HomeMy WebLinkAbout2269-PE-0006POLE
4' PROJECTION #6 GROUND WIRE TO
LIGHT POLE GROUND LUG.
BASE COVER
— o
' -
f- GROUND CLAMP
v (SEE NOTE #6)
GROUT 97 1. 0II I 4 ANCHOR BOLTS
" DIA. X 36 X 4'-
Q_ I I 1 ( i ( I ) Ii 8 NUTS AND FLAT WASHERS
POWER CIRCUIT, SEE PLAN • Q •
Q•. •- a. I I L I I I I I t>GRADE ti--
a I i I" DIA II
_ Q I 1
4' SO. WEATHERPROOF BOX (FOR CCTV) ANCHOR BOLTS I I 1 1 11 I
4' SO. WEATHERPROOF WITH BARRIER AND GASKETED COVER Q . I I 1 ( I ( I �11 011,_�
BOX WITH GASKETED �.,�,) I I Li
COVER COVER FOR PA k LL
12' PIGTAIL POWER CIRCUIT 1
SEE PLAN FOR SIZE
(( I I v 1 11
10
RACEWAYS
PULL CORD —�/z' HOLE WITH GROMMET CL
ij
PULL CORD \\
// \\
/ p
MOUNT 12' ABOVE TOP OF RACEWAY
PLATFORM (TYP.) DETAIL An -
a °
SCALE: 3'
FOUNDATION NOTES:
POWER CIRCUIT. SEE PLAN
I. CONCRETE SHALL BE CLASS 560-C-3250 WITH A 12_#5 a. a
MAXIMUM SLUMP OF 4 INCHES AND CURED FOR VERTICAL BARS
TEN DAYS BEFORE THE LIGHT STANDARD IS ERECTED.
FLEXIBLE METAL CONDUIT WITH PULL
CORD, INSTALL INSIDE POLE (CCTV) -� #4 SPIRAL THREE
2. RACEWAY TRENCH SHALL BE BACKFILLED AND FiRMLY � — EXTRA TURNS.
COMPACTED BEFORE THE LIGHT STANDARD IS ERECTED., TOP A BOTTOM (NOTE 3> .,
i/2' FLEXIBLE METAL CONDUIT WITH PULL
CORD, INSTALL INSIDE POLE (PA) 3. USE #4 SPIRAL AT 6" PITCH OR SUBSTITUTE #4 TIES
AT 6' ON CENTER. 44 TIES SHALL HAVE 1 ' -6 LAP. A A
4. EXCAVATION FOR FOUNDATION SHALL BE MADE WITH
AN AUGER OF THE SAME DIAMETER AS THE FOUNDATION.
SOIL SURROUNDING THE FOUNDATION SHALL REMAIN =
IN ITS UNDISTURBED STATE.
HANDHOLE
5. THE ANCHOR BOLTS SHALL BE PROPERLY SECURED IN PARK I NG LOT AND STREET
PLACE, USING FACTORY SUPPLIED TEMPLATE. LIGHTING STANDARD FOUNDATION DETAIL
ELECTRICAL RACEWAY, SEE 6. PROVIDE GROUND CLAMP AND SECURE TO VERTICAL BAR OF
PLAN FOR CONTINUATION SCALE: NONE
THE REBAR CAGE WITH #6 GROUND WIRE PIGTAIL TO LIGHT
POLE GROUND LUG.
LIGHT POLE FOUNDATION
PA
CCTV
P 12' MAXIMUM WIDTH EXCEPT AS
APPROVED .BY THE CONSTRUCTION
MANAGER
RACEWAY
WIRING I N LIGHT POLESPLATFORM (TYP) J CLU / Z� <
o+ WARNING TAPE AS SPECIFIED
_ z
Q
M N
M
M
000RACEWAY AND WIRING AS PER
0 PLANS, COMPLETE WITH
TOP V I EW�' may/ GROUND*
INSULATED EOU i PMENT
SECTION A -A ///� u D WIRE.
LIGHTING STANDARD FOUNDATION
SCALE : i"=1,_O"
SCALE 1 . =1 , -O.
Z
w TYPICAL WIRING IN TRENCH DETAIL
YZF
-
CcLLI
0 J
I'
SCALE: NONE
J
U
N _
I r �
Z Z
cL w
Cr
O
-
U Q
Q Z - Cr v
Z cn
Ow
CITY OF FONTANA,' CALIFORNIA
U o CHECKED BYo,
uJ M 'fC.• APPROVED, �'°= ,. .K•c.�; �+�"° °� '`;. OR. N0. DATE,
CITY ENGINEER RE.
Z w
Information confidential DESIGNED BY
_ ,
-— a J l plans, drawings, ngs, spec i f l SOUTHERN CONTRACT' N0.
R. SLAY Q U HERN CALIFORNIA REGIONAL RAIL AUTHORITY C6320
cations. and or information COFAt LITER RAIL SAN BERNARDINO LINE
furnished herewith sha I i DRAWN BY DRAWING NO.
remain the property of the SCRRAProfessional Engineering Services an
d staff Support forthe MetroiI nk Regional Rail System A. SHAMSABAD 16777 ORANGE
E 111A i f
ONTANA CALIFORNIA
� Southern California Regional !
LO w Rail Authority and CHECKED BY
PE 0006
ri PAR51:3i'�15 ®E L
o w shall be held confident►aI: R. SLAY E INC.
®-dftLru&As" TREVISION
1TR.i ,I . - loa west walnut Street SKEET N0.
and shall not be used for. .,. � eet .
F- any purpose not provided APPROVED BY Pasadena California
a 9 Ic4
ww for in agreements with the
D. KRV
F7 LIGHTING STANDARD DE:2 /6/93 ISSUED FOR BID TAILS
California Regionai
Rail Authority. DATE SCALE
REV DATE. DESCRIPTION
1,!>SUB � .,�„
sue. APP. 7/6/93 APPROVED:
RELEASED
NONE