HomeMy WebLinkAbout5224-1GENERAL NOTES FOR SEWER IMPROVEMENT PLANS 1. ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA 26. NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR STANDARD PLANS, THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS APPROVAL OF THE CITY ENGINEER. CITY .,OF FFOR PU ELIC WORKS CONSTRUCTION GR ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION UNLESS OTHERWISE 27. SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT NOTED. MANHOLE WALLS TO ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT. SEWER IMPROVEMENT P 2. WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS 28. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING THAT CAN NOT BE RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE FACILITIES, AND VERIFY ELEVATION AND LOCATION OF CONNECTIONS. CITY "GREEN BOOK", THE CONTRACTOR SHALL IMMEDIATELY REPORT SAID CONFLICT TO APPROVAL OF CONNECTIONS TO EXISTING FACILITIES DOES NOT IMPLY CORRECTNESS PARCEL THE CIT I MAP NO. 19546 Y ENG NEER FOR RESOLUTION. F 0 ELEVATIONS OR LOCATIONS SHOWN ON THE PLANS. 3. ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY 29. ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS ENGINEER. OTHERWISE APPROVED BY THE CITY ENGINEER. 4. CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA 30. TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A COMMUNITY DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START PLUG 12" BELOW THE GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST OF ANY WORK, INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO NEXT TO THE STREET RIGHT OF WAY, THE LATERAL SHALL TERMINATE 3 FEET WORKING DAYS PRIOR TO THE START OF ANY WORK IN PUBLIC RIGHT-OF-WAY WITHIN INSIDE THE LOT AS MEASURED FROM THE UTILITY EASEMENT. THE CITY LIMITS. CALL (909) 350-7610. 31. THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE 5. CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND LOCATION OF THE SEWER LATERAL. PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST NON -METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY 32. IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE 1026.0 TRAFFIC ENGINEER. PROPOSED IMPROVEMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY. 1024.0 6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES. 33. NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN PLACED, INSPECTED AND APPROVED BY THE CITY. 1022.0 7. THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE 34. ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED DIVISION OF INDUSTRIAL SAFETY. PRIOR TO PAYING OF STREETS. 1020.0 8. THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN 35. APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT DEPTH SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER PRIOR TO PLACEMENT. 1018.0 APPROVED MEANS PURSUANT TO THE REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET SHALL 36. ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND MOVEMENT, TO FINISHED GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING. 1016.0 9. NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY 37. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, WITHOUT OBTAINING A SEPARATE PERMIT FOR THAT PURPOSE. STRIPING, BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE 1014.0 SATISFACTION OF THE CITY TRAFFIC ENGINEER. 10. THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION, HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO 38. AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER 1012.0 DETERMINE, IN THE FIELD, THE TRUE LOCATION AND ELEVATION OF ANY EXISTING OF RECORD, WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER. UTILITIES, AND TO EXERCISE PROPER PRECAUTION TO AVOID DAMAGE THERETO. THE PRIVATE ENGINEER'S NOTICE TO CONTRACTOR CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT 1-800-227-2600 1010.0 TWO WORKING DAYS BEFORE EXCAVATION. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES AND/OR STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE 11. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY AVAILABLE RECORDS. THESE LOCATIONS ARE APPROXIMATE AND SHALL BE 1008.0 COMPANIES INCLUDING, BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE CONFIRMED BY THE CONTRACTOR, SO THAT ANY NECESSARY ADJUSTMENT CAN TELEVISION, LANDSCAPING, LANDSCAPE IRRIGATION, DOMESTIC WATER, RECLAIMED BE MADE IN ALIGNMENT AND/OR GRADE OF THE PROPOSED IMPROVEMENT. THE WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND CALTRANS. ALL UTILITY CONTRACTOR IS REQUIRED TO TAKE DUE PRECAUTIONARY MEASURE TO PROTECT 1006.0 COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK ANY UTILITY LINES SHOWN AND ANY OTHER LINES NOT ON RECORD OR NOT SHOWN AROUND THEIR FACILITIES. ON THESE PLANS. 1004.0 12. THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN CONSTRUCTION CONTRACTOR AGREES THAT IN ACCORDANCE WITH GENERALLY ACCEPTED VALVES WITHOUT APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL CONSTRUCTION PRACTICES, HE WILL BE REQUIRED TO ASSUME SOLE AND COMPLETE COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR VALVE OPERATION RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF 1002.0 AND WATER REQUIREMENTS. THE PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY. THIS REQUIREMENT SHALL BE MADE TO APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. CONSTRUCTION CONTRACTOR FURTHER AGREES TO DEFEND, INDEMNIFY AND HOLD 1000.0 13. STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE DESIGN PROFESSIONAL HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN NOTED. CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING LIABILITY 999.0 14. ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ARISING FROM THE SOLE NEGLIGENCE OF THE DESIGN PROFESSIONAL. 667+50 ENABLE THE CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING DURING CONSTRUCTION. 15. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER. 16. REMOVAL AND REPLACEMENT OF EXISTING SURVEY, INCLUDING SURVEY MONUMENTS, MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED CIVIL ENGINEER OR LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE WEEK PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT. 17. THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION AREA FOR RESIDENTS AND EMERGENCY VEHICLES. 18. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL, INCLUDING ADEQUATE WATERING, AT ALL TIMES. 19. THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING CONSTRUCTION WITHOUT PRIOR WRITTEN APPROVAL, 20. NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR. 21. A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE TO OBTAIN THE REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT PORTION OF THE WORK UNTIL THE SPECIFIED DENSITY IS OBTAINED. 22. CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE TEMPORARY NON-ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS. 23. ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH EXISTING CONCRETE. 24. IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A TERMINAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE DOWNSTREAM MANHOLE, SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT. 25. SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS OF THE ASTM DESIGNATION C700 FOR V.C.P. BENCHMARK CITY OF FONTANA BENCHMARK NO. 289 ELEVATION = 1032.22 FEET 0 O FOUND RAILROAD SPIKE IN POLE NO. 61319 AT THE NE CORNER OF SANTA D - _11 a - ANA AVENUE AND CATAWBA AVENUE. �A TOLL FREE 1-800-227-2600 A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT PROTECTIVE BLANKET - OF 2 SACK CONCRETE 1015.93 INV. DROP MANHOLE 1011.66 INV. 21" SEWER 668+35.03 1011.96 INV. 668+00 668+50 a La � 8" EXTRA STRENGTH VCP SEWER PIPE PER CITY REQUIREMENTS. 442 LF 3939 E. CORONADO STREET PIPE BEDDING BACKFILL AND REPAVING TO BE IN ACCORDANCE WITH CITY OF FONTANA STD. > OCONSTRUCT Q :n u -i OCONSTRUCT c a O4 Q I I 7951 REDWOOD AVENUE I O5 w d_ f O LLQ CD 6 r` O+ M (n Q N O EX. MH #18 ! V- Q STA. 83+63.46 J � 1021.26 RIM 0 1014.98 INV. � w o> 00 PER SEWAGE O coN p O COLLECTION z 0 r SYSTEM PLAN co O o NO. 82/100. a cO as STA. 81+07.00 0 Q o _ t RIM J z z Q FINISHED STA. 668+35.031 o O a 6 + o CENTERLINE O5 WATER LATERA ZU Z SLEEVE � Q w Q �18" 0.53% M (nN M w O O O E Z z Q)j 0 +0 O^ N O 0 c� ^ co M O N (_ O rr7 co i. o O O L Ln + O co 00 + 0+0 00 CSO 06 r` O o0 06 co coo (0 � Z, ca O O O 1017.16 (0.D.) PROTECTIVE BLANKET - OF 2 SACK CONCRETE 1015.93 INV. DROP MANHOLE 1011.66 INV. 21" SEWER 668+35.03 1011.96 INV. 668+00 668+50 a QUANTITIES � 8" EXTRA STRENGTH VCP SEWER PIPE PER CITY REQUIREMENTS. 442 LF 3939 E. CORONADO STREET PIPE BEDDING BACKFILL AND REPAVING TO BE IN ACCORDANCE WITH CITY OF FONTANA STD. 1008. OCONSTRUCT Q :n u -i OCONSTRUCT c 2 EA O4 Q I I 7951 REDWOOD AVENUE I O5 w d_ f O LLQ CD 6 r` O+ M (n N O N O EX. MH #18 ! V- Q STA. 83+63.46 04 � 1021.26 RIM 0 1014.98 INV. O 00 PER SEWAGE O coN p O COLLECTION z O r SYSTEM PLAN co O o NO. 82/100. + cO as STA. 81+07.00 (.0 _ t RIM O1018.16 1012.54 INV. EXISTING FINISHED STA. 668+35.031 0 6 + EX. MH #18 STA. 78+54.18 (1015.84) RIM '1010.16) INV. PER SEWAGE COLLECTION SYSTEM PLAN NO. 82/100. i Q RECORD DRAW/NC REV. REVISION DESCRIPTION �--8" EXTRA 1016.08 INV. STRENGHT 1015.66 (O.D.) VCP SEWER \ 668+72.38 0 1015.26 TOP OF 4" GAS 1014.66 TOP OF PIPE (O.D.) 669+00 669+50 670+00 > > o? o? O O Ki 0) r: rn M O M +to +r: o � O r- O r� O .- 670+50 �8" EXTRA STRENGTH VCP SEWER --t r: M + N r` ca Muj O M + , N Li J O z a v � M (n + w N t0 � N N O 1024.0 1022.0 WATER 0 LATERAL 1020.0 -S=0.53% 1018.0 1016 0 > ; >:86 z z "t z -t as cD c0 rn c0 00 U m N ?� zM� �� 1014.0 00 00 +,00 + 06 C ~ J^ JN- N ON 3:w z � ij(D c^0-Q_in N w r` N FINISH GRADE o OVER PIPE 1019.34 INV. 1018.56 INV. I 39.00' LATERAL "A" 671+00 671+50 672+00 POTHOLE AND VERIFY UNDER M.W.D. SUPERVISION. CALL JOHN OSORNIA OF THE WATER SYSTEMS OPERATIONS GROUP AT (951) 710-5570. p (1018.40)± FS 670+35.00 _ 1017.16 TOP OF STEEL SLEEVE 120.92 RI MO 1016.08 INV. -8 SEWER - 1014.66 TOP OF P.C.P. (O.D.) j 0.53% 669+00 S 69000 SANTA ANA AVENUE SEE SECTION HEREON w _ w W 0.53% 67�+00 8 S o - E SEWER CONSTRUCTION NOTES QUANTITIES OCD� Elf 8" EXTRA STRENGTH VCP SEWER PIPE PER CITY REQUIREMENTS. 442 LF 3939 E. CORONADO STREET PIPE BEDDING BACKFILL AND REPAVING TO BE IN ACCORDANCE WITH CITY OF FONTANA STD. 1008. OCONSTRUCT 6" SEWER CLEANOUT PER CITY OF FONTANA STD. 2004. u -i OCONSTRUCT MANHOLE PER CITY FONTANA STD. 2001. 2 EA O4 O � (909) 335-7507 7951 REDWOOD AVENUE + L. O, O5 Cn O O O LLQ CD 6 r` O+ M (n N O N O O O V- ma. O 00 04 LL_0 0 No. 43082 O + 0 N O O coN p O O N �p O co O DATE STANDARDS IN EFFECT. O N ^ N cD O cO O EXISTING FINISHED GRADE AT CENTERLINE O5 WATER LATERA STEEL SLEEVE 0.53% �18" 0.53% �--8" EXTRA 1016.08 INV. STRENGHT 1015.66 (O.D.) VCP SEWER \ 668+72.38 0 1015.26 TOP OF 4" GAS 1014.66 TOP OF PIPE (O.D.) 669+00 669+50 670+00 > > o? o? O O Ki 0) r: rn M O M +to +r: o � O r- O r� O .- 670+50 �8" EXTRA STRENGTH VCP SEWER --t r: M + N r` ca Muj O M + , N Li J O z a v � M (n + w N t0 � N N O 1024.0 1022.0 WATER 0 LATERAL 1020.0 -S=0.53% 1018.0 1016 0 > ; >:86 z z "t z -t as cD c0 rn c0 00 U m N ?� zM� �� 1014.0 00 00 +,00 + 06 C ~ J^ JN- N ON 3:w z � ij(D c^0-Q_in N w r` N FINISH GRADE o OVER PIPE 1019.34 INV. 1018.56 INV. I 39.00' LATERAL "A" 671+00 671+50 672+00 POTHOLE AND VERIFY UNDER M.W.D. SUPERVISION. CALL JOHN OSORNIA OF THE WATER SYSTEMS OPERATIONS GROUP AT (951) 710-5570. p (1018.40)± FS 670+35.00 _ 1017.16 TOP OF STEEL SLEEVE 120.92 RI MO 1016.08 INV. -8 SEWER - 1014.66 TOP OF P.C.P. (O.D.) j 0.53% 669+00 S 69000 SANTA ANA AVENUE SEE SECTION HEREON w _ w W 0.53% 67�+00 8 S o - E SEWER CONSTRUCTION NOTES QUANTITIES OCONSTRUCT 8" EXTRA STRENGTH VCP SEWER PIPE PER CITY REQUIREMENTS. 442 LF 3939 E. CORONADO STREET PIPE BEDDING BACKFILL AND REPAVING TO BE IN ACCORDANCE WITH CITY OF FONTANA STD. 1008. OCONSTRUCT 6" SEWER CLEANOUT PER CITY OF FONTANA STD. 2004. 1 EA OCONSTRUCT MANHOLE PER CITY FONTANA STD. 2001. 2 EA O4 CONSTRUCT DROP MANHOLE PER CITY FONTANA STD. 2002. CONTRACTOR SHALL BE (909) 335-7507 7951 REDWOOD AVENUE RESPONSIBLE TO MAINTAIN UNINTERRUPTED FLOW IN EXISTING SEWER MAIN DURING CONSTRUCTION. 1 EA O5 RELOCATE EXISTING UTILITY TO PROVIDE MINIMUM 12" CLEARANCE, IF REQUIRED. 4 EA FONTANA WATER COMPANY SHOULD CONSTRUCTION OF THE REQUIRED 15966 ARROW ROUTE CABLE -TV IMPROVEMENTS NOT COMMENCE WITHIN TWO OeP� TSS (909) 822-2201 YEARS OF THE DATE OF APPROVAL SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER, THE No. 43082 i �9•l� vir S-- CITY ENGINEER MAY REQUIRE REVISIONS TO THE w.. PLANS TO BRING THEM INTO CONFORMANCE WITH •L �T'IFOFfCAI�F���\P DATE ENGR. I CITY DATE STANDARDS IN EFFECT. CHRISTOPHER COLUMBUS TRANSCONTINENTAL FREEWAY SLOVER AVENUE w w z z L'' w > Of m > Q Q Q SITE SANTA ANA AVENUE � �Al1,4ALI-1 VICINITY kAeP NOT TO SCALE UTILITY PROVIDERS SEWER TELEPHONE CITY OF FONTANA AT&T 8353 SIERRA AVENUE 3939 E. CORONADO STREET FONTANA, CA 92335 ANAHEIM, CA 92807 (909) 350-7629 (714) 666-5503 GAS SOUTHERN CALIFORNIA GAS CO. ELECTRIC SAN DIMAS, CA 91773 SOUTHERN CALIFORNIA EDISON (909) 335-7507 7951 REDWOOD AVENUE FONTANA, CA 92336 WATER (714) 796-9932 FONTANA WATER COMPANY 15966 ARROW ROUTE CABLE -TV FONTANA, CA 92335 TIME WARNER CABLE (909) 822-2201 (909) 975-9493 CALTRANS CLASS II AGGREGATE 668+63.11 BASE 12" AB COMPACTED TO (1018.40) FS 95% RELATIVE COMPACTION. 8" EXTRA STRENGTH V.C.P. PIPE ° `1.24' ° 1020.0 - _-_-_-_----- START 18" 1018.0 STEEL SLEEVE ` 668+37.53 w 8.00' -cD0 8.0 " PROTECTIVE BLANKET 672+50 672+75 SEE SEPARATE SEWER AND WATER PLAN FOR CONTINUATION. I� 2 I _ LATERAL "A 5 ;f 673+00 672+37.44 (1022.47) RIM 3 1018.26 INV. LEGEND INV = INVERT HDPE = HIGH DENSITY POLYETHYLENE FS = FINISHED SURFACE AB = AGGREGATE BASE STD = STANDARD STA = STATION V.C.P. = VITRIFIED CLAY PIPE P.C.P. = PRECAST CONCRETE PIPE OF 2 SACK CONCRETE SLURRY 1014.66/ TOP OF P.C.P. r Prepared Under The Supervision Of JOSEPH C. TRUXAW AND ASSOCIATES, INC. 265 S. ANITA DRIVE, SUITE 111 ORANGE, CA 92868 DRAWN BY: PHONE: (714) 935-0265 KDL FAX: (714) 935-0106 DESIGNED BY: KDL r.�. Date :_7.2_./!r CHECKED BY: WILLIAM T. TRUXAW R.C.E. 43082 WTT 6.5" AC PAVEMENT ° 18" STEEL CASING .11 END 18" STEEL SLEEVE 669+50.00 1015.66 BOTTOM OF STEEL CASING --EXISTING 11'-8" (I.D.) MWD PIPE SEWER LINE SECTION AT � OF MWD PIPE STA. FRR+R_A 11 NOT TO SCALE GRAPHIC SCALE 40 0 20 40 80 160 ( IN FEET ) 1 inch = 40 ft. CITY OF FONTANA, CALIFORNIA SEWER IMPROVEMENT PLAN SANTA ANA AVENUE SCALE: 1 "=40' -FROM STA. 668+43.03 DATE: T T-+44.44 3/2/15 APPRWVED BY: / DRAWING NO.: 1DATE:- 6 CITY R R.C.E. 51152 5224 /1