A. THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES NECESSARY
TO PROTECT EXISTING FACILITIES, WHICH ARE TO REMAIN IN PLACE, FROM
DAMAGE. ANY FACILITIES DAMAGED BY THE CONTRACTOR'S OPERATIONS
SHALL BE EXPEDITIOUSLY REPAIRED OR RECONSTRUCTED TO THE ENGINEER'S
SATISFACTION AT THE CONTRACTOR'S EXPENSE WITHOUT ADDITIONAL
COMPENSATION.
B. LOCATION OF EXISTING PIPING AND EQUIPMENT IS BASED ON RECORD
DRAWINGS AND FIELD INFORMATION.
CONTRACTOR SHALL FIELD LOCATE ALL EXISTING PIPING AND EQUIPMENT
THAT CONFLICTS WITH CONSTRUCTION AND REMOVE AND REPLACE AS
REQUIRED. AFTER CONSTRUCTION IS COMPLETE, EXISTING PIPING SYSTEMS
SHALL BE RETURNED TO THE SAME OR BETTER CONDITION THAT AS BEFORE.
ALL FIELD RELOCATION OF EXISTING PIPING SHALL BE RECORDED ON RECORD
DRAWINGS. IN AREAS WHERE GAS PIPING IS LOCATED, CONTRACTOR SHALL
POTHOLE AND LOCATE GAS PIPING BEFORE EXCAVATION OF THE AREA.
C. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE
TO THE EXISTING STRUCTURES OR OTHER EXISTING IMPROVEMENTS TO REMAIN.
CONTRACTOR SHALL ALSO PROVIDE ALL NECESSARY BRACING, SCAFFOLDING OR
OTHER MEASURES NECESSARY FOR CONSTRUCTION.
D. REMOVAL, ABANDONMENT OR TEMPORARY RELOCATION OF EXISTING PIPES OR
UTILITIES SHALL BE SCHEDULED WITH THE ENGINEER TO AVOID UNNECESSARY
DISRUPTION OF PLANT OPERATIONS.
E. ELEVATIONS SHOWN ARE BASED UPON THE AS -BUILT DRAWINGS. CONTRACTOR
SHAD_ FIELD VERIFY AND ADJUST ELEVATIONS AS REQUIRED TO MAINTAIN
DIMENSIONAL RELATIONSHIPS DEPICTED IN DRAWINGS.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING AND
SUPERVISING AN AIR MONITORING PROGRAM WHILE WORK IS BEING PERFORMED
ON, IN OR ADJACENT TO ANY OF THE ENCLOSED SPACES. THE CONTRACTOR
SHALL COMPLY NTH CAL -OSHA AND ALL OTHER LOCAL AGENCY REQUIREMENTS.
G. CONTRACTOR SHALL RESTORE ALL EXISTING PAVED AREAS, GUARDRAILS AND
HANDRAILS DISTURBED DURING CONSTRUCTION INCLUDING INSTALLATION OF
PIPELINES, DRAINS AND ELECTRICAL DUCTS TO ORIGINAL CONDITION. CURB
AND GUTTER, AREA DRAINS, AND ALL SITE DRAINAGE AFFECTED BY THE WORK
SHALL BE RETURNED TO THE SAME OR BETTER CONDITION AFTER WORK IS
COMPLETED.
H. THE CONTRACTOR SHALL RESTORE ALL LANDSCAPING TO CORRECT GRADE UPON
COMPLETION. THIS SHALL INCLUDE REPLANTING OF TREES OF COMPARABLE
SIZE TO EXISTING (MIN. 36" BOX) FOR ANY DESTROYED BY THE PROJECT,
WITHIN 45 DAYS OF COMPLETION.
I. THE CONTRACTOR SHALL COMPLY WITH STATE DEPARTMENT OF HEALTH
SERVICES CRITERIA FOR THE SEPARATION OF POTABLE WATER MAINS AND
SANITARY SEWERS AS SET FORTH IN SECTION 64630, TITLE 22 OF THE
CALIFORNIA ADMINISTRATIVE CODE.
J. ADJUST ALL MANHOLES, VALVE BOXES AND PULL BOXES TO FINISHED GRADE
UNLESS OTHERWISE SHOWN OR DIRECTED. MANHOLES IN OPEN, UNPAVED AREAS
SHALL BE SET SIX (6) INCHES ABOVE GRADE.
K. THE CONTRACTOR SHALL GIVE TWO 2 WEEKS ADVANCE NOTICE TO OPERATIONS
FOR ANY SHUTDOWN(S) OF EQUIPMENT AND 72 HOURS PRIOR TO SHUTDOWN
CONTRACTOR SHALL AGAIN NOTIFY OPERATIONS. (SEE SPECIAL CONDITIONS)
L THE CONTRACTOR SHAD_ SCHEDULE HIS WORK TO CONTINUOUSLY MAINTAIN
PLANT OPERATIONS AND SHALL NOT UNDULY RESTRICT PLANT ACCESS OR
CIRCULATION.
M. THE CONTRACTOR SHALL PROVIDE ADEQUATE SANITARY CONVENIENCES FOR THE
USE OF ALL PERSONS AT THE CONSTRUCTION SITE OF THE WORK. SUCH
CONVENIENCES SHALL INCLUDE CHEMICAL TOILETS OR WATER CLOSETS LOCATED
AT APPROPRIATE LOCATIONS. AT COMPLETION OF THE WORK ALL SUCH
CONVENIENCES SHALL BE REMOVED AND THE SITE LEFT IN SANITARY CONDITION.
N. THE CONTRACTOR SHALL FURNISH POTABLE WATER FOR A DRINKING SOURCE
OTHER THAN THE EXISTING PLANT UTILITY WATER SUPPLY, WHICH SHALL MEET
ALL THE REQUIREMENTS OF THE COUNTY AND STATE HEALTH DEPARTMENTS.
CONTRACTOR SHALL ALSO SUPPLY AMPLE SIGNS THROUGHOUT THE WORK SITE
AREA ADVISING HIS EMPLOYEES THAT THE PLANT WATER IS NOT POTABLE.
0. THE CONTRACTOR SHALL PROVIDE AT HIS OWN COST ALL ELECTRICAL POWER
NECESSARY FOR CONSTRUCTION, TESTING, GENERAL AND SECURITY LIGHTING
AND ALL OTHER PURPOSES, WHETHER SUPPLIED THROUGH TEMPORARY OR
PERMANENT FACILITIES.
P. THE CONTRACTOR SHALL NOTE THAT THERE MAY BE OTHER PROJECTS UNDER
CONSTRUCTION AT THIS SITE AND/OR A NEARBY SITE. CONTRACTOR SHALL
COORDINATE WITH THE OTHER CONTRACTORS PRESENT ON THE SITE DURING
THE COURSE OF CONSTRUCTION.
Q. CONTRACTOR SHALL REPLACE ALL ASPHALT CONCRETE PAVEMENT AS SHOWN
IN DETAIL 'A', HEREON.
Zig •
3
N A. LAY PIPE TO UNIFORM GRADE BETWEEN INDICATED ELEVATION POINTS.
= MINIMUM COVER SHALL BE 3'-0* UNLESS OTHERWISE SHOWN.
B. SIZE OF FITTINGS SHOWN ON DRAWINGS SHALL CORRESPOND TO ADJACENT
STRAIGHT RUN OF PIPE, UNLESS OTHERWISE INDICATED. TYPE OF JOINT AND
o
0 FITTING MATERIAL SHALL BE THE SAME AS SHOWN FOR ADJACENT STRAIGHT
c
RUN OF PIPE.
C. LOCATION AND NUMBER OF PIPE HANGERS AND PIPE SUPPORTS SHOWN IS
ONLY APPROXIMATE. FINAL SUPPORT REQUIREMENTS SHALL BE DETERMINED
IN THE FIELD AND APPROVED BY THE ENGINEER PRIOR TO INSTALLATION.
,° MAXIMUM SPACING SHALL BE AS SPECIFIED
: D. APPROPRIATE STANDARD WALL PIPE DETAIL SHALL BE USED WHEREVER PIPING
PASSES FROM A STRUCTURE TO BACKFILL
Q
v
c Underground Service Alert
3
w o Call: TOLL FREE
t` 1-800
227-2600
0
j' Two WORKING DAYS BEFORE YOU DRG
0
0
L
a.
� REV
DATE I BY I DESCRIPTION
DESIGNED BY: T. Renner
DRAWN BY: C. Buzoni
CHECKED BY: M. Thornton
A GEAER4L MW MOTES CGbiIVT.J�
E. ALL FLEXIBLE CONNECTORS OR FLANGED COUPLING ADAPTERS SHOWN ON
DRAWINGS BELOW GROUND SHALL BE PROVIDED WITH THRUST TIES, BLOCKS,
OR ANCHORS UNLESS OTHERWISE NOTED. THRUST PROTECTION SHALL BE
ADEQUATE FOR THE TEST PROCEDURES SPECIFIED.
F. SYMBOLS, LEGENDS, AND PIPE USE IDENTIFICATIONS SHOWN SHALL BE
FOLLOWED THROUGHOUT THE DRAWINGS, WHEREVER APPLICABLE. ALL OF THE
VARIOUS APPLICATIONS ARE NOT NECESSARILY USED IN THE PROJECT.
G. ALL PIPING SPECIFIED TO BE PRESSURE TESTED, EXCEPT FLANGED, WELDED
GROOVED END OR SCREWED PIPING, SHALL BE PROVIDED WITH THRUST
PROTECTION AT ALL DIRECTION CHANGES, UNLESS OTHERWISE NOTED.
H. NUMBER AND LOCATION OF UNIONS SHOWN ON DRAWINGS ARE ONLY
APPROXIMATE. PROVIDE ALL UNIONS NECESSARY TO FACILITATE CONVENIENT
REMOVAL OF VALVES AND MECHANICAL EQUIPMENT.
I. UPON APPROVAL BY THE ENGINEER, ALL PIPELINES SHOWN ON DRAWINGS TO
BE ABANDONED SHALL BE PROPERLY CUT AND PLUGGED WITH NON-METALLIC
GROUT OR CEMENT CONCRETE.
C 0A6*7R 71Ci1N MOTE&
�1 CONSTRUCT
POLYETHYLENE ENCASED 30" AND 24", PRESSURE CLASS 200, DUCTILE IRON
PIPE (DIP) AND FITTINGS, BEDDING, TRENCH REPAIR, ASPHALT CONCRETE PAVEMENT,
AND PCC PAVEMENT PER DETAIL 'A', HEREON.
O2 CONSTRUCT
POLYETHYLENE ENCASED 30" AND 24", PRESSURE CLASS 350, DUCTILE IRON
PIPE (DIP) AND FITTINGS, BEDDING, TRENCH REPAIR, ASPHALT CONCRETE PAVEMENT,
AND PCC PAVEMENT PER DETAIL 'A', HEREON.
O CONSTRUCT
2-5" POLYVINYL CHLORIDE (PVC) CONDUIT AND FITTINGS, BEDDING, TRENCH
REPAIR, ASPHALT CONCRETE PAVEMENT, AND PCC PAVEMENT PER DETAIL 'A', HEREON.
O4 CONSTRUCT
2-42" STEEL CASINGS (0.563 INCH MINIMUM THICKNESS, RESPECTIVELY).
O5 CONSTRUCT
36" EXTRA STRENGTH VITRIFIED CLAY PIPE (VCP) SEWER, BEDDING AND
TRENCH REPAIR PER DETAIL 'A', SHEET 2.
O6 CONSTRUCT
AIR VAC/RELEASE SYSTEM, SIZE AS NOTED.
�7 CONSTRUCT
8' MANHOLE PER STANDARD PLANS FOR PUBLIC WORKS CONSTRUCTION
STANDARD PLAN NO. 200-2.
O CONSTRUCT
BALLARD.
O CONSTRUCT
4' x 4' PRECAST CONCRETE HANDHOLE/PULLBOX, HS -20 RATED, WITH
4" MINIMUM
WALL THICKNESS, OLDCASTLE PRECAST OR APPROVED EQUAL
10 CONSTRUCT
PIPE CAP.
11 REMOVE AND REPLACE EXISTING CURB AND GUTTER, SIDEWALK, CONCRETE BUS BAY,
ROCK SWALE, LANDSCAPING, AND IRRIGATION IN CONNECTION LOCATION.
LEGOVISMASOL&
EXISTING FIRE HYDRANT
k--
EXISTING WATER VALVE
Pa
- STA.
67+00.00
EXISTING POWER POLE
Nil B
EXISTING MAILBOX
"I E
EXISTING WATER METER
- STA.
EXISTING EDGE OF PAVEMENT
EXISTING TREE
L08
EXISTING SHRUB
-
EXISTING STREET LIGHT
ro a
EXISTING MANHOLE
11 OF 12
EXISTING SURVEY CONTROL
R/W
EXISTING RIGHT-OF-WAY
- STA.
PROPOSED SEWER
O
PROPOSED MANHOLE
L10
PROPOSED LATERAL
OU
UTILITY INTERFERENCE FLAG (APPROXIMATE LOCATION OF INTERFERENCE WITH
TYPE OF UTIUTY INDICATED BY. W -WATER; G -GAS; T -TELEPHONE; SD -STORM
DRAIN; S -SEWER; E -ELECTRIC; TV -CABLE TELEVISION; IR -IRRIGATION; FO -FIBER
OPTIC; U -UNKNOWN UTILITY).
RAW OF BEAMYO
CENTERLINE OF SAN BERNARDINO AVENUE BETWEEN MULBERRY AVENUE AND CALABASH AVENUE
BEING N89'27'11 "E PER PARCEL MAP 16903, RECORDED IN PARCEL MAP BOOK 208, PAGES 68
THROUGH 71, RECORDS OF SAN BERNARDINO COUNTY.
1" IRON PIPE, TAGGED SAN BERNARDINO COUNTY SURVEYOR, PER SURVEY CONDUCTED BY
ASSOCIATED ENGINEERS IN AUGUST 1997. LOCATED AT THE CENTERLINE INTERSECTION OF
SAN BERNARDINO AVENUE AND CALABASH AVENUE.
ELEVATION: 1064.21'
V V A
0.69984
Exb.9-30-08 /
&b, �,Vlti
�_OF CAL) -
DATE: 04/07 PREPARED BY:
DATE: 04/07 TKE Engineering, Inc.
DATE: 04/07 4446 Central Avenue
Riverside, Ca. 92506
RING (951) 680-0440
REVIEWED BY: I.E.UA Mir T. Fattahi, P.E. DATE:
APP'D Project Manager
ERE NCE
ON] 'r
GENERAL
1 OF 12 G01 COVER SHEET
2 OF 12 CO2 GENERAL NOTES, CONSTRUCTION NOTES, AND DRAWING LIST
CIVIL
3 OF 12
L01
FORCEMAIN
PLAN/PROFILE STA. 8+56f -
STA. 19+00.00
4 OF 12
L02
FORCEMAIN
PLAN/PROFILE STA. 19+00.00
- STA.
29+00.00
5 OF 12
L03
FORCEMAIN
PLAN/PROFILE STA. 29+00.00
- STA.
39+00.00
6 OF 12
L04
FORCEMAIN
PLAN/PROFILE STA. 39+00.00
- STA.
49+00.00
7 OF 12
L05
FORCEMAIN
PLAN/PROFILE STA. 49+00.00
- STA.
59+00.00
8 OF 12
L06
FORCEMAIN
PLAN/PROFILE STA. 59+00.00
- STA.
67+00.00
9 OF 12
L07
FORCEMAIN
PLAN/PROFILE STA. 67+00.00
- STA.
77+00.00
10 OF 12
L08
FORCEMAIN
PLAN/PROFILE STA. 77+00.00
- STA.
88+00.00
11 OF 12
L09
FORCEMAIN
PLAN/PROFILE STA. 88+00.00
- STA.
96+49.96
12 OF 12
L10
CONSTRUCTION DEETAILS
U71I7Y MOT/:CA7M L/ST
CITY OF FONTANA
CUCAMONGA VALLEY WATER DISTRICT
FONTANA WATER COMPANY
PUBLIC WORKS DEPARTMENT
ATTENTION: TED MUNSON/HUGO
BORJA
ATTENTION: LUIS MONTENEGRO
ATTENTION: CURTIS AARON
P.O. BOX 638
P.O. BOX 6010
16489 ORANGE WAY
RANCHO CUCAMONGA,
CA
EL MONTE, CA 91734-2010
FONTANA, CA 92335
91729-0638
(626) 448-6183
(909) 350-6760
(909) 987-2591
SOUTHERN CALIFORNIA GAS COMPANY MWD METROPOLITAN WATER
ATTENTION: RON SILVER DISTRICT OF SOUTHERN CALIFORNIA
P.O. BOX 2300 ATTENTION: KATHY MEYER
CHATSWORTH, CA 91313-2300 P.O. BOX 54153
(818) 701-4536 LOS ANGELES, CA 90054-0153
(213) 217-7663
SOUTHERN CALIFORINA EDISON COMPANY
FACILITIES MAPPING, BLDG. D PRAXAIR, INC.
ATTENTION: KIMBERUE GURULE HYDROGEN OPERATIONS
P.O. BOX 11982 ATTENTION: CURTIS STUBBINGS
SANTA ANA, CA 92711-1982 5705 EAST AIRPORT DRIVE
(714) 796-9932 ONTARIO, CA 91761
(909) 974-5105
COUNTY OF SAN BERNARDINO
DEPARTMENT OF PUBLIC WORKS TIME WARNER TELCOM
FLOOD CONTROL ATTENTION: BART VANWEY
825 EAST THIRD STREET 3281 GUASTI ROAD, STE. 350
SAN BERNARDINO, CA 92415-0835 ONTARIO, CA 91761
(909) 387-7995 (909) 456-3652
UNDERGROUND SERVICE ALERT
(800) 227-2600
PACIFIC BELL
ATTENTION: JAMES ZIELINSKI
1265 VAN BUREN STREET, RM. 180
ANAHEIM, CA 92807
(714) 666-5415
SAWCUT OR COLD PLANE
FOR TRENCHING.
2' OR LESS FROM 2" MIN. SAWCUT OR COLD
EDGE, REMOVE AND TRENCH /PLANE 1' FROM TRENCH CUTS.
INCLUDE IN REPAIR. i /
A.C. PAVEMENT TO BE 4" -
MIN. AND 1" THICKER THAN
EXISTING. TOP 1"-2" TO
BE PER SECTION 8.5 OF
COUNTY SPECIFICATIONS.
INLAND EMPIRE UTILITIES AGENCY
A Municipal Water District
LOCATION MAILING ADDRESS
6075 Kimball Avenue Post Office Box 9020
Chino, California 91710 Chino Hills, California 91709
Telephone (909) 993-1600
CLASS II BASE, MATCH EXISTING
THICKNESS OR 4" MIN. IN
ACCORDANCE WITH COUNTY
SPECIFICATIONS. COMPACTED TO
95% MINIMUM RELATIVE COMPACTION.
TRENCH BACKFILL INS `� d
ACCORDINANCE WITH
COUNTY SPECIFICATIONS .. » 5" CONDUIT
COMPACTED TO 90% RAW
MINIMUM RELATIVE
COMPACTION. =
......... ..... ............ ............
............... . ».....................-••••..............
. 2 . 6"
--
N .
... . _ ..............:................ ..
. .. :...._:_:--C---:::-:::• ••.:::.:::.:: 24" FORCEMAIN
30" FORCEMAIN,.'.'.'.'.'.'- -
......•. ......
PIPE ZONE BACKFILL, 1"
MAXIMUM SIZE IN ACCORDANCE
id%
WITH COUNTY SPECIFICATIONS.
................ .•.-.. COMPACTED TO 90% MINIMUM
.:.. 6" '..
. . . . . . : . ................ RELATIVE COMPACTION.
12» 12"
!—`
PROVIDE UNIFORM BEARING
FOR PIPE ON BOTTOM OF
TRENCH. DETAIL 'A':
N.T.S.
SAN BERNANDINO AVENUE AND FILE NUMBER
JOB NUMBER
ETIWANDA AVENUE SEWER FORCE MAIN SCALE N/A
GENERAL NOTES, CONSTRUCTION NOTES, GRAPHIC SCALE ..
AND DRAWING LIST OWNER NAME DATE
G-2
SHEET NO.
2
12
DRAWING NO. "
50 3�