HomeMy WebLinkAbout3705-1GENERAL SEWER NOTES: 1 ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD PLANS, THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION UNLESS OTHERWISE NOTED. 2 WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CAN NOT BE RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK", THE CONTRACTOR SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEER FOR RESOLUTION. 3 ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER. 4 CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY DEVE— LOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK. INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE START OF ANY WORK IN PUBLIC RIGHT—OF—WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610. 5 THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST NON—METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER. 6 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES. 7 THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF INDUSTRIAL SAFETY. 8 THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS PURSUANT TO THE REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND MOVEMENT. 9 NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT—OF—WAY WITHOUT OBTAINING A SEPARATE PERMIT FOR THAT PURPOSE. 10 THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION. HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE, IN THE FIELD, THE TRUE LOCATION AND ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER PRECAUTION TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT 1-800-227-2600 TWO WORKING DAYS BEFORE EXCAVATION. 11 THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING, BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND CALTRANS. ALL UTILITY COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK AROUND THEIR FACILITIES. 12 THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR VALVE OPERATION AND WATER REQUIREMENTS. 13 STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE NOTED. 14 ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE THE CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING DURING CONSTRUCTION. 15 THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER. 16 REMOVAL AND REPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING SURVEY MONUMENTS, MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED CML ENGINEER OR LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE WEEK PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT. 17 THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION AREA FOR RESIDENTS AND EMERGENCY VEHICLES. 18 THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL, INCLUDING ADEQUATE WATERING, AT ALL TIMES. 19 THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT—OF—WAY DURING CONSTRUCTION WITHOUT PRIOR WRITTEN APPROVAL. 20 NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR. 21 A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE TO OBTAIN THE REQUIRED DENSITY SHALL REQUIRE RE—WORKING OF 77 -IAT PORTION OF THE WORK UNTIL THE SPECIFIED DENSITY IS OBTAINED. 22 CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE TEMPORARY NON—ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS. 23 ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH EXISTING CONCRETE. 24 IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A TERMINAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE DOWN STREAM MANHOLE, SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT. 25 SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS OF THE ASTM DESIGNATION C700 FOR V.C.P.. 26 NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL OF THE CITY ENGINEER. 27 SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE WALLS TO ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT. 28 PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND VERIFY ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS TO EXISTING FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCATIONS SHOWN ON THE PLANS. 29 ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS OTHERWISE APPROVED BY THE CITY ENGINEER. 30 TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12" BELOW THE GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE STREET RIGHT—OF—WAY, THE LATERAL SHALL TERMINATE 3 FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY EASEMENT. 31 THE SEWER CONTRACTOR SHALL STAMP AN "5" IN THE FACE OF THE CURB AT THE LOCATION OF THE SEWER LATERAL. 32 IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED IMPROVEMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY. 33 NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN PLACED, INSPECTED AND APPROVED. 34 ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING OF STREETS. 35 APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT 36 ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED TO FINISHED GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING 37 UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING, BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION OF THE CITY TRAFFIC ENGINEER. 38 AS—BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF RECORD, WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER. M. W.D. CONSTRUCTION NOTES: 1. NOTIFY MR. JOE MIRONE OF M.W.D. 'S WATER SYSTEM OPERATIONS GROUP, TELEPHONE (909)776-2664, AT LEAST TWO (2) WORKING DAYS (MONDAY THROUGH THURSDAY) PRIOR TO ANY WORK IN THE VICINITY OF MWD'S FACILITIES AND RIGHT–OF–WAY. 2. EXISTING PIPELINE IS ADEQUATE FOR AASHTO H-20 LOADING, WITH A MINIMUM 4 FEET OF COVER, DURING CONSTRUCTION, WITH A MINIMUM 5 FEET OF COVER, EQUIPMENT IMPOSING LOADS NO GREATER THAN THOSE IMPOSED BY A LOADED CATERPILLAR 657E OR A 666B SCRAPER MAY OPERATE OVER THE PIPELINE, PROVIDED THE GROUND IS MAINTAINED IN A SMOOTH CONDITION ON BOTH SIDES OF THE PIPELINE. 3. A LIST AND SPECIFICATIONS OF ALL CONSTRUCTION EQUIPMENT PROPOSED TO BE USED OVER THE PIPELINE MUST BE SUBMITTED FOR M.W.D. 'S REVIEW AND APPROVAL AT LEAST 30 DAYS PRIOR TO CONSTRUCTION. 4. ALL M.W.D. 'S STRUCTURES SHALL BE NOTED AND LOCATED PRIOR TO ANY CONSTRUCTION WORK, WHEN A MANHOLE OR OTHER M.W.D. FACILITY MUST BE MODIFIED TO ACCOMMODATE THE CONSTRUCTION, THE FACILITY SHALL BE MODIFIED BY M.W.D. FORCES. CITY OF FONTANA UTILITY NOTIFICATION LIST CITY OF FONTANA ATTN: BRIAN WREN 8353 SIERRA AVENUE FONTANA, CA 92335 (909) 350-6632 SO. CALIFORNIA GAS COMPANY ATTN: GREG GASPAR 16231 VALLEY BLVD. FONTANA, CA. 92335 (909) 428-8411 EMERGENCIES: (800) 427-2200 SO. CALIFORNIA EDISON COMPANY 7951 REDWOOD AVE. FONTANA, CA. 92335 (909)) 820-5598 – UNDERGROUND (909 875-5100 637-1233 –PIPELINES SONS (909) 357-6233 – DISTRIBUTION CRAWFORD CANYON MUTUAL WATER CO. ATTN: BASIL J. FABRIZIO (909) 463-9580 UNDERGROUND SERVICE ALERT (800) 422-4133 METROPOLITAN WATER DISTRICT WATER SYSTEM OPERA TION GROUP ATTN: JOE MIRONE (909) 776-2664 PACIFIC BELL CO. ATTN: NORMA GUILLOT 1265 N. VAN BUREN STREET SUITE 180 ANAHEIM, CA 92807 (714) 666-5401 COMCAST (CABLE TV) ATTN: JACK HA YES 1205 DUPONT AVENUE ONTARIO, CA. 91761 (909) 390-4738 VERIZON ATTN: STEVE HOCK 1400 E. PHILLIPS BLVD. POMONA, CA. 91766 (909) 469-6327 FONTANA WATER COMPANY ATTN: MICHAEL J. McGRAW 8440 NUEVO AVENUE FONTANA, CA 92335 (909) 822-2201 FAX: (909) 823-5046 WEST VALLEY WATER DISTRICT ATTN: LON TSAI 855 W. BASELINE ROAD RIALTO, CA 92377 PRIVATE ENGINEER'S NOTICE TO CON TRA C TORS THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES OR STRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY A SEARCH OF AVAILABLE RECORDS; TO THE BEST OF OUR KNOWLEDGE, THERE ARE NO EXISTING UTILITIES EXCEPT THOSE SHOWN ON THESE PLANS. THE CONTRACTOR IS REQUIRED TO TAKE DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN ON THESE DRAWINGS. THE CONTRACTOR FURTHER ASSUMES ALL LIABILITY AND RESPON– SIBILITY FOR THE UTILITY PIPES, CONDUITS OR STRUCTURES SHOWN OR NOT SHOWN ON THESE DRAWINGS. CITY OF FONTA E I PROVERNE T PLK OX ENUE 6:76 T.T.M. No. PA 13 ,T; TM .. 68 7039 T.T.M. No. PA 14 7040 411111 • . 6874 /No -1 3 •• INN Mr 11111111 SOUTHERN CALIFORNIA EDISON EASEMENT .T M. N . 1 til THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR THE JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT; INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT THIS SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE OWNER AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER OR THE ENGINEER. CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF ANY WORK. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOT/FY THE ENGINEER OF ANY DISCREPANCIES. BEGINNING OF WORK MEANS ACCEPTANCE OF CONDITIONS. CONTRACTOR SHALL COMPLY WITH ALL N. P. D. E. S REQUIREMENTS. LEGEND A. C. B.C. B. V. C. B.W. C.B. C.L. E. C. E.P. E.G. E.V.C. F.L. FS. G.B. H.P. INV. 0.C. ASPHALTIC CONCRETE BEGIN CURVE BEG. VERTICAL CURVE BACK SIDEWALK CATCH BASIN CENTERLINE END CURVE EDGE PAVEMENT EDGE GRADE END VER 77CAL CURVE FLOW LINE FINISH SURFACE GRADE BREAK HIGH POINT INVERT ON CURVE P.C.C. (R) R/W TAN. T. C. W V (590.77) 590.77 Y Y 17/ll, 1/I PORTLAND CEMENT CONCRETE RIDGE LINE RIGHT OF WAY TANGEN T TOP OF CURB W/DTN VER 77 CAL DEPTH INDICATES EX/STING ELEVA 7TON INDICATES PROPOSED ELEVA TION INDICATES SLOPE 2: 1 AC PAVEMENT REMOVAL GRIND EDGE OF PA VEMEN T MH 4 MH 3 ▪ 1�. 168,6 PA 7 PA 20 PA 22 T.T.M. No. 17041 PA 16 MH,2 MH ;' 1 �I J! Mt i T.T.M. No. 17042 PA 17 PA 12 . 'I - INDEX MAP SCALE: 1 "=300' NOTE: LOCATIONS OF LINES AND LATERALS AND STREET CONNECTIONS HAVE NOT BEEN APPROVED. LOCAL STORM DRAIN LINE AND LATERAL CONNECTIONS MAY CHANGE UPON CITY/FIRE REVIEW OF TENTATIVES ONCE THEY ARE FORMALLY SUBMITTED FOR CITY REVIEW. CONSTRUCTION NO TES: QUANTITIES: INSTALL 10" EXTRA STRENGTH V.C.P. SEWER 1,874 LF INSTALL 8" EXTRA STRENGTH V.C.P. SEWER I Gq-LF CONSTRUCT PRECAST CONCRETE MANHOLE PER CITY 10 EA OF FONTANA STD. DWG. NO. 112 0.D.=48"). INSTALL 8" V.C.P. PLUG. 7 EA REMOVE PLUG AND JOIN EXISTING SEWER. 1 EA CONSTRUCT PRECAST CONCRETE MANHOLE PER CITY 1 EA OF FONTANA STD. DWG. NO. 112 0.D.=60"). INSTALL 8" D.I.P. SEWER, CLASS 350. .Z17 LF CONSTRUCT CONCRETE ENCASEMENT PER DETAIL ON SHT NO. 1. 80 LF +34 LFQ TABLE: 200-1.2 [A] SIEVE SIZE PERCENTAGE PASSING SIEVES 1 1‘.2" – 3/4 n 100 1/2'" 90-100 3/8" 20-60 NO. 4 0-15 NO. 8 0-5 ASTM C 131 TEST GRADING B VICINITY MAP N.T.S. 6" MIN. 10" MAX. TOP OF STRUCTURAL PAVEMENT SUBGRADE 3" MAX. SIZE NATIVE SOIL COMPACTED 95%. 6" MAX. SIZE NATIVE SOIL COMPACTED 96%. V.C.P. 10' OR DEEPER USE 1/2" CRUSHED STONE BEDDING PER STD. SPECS. FOR PUBLIC WORKS CONSTRUCTION - TABLE 200 1.2 [Al RECORD DRAWING/J THESE RECORD DRAWINGS HAVE BEEN PREPARED, IN PART, ON THE BASIS OF INFORMATION COMPILED AND FURNISHED BY OTHERS. THE ENGINEER WILL. NOT BE RESPONSIBLE FOR ANY ERROR6 OR OMISSIONS WHICH HAVE BUM INCORPORATED INTO THE DOCUMENTS AS A RESULT THEREOF. BENCH MARK: / 8-17 CAL TRANS BENCHMARK -17. A BRASS CAP IN THE CMICRETE BASE OF THE SOUTH LEG OF AN SCE TOWER 343' NORTH OF HIGHLAND, 0.2 M/ WEST OF SAN SEVA/NE RD., 2.65 MI WEST OF SIERRA AVE ELEVATION: 1 1428.609 BASIS OF BEARINGS: THE BRC N08959'31 "E ALONG THE CL SUMMIT AVE AS SHOWN ON TR. NO. 16427-1, M.B. 296/7-11. 6" TYP VARIES 6" MIN. 10" MAX. 1:1 SLOPE OR FLATTER OR ADEQUATE SHORING 1" MAX. SIZE SELECTED NATIVE BEDDING COMPACTED TO 90%. O TYPICAL BEDDING DETAIL N.T.S. a- 24" O.C. 0 • 4.4 44 14 • 4 .4a • 4 . 4 b. a4. •••4 4 • 4. .. 4 4 • .4 • a s 47- • 4 .• 4. 4 2" TYP CONCRETE INCASEMENT CLASS 560-C-32po P.C.C. "ER SECTION 201 OF THE STANDARD SPECIFICATION PIPE ENCASEMENT DETAIL "B" N.T.S. NOTES: 1. TRENCH WIDTH SHALL BE CONTROLLED TO TOP OF PIPE ZONE. 2. TRENCH DEPTHS OF GREATER THAN 5' SHALL HAVE ADEQUATE SHORING. 3. CLASS II AGG.BASE ALL TRENCHES LESS THAN 100' IN LENGTH. 4. COMPACTION SHALL BE 90% IN ALL ZONES UNLESS OTHERWISE SPECIFIED. TRENCH STABILITY SHALL CONFORM TO CAL–OSHA REQUIREMENTS. DIAL TWO WORKING BEFORE 4 �► YOU DIG DAYS BEFORE YOU DIG TOLL FREE 1-800-227-2600 A PUBUC SERVICE BY UNDERGROUND SERVICE ALERT REV. REVISION DESCRIPTION DATE ENGR. CITY DATE n REC,D14Gr REV. LA-r,sLI7 a*4/REV. N44ESI+T.3 mit, �ED T WO MN SHOWED PI I L T'? 3`4S' SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER, THE CITY ENGINEER MAY REQUIRE REVS/ONS TO THE PLANS TO BRING THEM INTO st4.6NFORMANCE WITH CONDITIONS AND STANDARDS IN EFFECT. �g•r7,� Prepared Under The Supervision Of : PREPARED IN THE OFFICE OF MADOLE AND ASSOCIA TES, INC. 760-A SOUTH ROCHESTER AVENUE ONTARIO, CA 91761 PHONE (909) 937-9151 ,.Date . CITY OF FONTANA, CALIFORNIA SEWER IMPROVEMENT PLANS CE 36637 EXP. 6-30-0 WENDELL L. I WA TSURU DRAM BY: t2M/ MA DESIGNED BY: CHECKED BY: aI TITLE SHEET KNOX A ENUE SCALE - AS SHOWN DATE: JAN 2004 Lu (O