HomeMy WebLinkAbout4237-4F
24'
EXACT LOCATION OF CONTROLLER SHALL BE AGREED
UPON BY EDISON, CITY LANDSCAPE INSPECTOR AND
CONTRACTOR PRIOR TO ANY TRENCHING OR
WIRE PLACEMENT
10'
T FOR
CONTROLLER
WIRES CONDUIT AND CONDUCTOR SIZES ARE BASED ON NONMETALLEC CONDUIT
AND COPPER CONDUCTORS VITH TYPE 'THHN/THWN• INSULATION:
GENERAL NOTES.
PROVIDE 100A METER AND 50A/2P MAIN C/B WHERE INDICATED
ON DRAVINGS
PROVIDE PtNELBOARD VHERE INDICATED ON DRAWINGS.
PROVIDE IRRIGATION CONTROLLER CABINET VHERE INDICATED
ON DRAVINGS.
TERMINATE AT EXISTION HANDHOLE. PER S.C.E. COMPANY REQ.
VERIFY EXACT LOCATION AND TERMINATION REQ. WITH S.C.E. CO.
PRIOR TO TRENCHING
FRONT VIEW
NTS
IRRIGATION CONTROL
BOARD
I ri
I.I
METER Ii
16'
METER FACES
STREET
36'
L
12'
▪ 90'
SVEEP
ELLS
.-„
CONDUIT FOR
CONTROLLER
WIRES
END VIEW
N IS
STRONG BOX
MODEL NO. SB— 24SS/120V
ELECTRIC METER & IRRIGATION CONTROLLER ENCLOSURE
aorESS/oa,
A 1 w�
No. 25126
EXP. 12/31/01
CIVIL
!E OF CAL‘‘
APPROVED BY:
CITY ENGINEER DATE:
ROBERT W. WEDDLE
DRAWN BY: TIMOTHY RASTEDT
DATE OF LAST REVISION:
CITY OF FONTANA
STRONG BOX
STD. PLAN NO.505
SHT. 10F3
G
WATERPROOF ALL
WIRE CONNECTIONS
AS PER STD.
RED
DELETE
BLACK
R
DIAMETER SAME SIZE
AS FLOW METER SIZE
MINIMUM DISTANCE UPSTREAM
10X DIAMETER OF FLOW
METER SIZE
MINIMUM DI TANCE DOWNSTREAM
5X DIAMETER OF FLOW METER SIZE
CC
No. 25126
4c EXP. 12/31/01
CIVIL
ldTE or CAl1F
APPROVED BY:
CITY ENGINEER DATE:
ROBERT W. WEDDLE
DRAWN BY: TIMOTHY RASTEDT
DATE OF LAST REVISION:
CITY OF FONTANA
FLOW METER
STD. PLAN NO. 510
SHT. 1❑F1
E
NOTE'
ALL POWER WIRES, GROUND WIRES ETC. SHALL BE
SEPARATELY SLEEVED AND SWEPT THROUGH
ENCLOSED PAD WITH SCH 40 RIGID CONDUIT
ALL SLEEVING SHALL BE A MINIMUM OF 18' BELOW
FINISHED GRADE. ALL SLEEVING IS A GRAPHIC REPRESENTATION
OF A TYP. INSTALLATION.
SIZE OF EQUIPMENT - 46'V X 18'D X 54' HIGH
ANSIZE OF CONC. SLAB - 52'V X 24'D X 8' THICK
V/84 REBARS AT 12' 0.C. TYP
4"
PROVIDE 20 AMP
2 POLE BREAKER
FOR NEW PUMPS
VHERE APPLICABLE
FINISHED GRADE
50 A
2P
GROUND FOR ELECTRICAL
mol
120/240
0 3V
12 CIR
PANEL
T
`�- 3/4'C, 116
SI
POWER
8' DIA X 12' D.
BOTTOMLESS GROUND WELL
WITH PARKWAY COVER,
FILL VITH PEA GRAVEL
5/8'DIA X 10' DRIVEN GROUND
ROD PER ARTICLE 250-81
OF 1990 NEC
PUMP
TEMPLA
ONCRETE
MOUNTING
SLAB
• CONDUIT FOR
GROUND ROD
INSTALLATION
EXTRA 1' CONDUITS
ELECTRIC METER & IRRIGATION CONTROLLER ENCLOSURE
No. 25126
* EXP. 12/31/01
CINE
841E of (ADEN
70
APPROVED BY:
CITY ENGINEER
ROBERT W. WEDDLE
DRAWN BY: TIMOTHY RASTEDT
DATE:
DATE OF LAST REVISION:
CITY OF FONTANA
STRONG BOX
STD. PLAN NO. 505
SHT. 2❑F3
F
10' VALVE BOX MARKED W/ 2'
LETTERS READING Q.C.
W/ LOCKING BOLT LII'
FINISH GRAD
QUICK COUPLER VALVE
12' MIN. FROM HARDSCAPE MATERIALS
6' MIN PEA GRAVEL
BRASS STREET ELL TY
•
—11=11=11-11-11-11-11-11-11-11•
1111-11-11=1111=11=