HomeMy WebLinkAbout3174-22EXISTING LIGHTING CONTACTOR PANEL
EXISTING MUSCO
NEW LIGHTING CONTACTOR
CABINET FOR PANEL SF
14"x10"x72" H. O
0
Q CONTRACTOR SHALL REMOVE NEW CONTACTORS FROM MUSCO
LIGHTING CONTACTOR CABINET AND MOUNT IN NEW ENCLOSURE
� EXISTING CONCESSION FLOOR PLAN�.�41
a
EXISTING
LIGHTING CONTROL PANEL "LCP" IWELECTRICAL ELECTRICAL ROOM
11111 Mai 1' 61, Km bm, ` W_ am- T, I mll ky- I I
3 4 5
(E) (E) (E) l
100 A
J 100 P l 20
3P 3P J
PROVIDE NEMA 3RD HINGED, LOCKABLE
DOOR JUNCTION BOX WITH ONE
125V DOUBLE DUPLEX ON INTERIOR
I
FINISHED GRADE
12"
RECEPTACLE DETAIL
SCALE f2
N.T.S.
NOTE*
BOX SHALL BE LOCATED
AGAINST BACK STOP FENCE
SCALE
N.T.S. (31
EXISTING
MAIN SERVICE "MSA"
XFMR (E)
E
(E)
PANEL
"LP"
NEW
PANEL
06m"
SINGLE LINE DIAGRAM
EXISTINE
PANEL
�—�
(E)
(E)
TOTAL PANEL LOAD
—
PANEL
PANEL
BA OB_ OC
CIR KR
"FCD"
"SF"
TSA— 3
LOCATION
EXISTING PANEL CP
11860
(BASEBALL FIELD C)
EXISTING LOAD
100
2
TSA— 4
EXISTING LOAD
--- 9950 3
2 4 3500
(BASEBALL FIELD D)
--- 12682 5 3
- 6
EXISTING LOAD 500 3 20
TSA— 5
- 8
EXISTING LOAD 3510 5 20
---2900 9 2
(SENIOR BASEBALL FIELD)
EXISTING LOAD 3510 7 2
E
- 12
PROVIDE NEMA 3RD HINGED, LOCKABLE
DOOR JUNCTION BOX WITH ONE
125V DOUBLE DUPLEX ON INTERIOR
I
FINISHED GRADE
12"
RECEPTACLE DETAIL
SCALE f2
N.T.S.
NOTE*
BOX SHALL BE LOCATED
AGAINST BACK STOP FENCE
SCALE
N.T.S. (31
EXISTING
MAIN SERVICE "MSA"
XFMR (E)
E
(E)
PANEL
"LP"
NEW
PANEL
06m"
SINGLE LINE DIAGRAM
EXISTINE
PANEL
LP
LOCATION,
MAINt
ELECTRICAL ROOM
225A/3P
42 OOOAIC
TOTAL PANEL LOAD
BUS RATING
100 AMP
120/208V 30 4W
MOUNTINGS SURFACE
LOCATION
BA OB_ OC
CIR KR
A B C
KR CIR
OA VOOLHAMPSOC
LOCATION
EXISTING PANEL CP
11860
1 1501
EXISTING LOAD
100
2
13500
EXISTING LOAD
--- 9950 3
2 4 3500
EXISTING LOAD
--- 12682 5 3
- 6
EXISTING LOAD 500 3 20
PANEL 'TP' 2900 7 100
- 8
EXISTING LOAD 3510 5 20
---2900 9 2
- 10
EXISTING LOAD 3510 7 2
11 -
- 12
EXISTING LOAD 2520 9 20
13 -
- 14
EXISTING LOAD 1865 11 20
EXISTING LOAD 360 15 20
- 16
EXISTING LOAD 3125 13 20
EXISTING LOAD 360 17 20
- 18
EXISTING LOAD 1980 15 120
EXISTING LOAD 500 1 119 20
1 - 20
EXISTING LOAD 1800 17 20
EXISTING LOAD 11000 21 20
- 22
- 19 -
EXISTING LOAD 1000 23 20
- 24
- 21 -
- 22 -
15260 14210 14046
SUB TOTAL
- 24 -
3500 13500 1 0
- 25 -
- 26 -
OA = 18760
OB =17710
- 28 -
OC = 14046
• - 29 -
TOTAL CONNECTED VA
- 50516 VA
LCL, 2272 VA Q 257.
= 568 VA
TOTAL PANEL LOAD
= 51084 VA
FEEDER AMPS
= 142.0 AMPS
1
I
REMOVE EXISTING CIRCUIT BRCAKER AND PROVIDE NEW AS SHOWN.
SINGLE LINE DIAGRAM NOTES:
O EXISTING 2"C.O. PULL IN NEW 3 #2/0 do 1 #6 E/G
O 2"C. 3 #2/0 do 1 #6 E/G
O3 CONNECT CONDUCTORS TO EXISTING 150A MAIN IN PANEL
PROVIDE SIGN ON PANEL WHICH READS "FED WITH 100A"
LOAD SUMMARY
EXISTING CONNECTED
LOAD 483.1 KVA
PANEL FAC —BUS #1 52.0 KVA
PANEL FAC — BUS �2 52.0 KVA
PANEL SF 108.0 KVA
PANEL HP (ADDED LOAD) 8.1 KVA
TOTAL LOAD 703.2 KVA
or 843.8 AMPS
AT 480/277V. 30 4W
NOTE:
THE LOAD FOR PANEL "TP" WAS ALREADY
FACTORED IN ON PHASE ONE OF THIS
PROJECT
SCALE
N.T.S.
�
PANEL
Hp
LOCATION,
I MAIN,
IN MSA
M.L.O.
65,000AIC
TOTAL PANEL LOAD
= 46068 VA
BUS RATING
225 AMP
480/277V 30 4W
MOUNTINGS FLUSH
LOCATION
VO TAMPS
OA OB OC
CIR
BKR
A B C
BKR CIR
OA OB
OC
LOCATION
EXISTING LOAD
400
1
20
1
20
2
12860
EXISTING LOAD
EXISTING LOAD 500 3 20
2 4 2860
EXISTING LOAD
EXISTING LOAD 3510 5 20
20 6 1505
EXISTING LOAD
EXISTING LOAD 3510 7 2
20 8 2405
EXISTING LOAD
EXISTING LOAD 2520 9 20
- 10 -
EXISTING LOAD 1865 11 20
- 12 -
■
EXISTING LOAD 3125 13 20
-141 -
EXISTING LOAD 1980 15 120
- 16 -
EXISTING LOAD 1800 17 20
- 18 -
■
- 19 -
- 20 -
■
- 21 -
- 22 -
- 23 -
- 24 -
- 25 -
- 26 -
■
- 27 -
- 28 -
• - 29 -
20 30 690
S.W. PARKING LOT LIGHTING
- 31 -
2 32 690
-
- 33 -
20 34 -
SPARE
• - 35 -
20 361 2045
S.W. WALK LIGHTING
• - 37 -20
38 1865
S.E. WALKWAY LIGHTING
- 39 -
20 40 1380
S.E. PARKING LOT LIGHTING
TIMESWITCH 100 41 20
2 42 1 1380
1---
7035 4980 7175
SUB TOTAL
78220 4240
5620
OA = 14855
OB = 9220
OC = 12795
TOTAL CONNECTED VA_=_36870
VA
LCLt 36870 VA ! 25%
= 9218 VA
TOTAL PANEL LOAD
= 46068 VA
FEEDER AMPS
= 55.3 AMPS
NOTED
A PROVIDE NEW CIRCUIT BREAKER MATCH EXISTING MANUFACTURER AND
OPERATING CHARACTERISTICS
8 CONNECT TO EXISTING (4) POLE CONTACTOR CONNECTED TO CHANNEL 'a' OF
EXISTING TIME SWITCH.
C CONNECT TO EXISTING (6) POLE CONTACTOR CONNECTED TO CHANNEL 'b' OF
ISTING TIME SWITCH.
'. rt
amt
7V
d�{ ,
k a
j
COX,�
�. cp a
MAIN SWITCHGEAR ELEVATION N. ` 2
0 REV' REMSIoN DEscR`P'noN DATE ENGR. qTY DATE SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT Prepared Under The Supervision Of : CITY OF FONTANA, CALIFORNIA SCALE: AS NOTED
j
Engineering Inc.
COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL ELEC;TRIC;/�-�L, PI,,,,A,N DATE: 5/15/02
110atrical Rushmalus& c""`sw`® SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER DRAWN BY:
7939 Palm Ave : -FM
3 JACK BULIK P
Highland. Ca. o n DIAL TWO WORKING THE CITY OF FONTANA MAY REQUIRE REVISIONS TO THE PLANS TOE-3DESIGNED BY:
909 864-0223
92346 'a BEFORE DAYS x BEFORE J�
YOU DIG BRING THEM INTO CONFORMANCE WITH CONDITIONS AND PHASE 2
Fax 909 864-0280 � a TOLL FREE 1-800-2z7-2600
jcaeng�earthlink.net �, Date : CHECKED BY: ROVED B 7 DRAWING NO.: 22
A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT STANDARDS IN EFFECT. �Tr�JCc ` " ew— 3174
CITY EN `NEE R.C.E. 51152 DATE. 31