Loading...
HomeMy WebLinkAbout5036-12�_M i` r EXIST. 42" GRAVITY SEWER `\ ROP( FOOTING j — —FLOW OW (INV. EL= 1080.8'± / �L PROPOSED 8' DIA. MANHOLE EXISTING GROUND— PROPOSED ROUND— PROPOSED 6' MANE FOOTINGJ- NV. EL=1081.13' 36" GRAVITY SEWER �PROPOSED 8' DIA. MANHOLE NV. EL=1082.15' ROPOSED 24" FORCE MAIN FLOWFROM UFT STATION -q TRENCH — — �_ — FROM j LIFT STATION A PROPOSED 30" FORCE MAIN NV. EL=1081.65' . EL=1081.15' CONNECTION DETAIL: SCALE: 1"=5' TAA rl •f%t%n 79.1 j (IN' c �v PIN T. VLA— 1 VV 1. 1 V Underground Service Alert 3 oRE ycr, �, Call: TOLL FREE r 1-800 227-2600 0 M WOF40G DAYS WOW YOU W 0 0 Q U i U �o a REV DATE BY DESCRIPTION N CONCRETEPHASE I CONCRETEPHASE 11 SECTION A -A: SCALE: 1"=2' M o.69984 Exp.9-30-08 9� CIV'`- c���F DESIGNED BY: T. Renner DATE: 04/07 PREPARED BY: DRAWN BY: C. Buzoni DATE: 04/07 TKE Engineering, Inc. CHECKED BY: M. Thornton DATE: 04/07 4446 Central Avenue Riverside, Co. 92506 RING (951) 680-0440 REVIEWED BY. I.E.U.A. Mir T. Fattahi, P.E. DATE: p,PP'p Project Manager GROUT CONNECT;ON HOLES SEE BELOW FOR SPACING PROP. 42" STEEL CASING PROP. 30" FORCE MAIN SPACER PLACED PER NOTE 8 FILL ANNULAR SPACE WITH AIR—BLOWN SAND PROP. 42" STEEL CASING PROP. 5" CONDUITS STRAPPING BANDS PROP. 24" FORCE MAIN PROP. 24" FORCE MAIN O.D. USE POLYETHYLENE CASING INSULATORS �- WITH POLYETHYLENE SKIDS. ALL BOLTS AND BANDS SHALL BE TYPE 304 STAINLESS 12" STEEL. 25.5" FILL ANNULAR SPACE WITH AIR—BLOWN SAND 12" 12" 12" iONL SECTION VIEW I EACH PIPE SECTION 2" CAST IRON PLUG 2" STANDARD STEEL PIPE HALF COUPLING INSIDE SURFACE OF--` STEEL CASING GROUT COUPLING N(INOTES: 1. CASING PIPE JOINTS SHALL BE CONTINUOUSLY WELDED WITHOUT DEFLECTION. 2. SEE PIPELINE PROFILE FOR LIMITS OF CASING PIPE. 3. CASINGS SHALL BE BORE AND JACKED TO THE LIMITS SHOWN ON PLANS. 4. COMPLETED CASING PIPE INTERIOR SHALL BE SWABBED WITH LUBRICANT (PIPE DOPE) PRIOR TO CARRIER INSTALLATION. CARRIER PIPE SHALL BE PULLED THROUGH CASING PIPE. 5. CARRIER PIPE SHALL BE SUCCESSFULLY TESTED PRIOR TO FILLING ANNULAR SPACE BETWEEN IT AND THE CASING. 6. CONTRACTOR SHALL SUBMIT METHODS AND MATERIAL TO ENGIEER FOR REVIEW PRIOR TO INSTALLATION. 7. BELLS OF CARRIER PIPES SHALL BE STAGGERED. 8. SPACING BETWEEN THE CASING INSULATORS SHALL BE PER THE MANUFACTURES RECOMMENDATIONS EXCEPT THAT THERE SHALL 13E AT LEAST 3 CASING INSULATORS PER PIPE SECTION, ONE 12" FROM EACH JOINT AND ONE CENTERED. ADDITIONALLY, ONE INSULATOR SHALL BE INSTALLED 12" FROM EACH END OF CASING. 9. BOTH ENDS OF THE CASING BETWEEN THE CASING AND THE CARRIER PIPE SHALL BE SEALED WATERTIGHT USING AN END SEAL. BANDS SHALL BE TYPE 304 STAINLESS STEEL. INLAND EMPIRE UTILITIES AGENCY A Municipal Water District LOCATION MAILING ADDRESS 6075 Kimball Avenue Post Office Box 9020 Chino, California 91710 Chino Hills, California 91709 Telephone (909) 993-1600 SAN BERNANDINO AVENUE AND nLE NUMBER JOB NUMBER ETIWANDA AVENUE SEWER FORCE MAIN SCALE N/A CONSTRUCTION DETAILS GRAPHIC SCALE OWNER NAME r�v L-10 SHEET NO. 12 12 DATE DRAWING NO. -8-48 `7 X03& 0 II GROUT PLUG O a0 o 0 om Mit It co N I 0 O O I— m Co O III N I) n I) EACH PIPE SECTION 2" CAST IRON PLUG 2" STANDARD STEEL PIPE HALF COUPLING INSIDE SURFACE OF--` STEEL CASING GROUT COUPLING N(INOTES: 1. CASING PIPE JOINTS SHALL BE CONTINUOUSLY WELDED WITHOUT DEFLECTION. 2. SEE PIPELINE PROFILE FOR LIMITS OF CASING PIPE. 3. CASINGS SHALL BE BORE AND JACKED TO THE LIMITS SHOWN ON PLANS. 4. COMPLETED CASING PIPE INTERIOR SHALL BE SWABBED WITH LUBRICANT (PIPE DOPE) PRIOR TO CARRIER INSTALLATION. CARRIER PIPE SHALL BE PULLED THROUGH CASING PIPE. 5. CARRIER PIPE SHALL BE SUCCESSFULLY TESTED PRIOR TO FILLING ANNULAR SPACE BETWEEN IT AND THE CASING. 6. CONTRACTOR SHALL SUBMIT METHODS AND MATERIAL TO ENGIEER FOR REVIEW PRIOR TO INSTALLATION. 7. BELLS OF CARRIER PIPES SHALL BE STAGGERED. 8. SPACING BETWEEN THE CASING INSULATORS SHALL BE PER THE MANUFACTURES RECOMMENDATIONS EXCEPT THAT THERE SHALL 13E AT LEAST 3 CASING INSULATORS PER PIPE SECTION, ONE 12" FROM EACH JOINT AND ONE CENTERED. ADDITIONALLY, ONE INSULATOR SHALL BE INSTALLED 12" FROM EACH END OF CASING. 9. BOTH ENDS OF THE CASING BETWEEN THE CASING AND THE CARRIER PIPE SHALL BE SEALED WATERTIGHT USING AN END SEAL. BANDS SHALL BE TYPE 304 STAINLESS STEEL. INLAND EMPIRE UTILITIES AGENCY A Municipal Water District LOCATION MAILING ADDRESS 6075 Kimball Avenue Post Office Box 9020 Chino, California 91710 Chino Hills, California 91709 Telephone (909) 993-1600 SAN BERNANDINO AVENUE AND nLE NUMBER JOB NUMBER ETIWANDA AVENUE SEWER FORCE MAIN SCALE N/A CONSTRUCTION DETAILS GRAPHIC SCALE OWNER NAME r�v L-10 SHEET NO. 12 12 DATE DRAWING NO. -8-48 `7 X03&