALLEABLE IRON SCREWED FITTING. NOTES: 1. TANK INSTALLATION SHALL COMPLY WITH NEPA 30 30A, 70 AND UFC STANDARD 79-9 AND ALL APPLICABLE GEODES, STANDARD PRACTICES OF THE TRADE AND AUTHORITES HAVING JURISDICTION AND TANK MFG. INSTRUCTIONS. 2. CONTRACTOR SHALL OBTAIN ENVIRONMENT HEALTH SERVICES APPROVAL OF ABOVE GROUND FUEL TANK, -BEFORE INSTALLATION. 3. ANCHORING TANK SHALL BE INSTALL PER TANK MANUFACTURER RECOMMENDATIONS. 3"SD&OD DN ® WALL 3"SD&OD UP ,zoo en P. nn COI( I rul ID PROJECT NORTH PROJECT NORTH SCALE 1/4 90=1 11—off SCALE 1/4 to= 1 0— to 1toGDNINWALL FOR CONT. P.O.C. 1" G W/ GC FOR CONT. 3 SEE V UP TO 3" VTR 1 TO RANGE (90 CFH) SEE 1 2» V UP TO 2" VTR 2. 2. DISHWASHER ROUGH—IN & 1/4 1 2" CW DN IN WALL FD 2" V UP IN WALL ABV. CONN. 1/2" HW W/ S.O.V. / 2 & 3/4" HOSE WASTE THRU SH 3/4it TP W/ S.O.V. & AP COU TER MOUNTED 'AIR I �� I I 1 2" CW W ANGLE STOP 1 3 q 1 GAP FITTING TO GARBAGE FOR ICE MAKER DISPOSER (TYP OF 2 PLCS) 1.E.=20.50 -- --»--._..W.C.0. (TYP)C.O.T.G. ' S 1" I I. .=20.10 (BOT. OF SLVE) 3/4" 2 S 4 1 (BOT. OF SLVE) 4„ FOR CONT. 1 n 1 2 .— -N , —1_ 2 1/2 SEE 1 2" 2, Q 1 /2" I.E.=20.50' 2» FOR CONT. 2. 2» I 3 .C.O. ------ ----------- SEE 1 1 /4» I. .=2 .38' I = (BOT. OF SLVE / 2 2. {BOT. OF SLVE) 2" I Fp I.E.=20.64 ) , 3 4 — » 3/4" 1 2" V UP TO ABV. CLG. _ _ FOR CONT. FOR CONT. 3/4 _ -' I „ SEE 1 I WB 3/4 H& CW DN 1 1/2SEE 1 2. I 3/4» 1 IN WALL 1 1/2 2. " J H ® + 20" ABV. 2�1 1 /4" P.O.C. 3/4" G W/ GC FOR CONT. FOR CONT. TO DRYER (35 CFH) 1 FIN. FLR. SEE SEE 2. 2. PAKTIAL FLS PLAN ......�� R.COR PLM FOR CONT. 1 P2. 3/4» 1 1 2„ W.C.O. (TYP) — H ®+ 20" ABV FOR CONT. /2» 3/4" ._4 / PROJECT NORTH SCALE 1 2 1/4 "=1'-0" "W/ A. P. 1 � P W/ S. 0. V. & AP 2" V UP IN WALL ABV. 2" CW DN IN WALL N=Fl FLR. W/ S.O.V. Ar A.P. 2 � 1 3/4" CW & 3/4"ALINE DN 2. oo," WC (TYP OF 2 PLCS) 4 TYP OF 3 PLCS 1 1 SEE DET. � WALL 0+ 8 —0 ABV. L /1/2 2 2 FIN. FLR. 1 ( ) I ___3" V UP TO 3" VTR f' " W/ C (1 V._ 3/4 'FOR C:C�NT ({ 2 r UK CMV 1.1 f 0�__ - f A SEE 1 SEE 2 SH 1 1/2" CW DN IN WALL 3�4" 2• 2 — — I 2» 2 4" FLUE UP THRU ROOF 1" FS I.E.=18.39' 2" 3/4" 1 1 /2" HW `DN IN WALL 1 1 /2" 1 (T� OF 2 PLCS) FOR CONT. 3/4" G DN IN WALL �� {BOT. OF SLVE) 2�► 3/ „ " SEE 1 / c SS 3/4 CW W/ ANGLE STOP FOR CONT. 4» 4 to — —4 2• CP 2 1 FOR ICE MACHINE SEE 1 I.E.=1 .17' 1 SEE DET. 4 » 2" 3 4" co » 3 / (BOT. OF SLVE) (BOT. OF SLVE) 3/4 HWR DN IN WALL _ 3/4" 1 1/2 FOR CONT. FOR CONT.'. 2 I It FOR CONT. SH (TYP OF 2 PLCS) /4"/N,2" 3 4" SEE 2 SEE 1 2 3 SEE 1 FD I» / 2, /4 2• 2 (TYP OF 3 PLCS) 12 1 CD DN IN WALL to & CONN. TO LAV. T & AP NOTE: O COMBUSTION AIR DOOR LOUVERS: (SCREENED PROOF). THE LOWER: 12" X 12" (FREE AREA) WITH IN LOWER 12" OF THE ENCLOSURE. THE UPPER: 12" X 12" FREE AREA) WITH IN UPPER 12" OF THE ENCLOSURE REFER TO ARCH. DWG'S FOR LOUVERS). PROJECT NORTH PARMAL R SCALE 1/4 *p=19 -Off 3 2 AIL PIECE 2FOR CONT. FD (TYP OF 3 PLCS)12",� SEE 1 1" 4 2R � (TYP OF 2 PLCS) �— - — — —I 3/4 / „ CD UP 2",,,y 2 I 3 2" V UP IN WALL ABV. I 1 _ 2 JI of 1" G H — — W/ A. P. 2» I I I H W/ A. P. TP WC — 1 TP 1 1 W/ S.O.V. & AP _ 41 W/ S.O.V. & AP 2» » 2„ 1 1/4's 2" CW DN IN WALL UR Iof FOR CONT. W/ S. 0. V. & A. P. 1 I SEE 1 » 2. 2" / » 2 1/2 1 1 2 2" CW DN IN WALL .E.=19.92' FOR CONT. W/ S.O.V. & A. P. BOT. OF SLVE) SEE 1 P2.1 ASmBUILTS PROJECT NORTH SCALE 1/4 $$=i ' — 0" �Ar itects Virginia Dare Tower 10470 Foothill Blvd. Rancho Cucamonga California 91730-3754 tel: 909 987 0909 fax: 909 980 9980 CONSULTANT r• P BP & Associates, Inc. consuit�g Enginsm 14471 Chambers Rd. Suits 102 Tustin, Califomia 92780 Telthone (714) 734 1m ax (714) 7341783 Hrrrcvvtu �HANJ �r f7f. CALF APPROVED JUL 3.0 ZOOZ- APPROVED SD ARC , v ,A LARRY-WOLFF C-9784 Q ktt01/31/0D , NO DATE IBY IREMARKS TOILET ROOM AND PARTIAL FLOOR PLANS DRAWN TP CHECKED TP DATE FEB. 1999 SCALE AS NOTED JOB N0. I: 98177 ABOVE GROUND TANK CONVAULT 2000 GALLON CAPACITY, 1000 GALLON DIESEL AND 1000 GALLON GASOLINE. THE TANK SHALL HAVE TWO f"N SEPARATE CONNECTION FOR SUPPLY AND RETU NN FROM EMERGENCY GENERATOR. THE TANK SHALL HAVE TWO (2) SIDE MOUNTED PUMPS, ONE FOR DIESEL AND OTHER FOR GASOLINE. THE GASOLINE SHALL HAVE TYPE 2 PRODUCT LINE/VAPOR RETURN ASSEMBLY. EACH PUMP SHALL BE MINIMUM 7 AMPS EACH AND TOTAL MAXIMUM 20 AMPS. TANK TO BE EQUIPPED WITH A SEVEN GALLON UL LISTED OVERFILL, EARTHQUAKE RESTRAINTS AND A PKG15DOL DIESEL PACKAGE. ON THE NORTH END OF THE TANK, USING A STENCIL, PAINT THE STATEMENTS, to NO SMOKING" AND "EMERGENCY SHUT OFF SWITCH AT 1" CONTAINMENT AREA MAIN BUILDING". LETTERING TO BE 2 INCHES HIGH, STORM WATER DRAIN BLACK IN COLOR AND OF HELVETICA REGULAR TYPE ONE REQUIRED, LOCATE AS INDICATED ON THE DRAWINGS. S.O.V. NORMALLY CLOSED O OF 912 P.O.C. TO TANK WITH 1" DOR PER THE MANUFACTURER RECOMMENDATION 2" DOV UP 12'-0" ABV FIN GRADE WITH Q SIDE MOUNTED PUMPS WITH0000 3/4" MOUNTING BRACKET, NOZZLE, FILTER, HOSE AND 1» ACCESSORIES AS REQUIRED 00, P.O.C. TO TANK WITH 3/4" DOS FOR CONT. PER THE MANUFACTURER SEE 1 RECOMMENDATION P1.1 ND DIESEL TANK INFORMATION Q OPW MODEL 23-0033, (2") VAPOR VENT. MATERIAL: 1. 3/4" DIESEL FUEL SUPPLY LINE AND 1" DIESEL FUEL RETURN LINE SHHALL BE SCHEDULE 40 BLACK STEEL PIPE CONFORMING TO ASTM A-53 USING 150 POUND BANDED MALLEABLE IRON SCREWED FITTING. NOTES: 1. TANK INSTALLATION SHALL COMPLY WITH NEPA 30 30A, 70 AND UFC STANDARD 79-9 AND ALL APPLICABLE GEODES, STANDARD PRACTICES OF THE TRADE AND AUTHORITES HAVING JURISDICTION AND TANK MFG. INSTRUCTIONS. 2. CONTRACTOR SHALL OBTAIN ENVIRONMENT HEALTH SERVICES APPROVAL OF ABOVE GROUND FUEL TANK, -BEFORE INSTALLATION. 3. ANCHORING TANK SHALL BE INSTALL PER TANK MANUFACTURER RECOMMENDATIONS. 3"SD&OD DN ® WALL 3"SD&OD UP ,zoo en P. nn COI( I rul ID PROJECT NORTH PROJECT NORTH SCALE 1/4 90=1 11—off SCALE 1/4 to= 1 0— to 1toGDNINWALL FOR CONT. P.O.C. 1" G W/ GC FOR CONT. 3 SEE V UP TO 3" VTR 1 TO RANGE (90 CFH) SEE 1 2» V UP TO 2" VTR 2. 2. DISHWASHER ROUGH—IN & 1/4 1 2" CW DN IN WALL FD 2" V UP IN WALL ABV. CONN. 1/2" HW W/ S.O.V. / 2 & 3/4" HOSE WASTE THRU SH 3/4it TP W/ S.O.V. & AP COU TER MOUNTED 'AIR I �� I I 1 2" CW W ANGLE STOP 1 3 q 1 GAP FITTING TO GARBAGE FOR ICE MAKER DISPOSER (TYP OF 2 PLCS) 1.E.=20.50 -- --»--._..W.C.0. (TYP)C.O.T.G. ' S 1" I I. .=20.10 (BOT. OF SLVE) 3/4" 2 S 4 1 (BOT. OF SLVE) 4„ FOR CONT. 1 n 1 2 .— -N , —1_ 2 1/2 SEE 1 2" 2, Q 1 /2" I.E.=20.50' 2» FOR CONT. 2. 2» I 3 .C.O. ------ ----------- SEE 1 1 /4» I. .=2 .38' I = (BOT. OF SLVE / 2 2. {BOT. OF SLVE) 2" I Fp I.E.=20.64 ) , 3 4 — » 3/4" 1 2" V UP TO ABV. CLG. _ _ FOR CONT. FOR CONT. 3/4 _ -' I „ SEE 1 I WB 3/4 H& CW DN 1 1/2SEE 1 2. I 3/4» 1 IN WALL 1 1/2 2. " J H ® + 20" ABV. 2�1 1 /4" P.O.C. 3/4" G W/ GC FOR CONT. FOR CONT. TO DRYER (35 CFH) 1 FIN. FLR. SEE SEE 2. 2. PAKTIAL FLS PLAN ......�� R.COR PLM FOR CONT. 1 P2. 3/4» 1 1 2„ W.C.O. (TYP) — H ®+ 20" ABV FOR CONT. /2» 3/4" ._4 / PROJECT NORTH SCALE 1 2 1/4 "=1'-0" "W/ A. P. 1 � P W/ S. 0. V. & AP 2" V UP IN WALL ABV. 2" CW DN IN WALL N=Fl FLR. W/ S.O.V. Ar A.P. 2 � 1 3/4" CW & 3/4"ALINE DN 2. oo," WC (TYP OF 2 PLCS) 4 TYP OF 3 PLCS 1 1 SEE DET. � WALL 0+ 8 —0 ABV. L /1/2 2 2 FIN. FLR. 1 ( ) I ___3" V UP TO 3" VTR f' " W/ C (1 V._ 3/4 'FOR C:C�NT ({ 2 r UK CMV 1.1 f 0�__ - f A SEE 1 SEE 2 SH 1 1/2" CW DN IN WALL 3�4" 2• 2 — — I 2» 2 4" FLUE UP THRU ROOF 1" FS I.E.=18.39' 2" 3/4" 1 1 /2" HW `DN IN WALL 1 1 /2" 1 (T� OF 2 PLCS) FOR CONT. 3/4" G DN IN WALL �� {BOT. OF SLVE) 2�► 3/ „ " SEE 1 / c SS 3/4 CW W/ ANGLE STOP FOR CONT. 4» 4 to — —4 2• CP 2 1 FOR ICE MACHINE SEE 1 I.E.=1 .17' 1 SEE DET. 4 » 2" 3 4" co » 3 / (BOT. OF SLVE) (BOT. OF SLVE) 3/4 HWR DN IN WALL _ 3/4" 1 1/2 FOR CONT. FOR CONT.'. 2 I It FOR CONT. SH (TYP OF 2 PLCS) /4"/N,2" 3 4" SEE 2 SEE 1 2 3 SEE 1 FD I» / 2, /4 2• 2 (TYP OF 3 PLCS) 12 1 CD DN IN WALL to & CONN. TO LAV. T & AP NOTE: O COMBUSTION AIR DOOR LOUVERS: (SCREENED PROOF). THE LOWER: 12" X 12" (FREE AREA) WITH IN LOWER 12" OF THE ENCLOSURE. THE UPPER: 12" X 12" FREE AREA) WITH IN UPPER 12" OF THE ENCLOSURE REFER TO ARCH. DWG'S FOR LOUVERS). PROJECT NORTH PARMAL R SCALE 1/4 *p=19 -Off 3 2 AIL PIECE 2FOR CONT. FD (TYP OF 3 PLCS)12",� SEE 1 1" 4 2R � (TYP OF 2 PLCS) �— - — — —I 3/4 / „ CD UP 2",,,y 2 I 3 2" V UP IN WALL ABV. I 1 _ 2 JI of 1" G H — — W/ A. P. 2» I I I H W/ A. P. TP WC — 1 TP 1 1 W/ S.O.V. & AP _ 41 W/ S.O.V. & AP 2» » 2„ 1 1/4's 2" CW DN IN WALL UR Iof FOR CONT. W/ S. 0. V. & A. P. 1 I SEE 1 » 2. 2" / » 2 1/2 1 1 2 2" CW DN IN WALL .E.=19.92' FOR CONT. W/ S.O.V. & A. P. BOT. OF SLVE) SEE 1 P2.1 ASmBUILTS PROJECT NORTH SCALE 1/4 $$=i ' — 0" �Ar itects Virginia Dare Tower 10470 Foothill Blvd. Rancho Cucamonga California 91730-3754 tel: 909 987 0909 fax: 909 980 9980 CONSULTANT r• P BP & Associates, Inc. consuit�g Enginsm 14471 Chambers Rd. Suits 102 Tustin, Califomia 92780 Telthone (714) 734 1m ax (714) 7341783 Hrrrcvvtu �HANJ �r f7f. CALF APPROVED JUL 3.0 ZOOZ- APPROVED SD ARC , v ,A LARRY-WOLFF C-9784 Q ktt01/31/0D , NO DATE IBY IREMARKS TOILET ROOM AND PARTIAL FLOOR PLANS DRAWN TP CHECKED TP DATE FEB. 1999 SCALE AS NOTED JOB N0. I: 98177