HomeMy WebLinkAbout2769-37EXHAUST FAN - SCHEDUL o UNIT SYMBOL EF -1 do EF -2 EF -3 EF -4 POWER SOURCE LOCATION LOCATION ROOF ROOF ROOF MANFACTURER CARRIER CARRIER CARRIER MANUFACTURER LOREN COOK LOREN COOK LOREN COOK 48SX030 48SX036 48SX036 48SX048 MODEL 195R8 -B 120R28 100R2B GAS .ELECTRIC TYPE UP -BLAST UP -BLAST UP -BLAST SEE ELECTRICAL OUTSIDE AIR -CFM SERVICE EXHAUST EXHAUST EXHAUST EXTERNAL S.P. - 'WG 0.50 0.50 0.50 FAN - CFM 5000 875 250 81.6. 82.0 82.0 83.0 EXTERNAL S.P. - "WG 0.5 0.5 0.25 64.4 CONTROL INTERLOCK FOR EF -3 & EF -4. FAN MOTOR - HP /RPM 1-1 /2 - 1142 1 /6 - 1180 1 /6 - 950 COOLING CAPACITY -MBH MOTOR DRIVE BELT BELT BELT SENSIBLE COOLING -MBH 22.1. 29.9 29.9 OUTLET VELOCITY -FPM NA NA NA 'w 60 80 80 TIP SPEED -FPM 5871 3650 2490 STANDARD AC -1 THRU AC -4 DISCHARGE UP -BLAST UP -BLAST UP -BLAST COMPRESSOR N0./RLA (EA) WHEEL TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL OUTDOOR INTERLOCK ' EXHAUST FANS EF -3 �c EF -4 TO AC -2 SUPPLY FAN OPERATION. VOLTS -PHASE 208 - 3� 120 - 1 � 120 - 10 2.6 2.8 2.8 7.2 CURB TYPE PRE -FAB. PRE -FAB. PRE -FAB. �` E X H A U S T F A N OPERATING WEIGHT LBS 200 115 90 MIN. EER /SEER REMARKS: PROVIDE ROOF CURB AND BACKDRAFT DAMPER FOR ALL EXHAUST FANS. 11.05 - / -- FAN AFUE 81x 81x 81x 82x MOTOR VOLT -PHASE 208 - 10 208 - 30 208 - 3� 208 - 30 OPERATING WEIGHT LBS 460 500 500 550 MOTOR CURE TYPE PRE -FAB PRE -FAB PRE -FAB PRE-FAB0 REMARKS: O UNIT COMPLETE WITH TIME GUARD II CONTROL O2 UNIT COMPLETE WITH OUTDOOR COIL GRILLE. 0 UNIT COMPLETE WITH FACTORY 8" HIGH ROOF CURB. CONTRACTOR SHALL CO-ORDINATE W/ G.C. ALL REQUIREMENTS AND RESPONSIBILITIES FOR INSTALLATION OF AN ADDITIONAL LEVELING CURB TO CONFORM WITH ROOF SLOPE PRIOR TO BID.CN CURB HEIGHT SHALL BE MAINTAINED AS LOW AS POSSIBLE. a4 UNIT .COMPLETE WITH BASE RAIL TYPICAL AC UNIT WIRING DIAGRAM EF -3 ? 4 UNITS WIRING DIAGRAM 208/30 208/30 E CIRC. BRKR. W MAGNETIC Sf ARTER INTERLOCK W[ APPARATUS ROOM LIGHTSWITCHES PROVIDE STATUS INDICATOR LIGHT. i` I, ELECTRICAL INTERLOCK ®HR. O BY -PAS TIMER SWITCH DISC. SW. E 0 AS-BUILTS EF EF 2 APPARATUS ROOM VENTILATION DIAGRAM TYPICAL WIRING. DIAGRAMS SCALE 1 NONE 6"X56" 3000 EXHAUST FAN - SCHEDUL o UNIT SYMBOL EF -1 do EF -2 EF -3 EF -4 POWER SOURCE LOCATION LOCATION ROOF ROOF ROOF MANFACTURER CARRIER CARRIER CARRIER MANUFACTURER LOREN COOK LOREN COOK LOREN COOK 48SX030 48SX036 48SX036 48SX048 MODEL 195R8 -B 120R28 100R2B GAS .ELECTRIC TYPE UP -BLAST UP -BLAST UP -BLAST SEE ELECTRICAL OUTSIDE AIR -CFM SERVICE EXHAUST EXHAUST EXHAUST EXTERNAL S.P. - 'WG 0.50 0.50 0.50 FAN - CFM 5000 875 250 81.6. 82.0 82.0 83.0 EXTERNAL S.P. - "WG 0.5 0.5 0.25 64.4 CONTROL INTERLOCK FOR EF -3 & EF -4. FAN MOTOR - HP /RPM 1-1 /2 - 1142 1 /6 - 1180 1 /6 - 950 COOLING CAPACITY -MBH MOTOR DRIVE BELT BELT BELT SENSIBLE COOLING -MBH 22.1. 29.9 29.9 OUTLET VELOCITY -FPM NA NA NA 'w 60 80 80 TIP SPEED -FPM 5871 3650 2490 STANDARD AC -1 THRU AC -4 DISCHARGE UP -BLAST UP -BLAST UP -BLAST COMPRESSOR N0./RLA (EA) WHEEL TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL OUTDOOR INTERLOCK ' EXHAUST FANS EF -3 �c EF -4 TO AC -2 SUPPLY FAN OPERATION. VOLTS -PHASE 208 - 3� 120 - 1 � 120 - 10 2.6 2.8 2.8 7.2 CURB TYPE PRE -FAB. PRE -FAB. PRE -FAB. �` E X H A U S T F A N OPERATING WEIGHT LBS 200 115 90 MIN. EER /SEER REMARKS: PROVIDE ROOF CURB AND BACKDRAFT DAMPER FOR ALL EXHAUST FANS. AIR. CONDITIONER SCHEDUL UNIT SYMBOL 0Q(D0 AC -1 AC -2 AC -3 AC -4 POWER SOURCE LOCATION ROOF ROOF ROOF ROOF MANFACTURER CARRIER CARRIER CARRIER CARRIER PROGRAMABLE ROOM T -STAT MODEL 48SX030 48SX036 48SX036 48SX048 SCHEDULE TYPE GAS ELECTRIC GAS ELECTRIC GAS ELECTRIC GAS .ELECTRIC INDOOR FAN -CFM 800 1250 1250. 1300 SEE ELECTRICAL OUTSIDE AIR -CFM 150 250 250 300 EXTERNAL S.P. - 'WG 0.50 0.50 0.50 0.50 EVAP. EAT - � F - DB 81.6. 82.0 82.0 83.0 EVAP. EAT - � F - WB 63.9 64.0 64.0 64.4 CONTROL INTERLOCK FOR EF -3 & EF -4. COND. EAT - �F - DB 110 110 110 110 COOLING CAPACITY -MBH 25.4 33.1 33.1 41.3 LOW VOLTAGE B SENSIBLE COOLING -MBH 22.1. 29.9 29.9 35.4 HEATING CAPACITY -MBH 'w 60 80 80 FILTER TYPE STANDARD STANDARD STANDARD STANDARD AC -1 THRU AC -4 COMPRESSOR INPUT -KW 3.0 3.75 3.75. 5.28 COMPRESSOR N0./RLA (EA) 1 / 15.0 1 / 10.9 1 / 10.9 1 / 15.0 OUTDOOR INTERLOCK ' EXHAUST FANS EF -3 �c EF -4 TO AC -2 SUPPLY FAN OPERATION. I I INDOOR FAN MOTOR FLA 2.6 2.8 2.8 7.2 POWER EXHAUST FAN MOTOR FLA �► � � �` E X H A U S T F A N MCA / MOCP 22.8/30 17.8/25 17.8/25 27.4/40 MIN. EER /SEER - / 12 12 12 11.05 - / -- FAN AFUE 81x 81x 81x 82x MOTOR VOLT -PHASE 208 - 10 208 - 30 208 - 3� 208 - 30 OPERATING WEIGHT LBS 460 500 500 550 MOTOR CURE TYPE PRE -FAB PRE -FAB PRE -FAB PRE-FAB0 REMARKS: O UNIT COMPLETE WITH TIME GUARD II CONTROL O2 UNIT COMPLETE WITH OUTDOOR COIL GRILLE. 0 UNIT COMPLETE WITH FACTORY 8" HIGH ROOF CURB. CONTRACTOR SHALL CO-ORDINATE W/ G.C. ALL REQUIREMENTS AND RESPONSIBILITIES FOR INSTALLATION OF AN ADDITIONAL LEVELING CURB TO CONFORM WITH ROOF SLOPE PRIOR TO BID.CN CURB HEIGHT SHALL BE MAINTAINED AS LOW AS POSSIBLE. a4 UNIT .COMPLETE WITH BASE RAIL 2 4' AIR .DISTRIBUTION SCHEDULE SYM. MFR. do MODEL � SIZE CFM MAX. NECK MAX. S.P. TYPE DAMPER REMARKS CAPACITY VELOCITY N.C. DROP �� KRUEGER 1240P 6"X6" 0-180 400 30 .06 MODULAR NONE FRAME 23 FOR T -BAR PERFOR. �s 100X10" 181-280 s -a 12"X12" 261-400 s -t 14"X14" 401-550 8"X8" 0-180 O.B.D. FRAME 22 FOR GYP.BOARD CEILING s-� 10"X10" 181-280 12"X12" 281-400 s-� KRUEGER 880H 22"X6" 350 35 DEG. _ ADJUSTABLE s -e KRUEGER 880H 28"X8" 600 35 DEG. _ ADJUSTABLE KRUEGER 1190 22"X22" 0-1400 .03 PERFOR. NONE FRAME 23 FOR T -BAR T� KRUEGER 1190, 22"X22" 0-1400 FRAME 23 FOR T -BAR T-2 KRUEGER C1190 8"X8" 0-180 FRAME 22 FOR GYP.BOARD CEILING a KRUEGER C1190 12"X12" 300 FRAME 22 FOR GYP.BOARD CEILING R"z KRUEGER 1190 16"X16" 0-600 FRAME 22 FOR GYP.BOARD CEILRM R ING R -a KRUEGER S80H 22"X6" 350 45 DEG. - �-a 36"X12" 800 - E-� 8"X8" 0-180 O.B.D. - E-_ 10"X10" 181-280 - E-3 16"X32" 2000 -' E-4 1 ��-POWER SOURCE SEE AC UNIT POWER SOURCE SCHEDULE SEE EF UNIT PROGRAMABLE ROOM T -STAT SCHEDULE .DISCONNECT SWITCH SEE ELECTRICAL FDS DRAWINGS CONTROL INTERLOCK FOR EF -3 & EF -4. sum S LOW VOLTAGE B WIRING �uow r aREE?I G AC -1 THRU AC -4 INTERLOCK ' EXHAUST FANS EF -3 �c EF -4 TO AC -2 SUPPLY FAN OPERATION. I I AC -2 SUPPLY .FAN SHALL OPERATE CONTINUOUSLY. AC -2 SUPPLY FAN SHALL OPERATE CONTINIOUSLY AND SHALL BE E X H A U S T F A N BITER -LOCKED WITH EF -3 do EF -4. FAN MOTOR SEE NOTE ON M2.1 REGARDING ALTERNATE BID ITEM. MOTOR TYPICAL AC UNIT WIRING DIAGRAM EF -3 ? 4 UNITS WIRING DIAGRAM 208/30 208/30 E CIRC. BRKR. W MAGNETIC Sf ARTER INTERLOCK W[ APPARATUS ROOM LIGHTSWITCHES PROVIDE STATUS INDICATOR LIGHT. i` I, ELECTRICAL INTERLOCK ®HR. O BY -PAS TIMER SWITCH DISC. SW. E 0 AS-BUILTS EF EF 2 APPARATUS ROOM VENTILATION DIAGRAM TYPICAL WIRING. DIAGRAMS SCALE 1 NONE va"C.i alleGis Virginia Dare Tower 10470 Foothill Blvd Rancho Cucamonga California 91730-3154 tel: 909 987 0909 fax: 909 980 9980 CONSULTANT t P BP &Associates, Inc. Consulting Engineers 14471 Chambers Rd. Suite 102 Tustin California92380 Tele hone .(714) 7341777 FPox (714) 734 1783 APPROVED �EssOF rAIL /� W APPROVED AS-BIJILTS JUL 3 a zoozV% APPROVED AR�y�F����' � LARRY-WOLFF � C-9784 Q kMk01/31/00 pF GP,, NO DATE BY REMARKS MECHANICAL SCHEDULES & CONTROLS N DRAWN CHECKED - CHECKED AB DATE SEP. 1999 SCALE AS NOTED JOB N0. I: 98177