SLAB & REIN
PER PLAN
KNOCK—OUT PANEL
FOR FUTURE INLET
#4 0 18" o. c
BOTH FACES
SLAB & REINF
PER PLAN
12"
TEMPORARY CONC. CLOSURE WALL
AT END OF PROJECT
BULK HEAD @END OF BOX CULVERT O
NOT TO SCALE
#5 0 12" O.C. DOWELS
WRAP NEW SIDE ONLY
NEW CONC.
12" d 12"
3/4" DRILLED HOLE
FILL W/ APPROVED
EPDXY.
EXISTING CONC.
►— n"
PLACE A 1/2" EXPANSION
JOINT A MAX OF 2 TIMES
SPAN OR HEIGHT
STRUCTURAL NOTES
1.
DIMENSIONS FROM FACE OF CONCRETE TO STEEL ARE TO CENTER OF BAR AND
SHALL BE 2 INCHES UNLESS OTHERWISE SHOWN.
2.
CONCRETE DIMENSIONS SHALL BE MEASURED HORIZONTALLY OR VERTICALLY
ON THE PROFILE, AND PARALLEL TO OR AT RIGHT ANGLES (OR RADIALLY) TO
CENTERLINE OF CONDUIT ON THE PLAN EXCEPT AS OTHERWISE SHOWN.
EXISTING PLACE A 1/2"
3.
ALL BAR BENDS AND HOOKS SHALL CONFORM TO THE AMERICAN CONCRETE
CONSTRUCTION EXP. JOINT
INSTITUTE'S "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", 2001
EDITION, SECTION 7.1.
NEW
CONSTRUCTION
4.
PLACING OF REINFORCEMENT SHALL CONFORM TO THE AMERICAN CONCRETE
INSTITUTE'S " BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", 2001
EDITION, SECTION 7.5.
5.
TRANSVERSE CONSTRUCTION JOINTS SHALL NOT BE PLACED WITHIN 30 INCHES OF
MANHOLE OR JUNCTION STRUCTURE OPENINGS.
6.
TRANSVERSE CONSTRUCTION JOINTS IN WALLS AND SLABS SHALL BE IN THE SAME
PLANE. NO STAGGERING OF THE JOINTS WILL BE PERMITTED. TRANSVERSE
CONSTRUCION JOINTS SHALL BE NORMAL OR RADIAL TO THE CENTERLINE OF
REMOVE CONC PARALLEL TO
CONSTRUCTION.
PARAPET & SPLICE TO EXIST'G
7.
THE TRANSVERSE REINFORCING STEEL SHALL TERMINATE 1 INCHES FROM THE
LONGIT REBAR IN ALL MEMBERS
CONCRETE SURFACES UNLESS OTHERWISE SHOWN ON THE STRUCTURAL DETAILS.
8.
EXPOSED EDGES OF CONCRETE MEMBERS SHALL BE ROUNDED OR BEVELLED.
CULVERT EXTENSION
9.
NO SPLICES IN TRANSVERSE STEEL REINFORCEMENT SHALL BE PERMITTED OTHER
THAN SHOWN ON DRAWING WITHOUT THE APPROVAL OF THE ENGINEER. NO MORE
THAN TWO SPLICES WILL BE PERMITTED IN ANY LONGITUDINAL BAR BETWEEN
N 0 T TO SCALE
TRANSVERSE JOINTS. SPLICES SHALL BE STAGGERED.
10.
LONGITUDINAL STEEL SHALL BE LAPPED 20 BAR DIAMETERS AT SPLICES.
TRANSVERSE STEEL SHALL BE LAPPED 30 BAR DIAMETERS AT SPLICES.
11.
LONGITUDINAL STEEL SHALL BE CONTINUOUS AND EXTEND THROUGH ALL
CONSTRUCTION JOINTS.
12.
UNLESS OTHERWISE SHOWN ON THE DRAWINGS, TRANSVERSE JOINT KEYWAYS (IN
SLABS, WALLS AND WINDOWS), AS DETAILED FOR LONGITUDINAL KEYWAYS AT THE
BASE OF THE WALLS, SHALL BE PLACED AT THE END OF EACH POUR, BUT THE
SPACING THEREOF SHALL NOT EXCEED 50 FEET OR BE LESS THAN 10 FEET. ALL
CONSTRUCTION JOINTS IN BOTTOM OF SLAB, TOP OF SLAB, AND SIDE WALLS SHALL
BE IN THE SAME PLANE. NO STAGGERING OF THE JOINTS WILL BE PERMITTED.
13.
UNLESS OTHERWISE SHOWN ON THE DETAILS, IN CURVED SECTIONS TRANSVERSE
BARS SHALL BE PLACED RADIALLY. STRAIGHT TRANSVERSE BARS IN TOP AND
BOTTOM SLABS SHALL BE SPACED AS SHOWN ON THE THE TYPICAL SECTIONS.
SPACING SHALL BE AT THE CENTERLINE OF THE BARREL ON THE OUTSIDE OF THE
CUVE FOR DOUBLE BARREL BOXES. STRAIGHT BARS AND L—BARS IN WALLS
SHALL BE SPACED AS SHOWN IN THE TYPICAL SECTIONS, WITH THE SPACING
MEASURED BETWEEN THE VERTICAL LEGS OF THE BARS.
14.
AT THE BEGINNING AND ENDING OF ALL POURS, A CURTAIN OF REINFORCEMENT
COMPOSED OF B, C, C2, D, CW, F, G, AND H BARS SHALL BE PLACED 3 INCHES
FROM THE TRANSVERSE CONSTRUCTION JOINT.
STRUCTURAL
DESIGN CRITERIA
LIVE LOAD
H2O — S16 — 44 UNLESS OTHERWISE NOTED
DEAD LOAD
EARTH LOAD PER MORSTON'S FORMULA: w = 125 PCF
Ku = Ku' = 0.150
Bd = OUTSIDE WIDTH OF BOX PLUS 4 FEET
SIDE EARTH: 70 PSF PER FOOT OF DEPTH
INTERNAL WATER PRESSURE: 62.4 PSF PER FOOT OF DEPTH
WEIGHT OF CONCRETE: 150 PCF
ALLOWABLE STRESSES
f,' = 3250 PSI (AT 28 DAYS) (SPECIAL INSPECTION IS REQUIRED PER GREEN BOOK)
f� = 1462 PSI
CONNECTION BETWEEN EXISTING AND NEW BOX O3 n = 9
SHEAR AND BOND STRESSES PER A.C.I. 318 — 2000
NOT TO SCALE REINFORCING STEEL: ASTM A615 GRADE 60
Thornton-Tomasetti/ Esso p O
Coil & Wlsh Engmeerso%*
V-KEt�r
15892 South Pasadena Ave. Tustin, CA 92780-5415 W No. S 04029
(714) 505.2751- (714) 505.1689 fax Exp 9_04 DIAL TWO WORKING
mm Yak Iff _N rk NJ 11vmbut cr Mor; MA * � BEFORE DAYS BEFORE
CMomm L -0Wk% 7X -orwW Om. CA flC T 4Q`�`. YOU DIG YOU III G
l0B# 66162B '�jf' �Et TOLL FREE 1-800-227-2600
A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT
(m r 1 «. .
DATE I M. I CITY I DATE
SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT
COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL
SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER,
THE CITY ENGINEER MAY REQUIRE REVISIONS TO THE PLANS TO
BRING THEM INTO CONFORMANCE WITH CONDITIONS AND
STANDARDS IN EFFECT.
Q�pFESS/CN
J 4�! F
No. 36052 m
Lj
Exp. 5,430/2004
CIV1�- �P
15. THE VERTICAL WALL STEEL IN INTERIOR WALLS AND IN THE INTERIOR FACE OF THE
EXTERIOR WALLS MAY BE SPLICED AT THE CONSTRUCTION JOINT AT THE BASE OF
THE WALL THE SPLICES SHALL BE 20 BAR DIAMETERS IN LENGTH.
16. IN ALL SECTIONS, LAP C AND C2 BARS. THE VERTICAL LENGTH OF C AND C2
BARS HAS BEEN CALCULATED FOR A 4 INCH STARTER WALL. IF THE HEIGHT OF
THE STARTER WALL IS VARIED, THE VERTICAL LENGTH OF THE C AND C2 BARS
SHALL BE VARIED CORRESPONDINGLY SO AS TO MAINTAIN A 30 DIAMETER LAP
BETWEEN THE TWO BARS. THE LAPS SHALL BE BASED ON THE SMALLER BARS.
17. REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60. ALL REINFORCING
SHALL BE FROM IDENTIFIED STOCK WITH MILL ANALYSIS SUPPLIED.
18. FOR BOXES WITH COVER GREATER THAN THOSE SHOWN IN TABLE, USE NEXT GREATER
COVER BOX CULVERT SIZE AND REINFORCEMENT.
19. QUANTITIES ARE APPROXIMATE AND FOR DESIGN PURPOSES ONLY.
20. FOR BOXES WITH SPAN LESS THAN THOSE SHOWN IN TABLE ( SUCH AS TRANSITION)
USE NEXT GREATER SIZE BOX CONCRETE DIMENSION AND REINFORCEMENT. MAKE
NECESSARY CHANGES IN BAR LENGTHS AND QUANTITIES.
Prepared By:
ALLARD ENGINEERING
CITY OF FONTANA, CALGOMA
BASELI:"" AVE= STOW RASE 2 -STAGE Z
DRAWN BY:
YN STRUCMAL DUALS AS S10WN
DESIGNED BY: DATE:
YN SEPTEMBER, 2002
CHECKED BY: APPRO' BY: DRAWING NO.: 4
RJA -27 -oz 30 9
OTY ENGINEER R.C.E. 51152 DATE: