HomeMy WebLinkAbout4257-15ELECTRICAL GENERAL NOTES AND SPECIFICATION
1. ALL WORK SHALL BE IN FULL ACCORDANCE WITH ALL STATE, COUNTY, LOCAL CODES, RULES AND REGULATIONS
OF GOVERNING AGENCIES HAVING JURISDICTION AND THE PRESENTLY ADOPTED EDITION OF THE NATIONAL ELECTRICAL
CODE (N.E.C.).
2
2. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND COMPLY WITH ALL INSPECTION REQUIREMENTS.
1
3
200A, 240/120V, 10, 3W, 42,000 AIC, NEMA 3R 3. THE CONTRACTOR SHALL VERIFY EXISTING SITE CONDITIONS. ALL UTILITY SERVICE REQUIREMENTS AND EXACT LOCATIONS
NON-RESIDENTIAL METER/SERVICE PEDESTAL OF SERVICE FACILITIES BEFORE SUBMITTING HIS BID. SUBMITTAL OF BID INDICATES CONTRACTOR'S COGNIZANT OF ALL JOB
PER EUESRC REQUIREMENTS SITE CONDITIONS AND WORK TO BE PERFORMED.
7 4
0
�"Es
g 0
Q00O'To
O
o
Ob o6�
0.p8 Q°o°0 00 0 00 00
o
od o
. 5
°o
W0
°0 0 �o o 0
p0
b
6 *
REFERENCE NOTES:
OPRECAST CONCRETE UNDERGROUND
PULL BOX SIZE AS INDICATED ON PLAN
O1" ABOVE PAVING OR 6" ABOVE
ROUGH GRADE AT LANDSCAPE AREA
OFINISH SURFACE SHALL SLOPE AWAY
FOR POSITIVE DRAINAGE
OCONTINUOUS BRICK BLOCK
O3/4" COMPACTED ROCK
OPVC CONDUIT, SIZE AND QUANTITY
AS NOTED ON PLANS
OCONDUITS MUST BE SEALED AFTER
PULLING WIRES (TYP.)
MAIN 200A, 2P
BUSS 200A, CU.
PANEL
SERVICE
"A"
208/120V, 10, 3W
r•• -••- ---•T-••
LOCATION SERVICE PEDESTAL
MOUNTING SERVICE PEDESTAL
A. I. C. 42,000
VOLT AMPS
DESCRIPTION
A B
U U BKR
w
' POLE AMP
CKT
NO.
A B
CKT
NO.
BKR
POLE AMP
tl O U
w
J it M
VOLT AMPS
A B
DESCRIPTION
TREE UPLIGHT 1000
8 1
20
1
6. ALL CONDUCTORS SHALL BE COPPER WITH TYPE THHN/THWN 600 VOLT INSULATION, MARKED EVERY 24" ALONG ITS LENGTH
2
1
20
8
1000
PACKAGES. MINIMUM SIZE OF WIRE SHALL BE NO. 12 AWG, UNLESS NOTED OTHERWISE. EACH CONDUCTOR
TREE UPLIGHT
TREE UPLIGHT
875
7 1
20
3
4
1
20
7
875
TREE UPLIGHT
L_..-..-.. ..L..-.. ..-..�
TREE UPLIGHT 875
7 1
20
5
s
1 1
20
71 1 1
875
TREE UPLIGHT
SECTIONS 300-5 AND SECTION 230-8 OF THE N.E.C.
TREE UPLIGHT
875
7 1
20
7
e
1
20
7
875
TREE UPLIGHT
TREE UPLIGHT 625
11. TEST THE COMPLETE SYSTEM TO DEMONSTRATE THAT THE ELECTRICAL COMPONENTS AND SYSTEMS ARE COMPLETE,
5 1
20
9
10
1
20
7
875
TREE UPLIGHT
TREE UPLIGHT
625
5 1
20
11
12
1
20
8
1000
TREE UPLIGHT
LIGHTING CONTROL 500
1 1
20
13
14
1
20
4
500
MON. SIGN LIGHTS
SPARE
1
20
15
16
1
20
1
500
IRRIG CONTROLLER
SPACE -
- 1
-
17
1s
1
-
-
-
SPACE
SPACE
-
1
-
19
20
1
-
-
-
SPACE
SPACE -
- 1
-
21
22
1
-
-
-
SPACE
SPACE
-
1
-
23
24
1
-
-
SPACE
SPACE -
- 1
-
25
26
1
-
-
SPACE
SPACE
-
- 1
-
27
28
1 1
-
-
SPACE
SPACE - 1 - 29
30
1 1
-
-
SPACE
TOTALS: 3000
2375
3250
3250
TOTALS:
6250
5625
10,875=
V.A. (L.C.L.) X 1.25
OTHER LOAD
TOTAL
"
"
13,594
1,000
14,594
V.A.
V.A.
VA.
A
TOTAL AMPS
B
61
NOTES: SEE LIGHTING CONTROL DIAGRAM ON THIS SHEET. RODS, MINIMUM 6 FT. INSTALLED AND FUNCTION PROPERLY. MAKE NECESSARY CORRECTIONS TO MALFUNCTION AND LEAVE SYSTEM READY
APART FOR OPERATION.
1. ALL SPLICES IN PULL BOXES SHALL BE WITH SCOTCHCAST 400 ELECTRICAL INSULATING 1 - 4" SERVICE CONDUIT
RESIN, OR TWO LAYERS OF RUBBER TAPE WITH TWO LAYERS OF BLACK SCOTCH 88 PER POWER CO. REQUIREMENTS 12. PROVIDE THE OWNER WITH ONE (1) SET OF COMPLETE ELECTRICAL "AS -BUILT' DRAWINGS AT THE COMPLETION OF
TAPE AND TWO COATS OF SCOTCHCOAT WATERPROOF RESIN. CONTRACTOR MAY ELECT TO THE JOB. SHOWING ACTUAL CONDUIT RUNS, DEPTHS AND LOCATIONS.
USE SPLICE KITS AND CONNECTORS APPROVED FOR UNDERGROUND APPLICATIONS. SUBMIT
SHOP DRAWINGS FOR APPROVAL.
13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL MAJOR PIECES OF ELECTRICAL EQUIPMENT INCLUDING BUT
2. PROVIDE AND INSTALL PULL BOX ADJACENT TO EACH LIGHT STANDARD AND AS NOT LIMITED TO THE FOLLOWING: METER/SERVICE/PANEL EQUIPMENT, LIGHTING FIXTURES AND LIGHTING CONTROLS.
INDICATED ON THE DRAWINGS.
THE CONTRACTOR SHALL SUBMIT UTILITY METERING SERVICE EQUIPMENT SHOP DRAWINGS TO THE SERVING
UTILITY FOR APPROVAL PRIOR TO FABRICATION.
14. ALL WORK SHALL BE GUARANTEED BY THE CONTRACTOR FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE
OF THE WORK BY THE OWNER.
A TYPICAL UNDERGROUND PULL BOX DETAIL NOT TO SCALE B PANELBOARD SCHEDULE C SINGLE LINE DIAGRAM NOT TO SCALE
5
2
N
PC
REFERENCE NOTES: SPECIFICATIONS: H
1OHINGED DEMAND RESET COVER 1. 12 GAUGE STAINLESS STEEL CONSTRUCTION
WITH POLYCARBONATE VIEWING 2. WEATHERPROOF, NEMA 3R ENCLOSURE 3/4"C - 3#12 & 1#12 GRD. THWN CU.
16.5" WINDOW 3. DETACHABLE PAD MOUNT SUB -BASE
OTEST BYPASS FACILITIES 4. COPPER BUSSED INTERIORS
DWG. 308
24.75" 8.56" &TO PANEL "A" TO PANEL "A" TO PANEL "A" I
6" O CUSTOMER SECTION (PANEL "A", LIGHTING 5. COMPLIES WITH EUSERC STANDARDS I HOT
6. ALL FACTORY WIRING 600 VOLT RATED COPPER
CONTACTORS AND PHOTOCELL) _1-1
1-1-=
4 8 7. ALL COMPONENTS UL LISTED HHa-_ H OENCLOSING COVER 120V � 3 � = 3 4 8. ALL EXTERIOR DOORS AND COVERS PADLOCKABLE A-13 N NSPARE SPARE SPARE SPARE N SPARE 9. UTILITY COVERS SEALABLE NEUTRAL CH1CH2 - -----
� O TEST BYPASS COVER -
10. PACIFIC UTILITY PRODUCTS CAT. #USP24-M2200- _ _
2 ❑ 48" 5 9 O METER SECTION BARRIER TO EXTEND 120-CTB-SS-120/240VAC 1 PH 3 WIRE 200 AMPS.
TO EDGE OF TEST BLOCK
10 O PROTECTIVE METALLIC BARRIER 3/4"C - 2#12 8�
1#12 GRD. THWN CU. 1 3 5 7 9 11 2 4 6 8 10 12 14
6
O METER SOCKET TO TREE UPLIGHTS TO TREE UPLIGHTS TO MONUMENT
SIGN LIGHTS
11
15 3
27.5" 73D O TEST BYPASS SUPPORT -
12
13 10 LANDING LUGS AND FACTORY
14
U. CONDUCTORS
11 PULL SECTION AND COVER REFERENCE NOTES:
°, 4 y d 1 "
1 ELECTRONIC TIME SWITCH, 7 DAY TWO -CHANNEL.
° , q a PARAGON ELECTRIC CO. #EC72/120V.
Nj X \\j\\� j\\j\\ \\j\� G 3/4" DIA. X 10 FT. COPPERCLAD
jj\j\\\\\\\\\j,;\\jj\jj\�� j\jj\\j\\\\\ STEEL GROUND ROD TIME CLOCK SETTING FOR EACH CHANNEL SHALL BE AS DIRECTED BY THE CITY.
GPOURED CONCRETE BASE, 6" MIN.
THICKNESS, EXTEND 6" BEYOND OPHOTO-CELL CONTROL, 120V.
FRONT VIEW SIDE VIEW OUTSIDE DIMENSION OF ENCLOSURE PARAGON ELECTRIC CO. #CW201-00
WITH MIN. 1/2% SLOPE FOR O30A CONTACTS, 8 POLE, 120V COIL ELECTRICALLY HELD LIGHTING CONTACTOR.
DRAINAGE
14 FINISHED GRADE SQUARE D CLASS 8903, TYPE LG80 OR EQUAL.
NOTE: PROVIDE 3 FT. MINIMUM CLEARANCE AROUND THE EQUIPMENT. O 30A CONTACTS, 4 POLE, 120V COIL ELECTRICALLY HELD LIGHTING CONTACTOR.
15 PROVIDE PHOTOCELL WINDOW AS REQUIRED SQUARE D CLASS 8903, TYPE LG40 OR EQUAL.
OMOUNT LIGHTING CONTROL EQUIPMENT INDSIDE THE METER/SERVICE PEDESTAL LAENQINEER8
MOUNTED CABINET. " 00 111
1 E
D PEDESTAL MOUNTED METER/SERVICE EQUIPMENT DETAIL NOT TO SCALE E LIGHTING CONTROL DIAGRAM NOT TO SCALE
CITY OF FONTANA
SECTION 4216/4217 OF THE GOVERNMENT FOOTHILL BLVD �oQP° a GAS"9�F ELECTRICAL DETAILS
ORECODE REQUIRES A DIG ALERT IDENTIFICATION
NUMBER BE ISSUED BEFORE A PERMIT TO LANDSCAPE MEDIAN ``Q °G tim DRAWNC. .R. FOOTHILL BOULEVARD SCALE:
EXCAVATE WILL BE VALID CITY OF FONTANA NO 16914 M �J'R' FROM ALMERIA AVENUE NONE
FROM ALM E RIA AVE ■ Exp. 6-30-07 DESIGNED iY DATE:
FOR YOUR DIG ALERT I.D. NUMBER CALL 2335 �` '� LRA TO TO AVENUE 02-16-07
111 CALIFORNIA,! 'S'j• F�fCTRIGP �P
UNDERGROUND SERVICE ALERT TO TOKAY AVE■ 9TFOF CA�\FCHECKED BY: APP VIED. Y: DATE: DRAWING NO.: 15
TOLL FREE 1-800-227-2600 - . p
4257 � 6
TWO WORKING DAYS BEFORE YOU DIG REV REVISION DESCRIPTION DATE CITY DATE ITYENGINEER X51152
to
4
M
r
N
to
CL
w
4. ALL MATERIALS SHALL BE NEW, UL LISTED AND APPROVED AS APPROPRIATE. MATERIALS SHALL MEET THE APPROVAL
OF THE DIVISION OF INDUSTRIAL SAFETY, AND ALL GOVERNING AGENCIES HAVING JURISDICTION. MATERIALS SHALL BE
r•• -••- ---•T-••
MANUFACTURED IN ACCORDANCE WITH APPLICABLE STANDARDS ESTABLISHED BY ANSI, UL, NEMA AND NBFU. INSTALL
i
PER MANUFACTURER'S RECOMMENDATIONS.
5. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. INSTALL THE ELECTRICAL SYSTEMS WITHOUT INTERFERING WITH IRRIGATION
*
I
AND OTHER UNDERGROUND SYSTEMS.
JLI
6. ALL CONDUCTORS SHALL BE COPPER WITH TYPE THHN/THWN 600 VOLT INSULATION, MARKED EVERY 24" ALONG ITS LENGTH
200A LANDING LUGSSHOWING
MANUFACTURER'S NAME, MAXIMUM ALLOWABLE VOLTAGE AND SIZE. DELIVER THE WIRE TO THE SITE IN
2PUNBROKEN
PACKAGES. MINIMUM SIZE OF WIRE SHALL BE NO. 12 AWG, UNLESS NOTED OTHERWISE. EACH CONDUCTOR
OF EVERY SYSTEM SHALL BE PERMANENTLY TAGGED IN COMPLIANCE WITH OSHA.
"A„7.
CONDUIT BELOW GRADE SHALL BE PVC SCHEDULE -40 WITH CODE SIZED GROUND. ALL CONDUIT SWEEPS AND RISERS
AND STUBS ABOVE GRADE SHALL BE RIGID STEEL CONDUIT WITH HALF -LAPPED TAPE COVERING OR WITH FACTORY
L_..-..-.. ..L..-.. ..-..�
COATED PVC. RIGID STEEL CONDUIT RACEWAY SHALL BE INSTALLED ABOVE GRADE.
8. ALL FEEDERS RUN IN NON-METALLIC CONDUITS SHALL HAVE GREEN GROUND CONDUCTORS SIZED IN ACCORDANCE WITH
APPLICABLE CODES. THE CONTRACTOR SHALL MAINTAIN UNIFORMITY AND CONTINUITY OF THE GROUNDING SYSTEM.
3/4"C-1 #2 THWN CU.
9, ALL CONDUIT ONLY (C.O.) SHALL HAVE A 3/16" NYLON PULL CORD OR ROPE, AND SEALED IN ACCORDANCE WITH
TO METALLIC COLD
SECTIONS 300-5 AND SECTION 230-8 OF THE N.E.C.
WATER PIPE
10. PROVIDE ALL LAMPS, LENSES ETC., FOR A COMPLETE LIGHTING FIXTURE. UNLESS NOTED OTHERWISE, ALL
3/4"C-1 #2 THWN CU. F
LAMPS SHALL BE GE, SYLVANIA OR PHILIPS.
TO TWO (2) 3/4" DIA. -
X 10 FT. COPPERCLAD
11. TEST THE COMPLETE SYSTEM TO DEMONSTRATE THAT THE ELECTRICAL COMPONENTS AND SYSTEMS ARE COMPLETE,
STEEL DRIVEN GROUND =
NOTES: SEE LIGHTING CONTROL DIAGRAM ON THIS SHEET. RODS, MINIMUM 6 FT. INSTALLED AND FUNCTION PROPERLY. MAKE NECESSARY CORRECTIONS TO MALFUNCTION AND LEAVE SYSTEM READY
APART FOR OPERATION.
1. ALL SPLICES IN PULL BOXES SHALL BE WITH SCOTCHCAST 400 ELECTRICAL INSULATING 1 - 4" SERVICE CONDUIT
RESIN, OR TWO LAYERS OF RUBBER TAPE WITH TWO LAYERS OF BLACK SCOTCH 88 PER POWER CO. REQUIREMENTS 12. PROVIDE THE OWNER WITH ONE (1) SET OF COMPLETE ELECTRICAL "AS -BUILT' DRAWINGS AT THE COMPLETION OF
TAPE AND TWO COATS OF SCOTCHCOAT WATERPROOF RESIN. CONTRACTOR MAY ELECT TO THE JOB. SHOWING ACTUAL CONDUIT RUNS, DEPTHS AND LOCATIONS.
USE SPLICE KITS AND CONNECTORS APPROVED FOR UNDERGROUND APPLICATIONS. SUBMIT
SHOP DRAWINGS FOR APPROVAL.
13. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ALL MAJOR PIECES OF ELECTRICAL EQUIPMENT INCLUDING BUT
2. PROVIDE AND INSTALL PULL BOX ADJACENT TO EACH LIGHT STANDARD AND AS NOT LIMITED TO THE FOLLOWING: METER/SERVICE/PANEL EQUIPMENT, LIGHTING FIXTURES AND LIGHTING CONTROLS.
INDICATED ON THE DRAWINGS.
THE CONTRACTOR SHALL SUBMIT UTILITY METERING SERVICE EQUIPMENT SHOP DRAWINGS TO THE SERVING
UTILITY FOR APPROVAL PRIOR TO FABRICATION.
14. ALL WORK SHALL BE GUARANTEED BY THE CONTRACTOR FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE
OF THE WORK BY THE OWNER.
A TYPICAL UNDERGROUND PULL BOX DETAIL NOT TO SCALE B PANELBOARD SCHEDULE C SINGLE LINE DIAGRAM NOT TO SCALE
5
2
N
PC
REFERENCE NOTES: SPECIFICATIONS: H
1OHINGED DEMAND RESET COVER 1. 12 GAUGE STAINLESS STEEL CONSTRUCTION
WITH POLYCARBONATE VIEWING 2. WEATHERPROOF, NEMA 3R ENCLOSURE 3/4"C - 3#12 & 1#12 GRD. THWN CU.
16.5" WINDOW 3. DETACHABLE PAD MOUNT SUB -BASE
OTEST BYPASS FACILITIES 4. COPPER BUSSED INTERIORS
DWG. 308
24.75" 8.56" &TO PANEL "A" TO PANEL "A" TO PANEL "A" I
6" O CUSTOMER SECTION (PANEL "A", LIGHTING 5. COMPLIES WITH EUSERC STANDARDS I HOT
6. ALL FACTORY WIRING 600 VOLT RATED COPPER
CONTACTORS AND PHOTOCELL) _1-1
1-1-=
4 8 7. ALL COMPONENTS UL LISTED HHa-_ H OENCLOSING COVER 120V � 3 � = 3 4 8. ALL EXTERIOR DOORS AND COVERS PADLOCKABLE A-13 N NSPARE SPARE SPARE SPARE N SPARE 9. UTILITY COVERS SEALABLE NEUTRAL CH1CH2 - -----
� O TEST BYPASS COVER -
10. PACIFIC UTILITY PRODUCTS CAT. #USP24-M2200- _ _
2 ❑ 48" 5 9 O METER SECTION BARRIER TO EXTEND 120-CTB-SS-120/240VAC 1 PH 3 WIRE 200 AMPS.
TO EDGE OF TEST BLOCK
10 O PROTECTIVE METALLIC BARRIER 3/4"C - 2#12 8�
1#12 GRD. THWN CU. 1 3 5 7 9 11 2 4 6 8 10 12 14
6
O METER SOCKET TO TREE UPLIGHTS TO TREE UPLIGHTS TO MONUMENT
SIGN LIGHTS
11
15 3
27.5" 73D O TEST BYPASS SUPPORT -
12
13 10 LANDING LUGS AND FACTORY
14
U. CONDUCTORS
11 PULL SECTION AND COVER REFERENCE NOTES:
°, 4 y d 1 "
1 ELECTRONIC TIME SWITCH, 7 DAY TWO -CHANNEL.
° , q a PARAGON ELECTRIC CO. #EC72/120V.
Nj X \\j\\� j\\j\\ \\j\� G 3/4" DIA. X 10 FT. COPPERCLAD
jj\j\\\\\\\\\j,;\\jj\jj\�� j\jj\\j\\\\\ STEEL GROUND ROD TIME CLOCK SETTING FOR EACH CHANNEL SHALL BE AS DIRECTED BY THE CITY.
GPOURED CONCRETE BASE, 6" MIN.
THICKNESS, EXTEND 6" BEYOND OPHOTO-CELL CONTROL, 120V.
FRONT VIEW SIDE VIEW OUTSIDE DIMENSION OF ENCLOSURE PARAGON ELECTRIC CO. #CW201-00
WITH MIN. 1/2% SLOPE FOR O30A CONTACTS, 8 POLE, 120V COIL ELECTRICALLY HELD LIGHTING CONTACTOR.
DRAINAGE
14 FINISHED GRADE SQUARE D CLASS 8903, TYPE LG80 OR EQUAL.
NOTE: PROVIDE 3 FT. MINIMUM CLEARANCE AROUND THE EQUIPMENT. O 30A CONTACTS, 4 POLE, 120V COIL ELECTRICALLY HELD LIGHTING CONTACTOR.
15 PROVIDE PHOTOCELL WINDOW AS REQUIRED SQUARE D CLASS 8903, TYPE LG40 OR EQUAL.
OMOUNT LIGHTING CONTROL EQUIPMENT INDSIDE THE METER/SERVICE PEDESTAL LAENQINEER8
MOUNTED CABINET. " 00 111
1 E
D PEDESTAL MOUNTED METER/SERVICE EQUIPMENT DETAIL NOT TO SCALE E LIGHTING CONTROL DIAGRAM NOT TO SCALE
CITY OF FONTANA
SECTION 4216/4217 OF THE GOVERNMENT FOOTHILL BLVD �oQP° a GAS"9�F ELECTRICAL DETAILS
ORECODE REQUIRES A DIG ALERT IDENTIFICATION
NUMBER BE ISSUED BEFORE A PERMIT TO LANDSCAPE MEDIAN ``Q °G tim DRAWNC. .R. FOOTHILL BOULEVARD SCALE:
EXCAVATE WILL BE VALID CITY OF FONTANA NO 16914 M �J'R' FROM ALMERIA AVENUE NONE
FROM ALM E RIA AVE ■ Exp. 6-30-07 DESIGNED iY DATE:
FOR YOUR DIG ALERT I.D. NUMBER CALL 2335 �` '� LRA TO TO AVENUE 02-16-07
111 CALIFORNIA,! 'S'j• F�fCTRIGP �P
UNDERGROUND SERVICE ALERT TO TOKAY AVE■ 9TFOF CA�\FCHECKED BY: APP VIED. Y: DATE: DRAWING NO.: 15
TOLL FREE 1-800-227-2600 - . p
4257 � 6
TWO WORKING DAYS BEFORE YOU DIG REV REVISION DESCRIPTION DATE CITY DATE ITYENGINEER X51152
to
4
M
r
N
to
CL
w