HomeMy WebLinkAbout3400-1GENERAL SEWER NOTES:
1 ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA
STANDARD PLANS, THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS
FOR PUBLIC WORKS CONSTRUCTION ("GREEN BOOK"). ALL REFERENCE
SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION
UNLESS OTHERWISE NOTED.
2 WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT
CAN NOT BE RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN
BOOK; THE CONTRACTOR SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY
ENGINEER FOR RESOLUTION.
3 ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER.
4 CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY DEVE—
LOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK. INSPECTION
COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE START OF
ANY WORK IN PUBLIC RIGHT—OF—WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610.
5 THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND
PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST
NON—METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER.
6 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES,
DELINEATORS OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES.
7 THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK
FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION
OF INDUSTRIAL SAFETY.
8 THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH
SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS
PURSUANT TO THE REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE
OF CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN
THE POTENTIAL EXISTS FOR GROUND MOVEMENT.
9 NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT—OF—WAY WITHOUT
OBTAINING A SEPARATE PERMIT, FOR THAT PURPOSE.
10 THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE
INFORMATION. HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRAC TOR
TO DETERMINE, IN THE FIELD, THE TRUE LOCATION AND ELEVATION OF ANY EXISTING
UTILITIES, AND TO EXERCISE PROPER PRECAUTION TO AVOID DAMAGE THERETO.
THE CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT 1-800-227- 2600
TWO WORKING DAYS BEFORE EXCAVATION.
11 THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES
INCLUDING, BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION,
LANDSCAPING, LANDSCAPE IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER,
STORM DRAIN, FLOOD CONTROL AND CALTRANS. ALL UTILITY COMPANIES SHALL BE
GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK AROUND THEIR FACILITIES
12 THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT
APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE
WATER COMPANY FOR VALVE OPERATION AND WATER REQUIREMENTS
13 STATION/NG REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE NOTED.
14 ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE
THE CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES THE CONTRACTOR SHALL
BE RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL
STAKING DURING CONSTRUCTION.
15 THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT
TIES OR BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER.
16 REMOVAL AND REPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING SURVEY
MONUMENTS, MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED
CIVIL ENGINEER OR LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE
DESTROYED AS A RESULT OF THIS CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR
SHALL NOTIFY THE ENGINEER ONE WEEK PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS
CAN BE ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT.
17 THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL
TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION
AREA FOR RESIDENTS AND EMERGENCY VEHICLES.
18 THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL,
INCLUDING ADEQUATE WATERING, AT ALL TIMES
19 THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS
TO BE DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT—OF—WAY
DURING CONSTRUCTION WITHOUT PRIOR WRITTEN APPROVAL.
20 NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR.
21 A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE
TO OBTAIN THE REQUIRED DENSITY SHALL REQUIRE RE—WORKING OF THAT PORTION
OF THE WORK UNTIL THE SPECIFIED DENSITY IS OBTAINED.
22 CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING
STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE
TEMPORARY NON—ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS
23 ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH
TO MATCH EXISTING CONCRETE.
24 IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE
A TERM/NAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE
DOWN STREAM MANHOLE, SEE CITY OF FONTANA STANDARD DETAIL FOR TERM/NAL CLEANOUT.
25 SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE
VITRIFIED CLAY PIPE (V. C. P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS
OF THE ASTM DESIGNATION C700 FOR V.C.P..
26 NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL
OF THE CITY ENGINEER.
27 SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE
WALLS TO ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT.
28 PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND
VER/FY ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS
TO EXISTING FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCATIONS
SHOWN ON THE PLANS.
29 ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS OTHERWISE
APPROVED BY THE CITY ENGINEER.
30 TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12"
BELOW THE GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE
STREET RIGHT—OF—WAY, THE LATERAL SHALL TERMINATE 3 FEET INSIDE THE LOT AS
MEASURED FROM THE UTILITY EASEMENT.
31 THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE
LOCATION OF THE SEWER LATERAL.
32 /F EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED
IMPROVEMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED
AGENCIES IMMEDIATELY.
33 NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN
PLACED, INSPECTED AND APPROVED.
34 ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR
TO PAVING OF STREETS.
35 APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT
36 ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED
TO FINISHED GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING
37 UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING,
STRIPING, BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION
OF THE CITY TRAFFIC ENG/NEER.
38 AS—BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF
RECORD, WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER.
I -1p eNIG1NeUrNNG, 1iJc.
!4G5 C4esrviUV) 120A.12
RPVLANPG,cA• 92371-
(709
12379'c Q Viet- C071/
u Ry c-
510 -Y7,
-51t' 7, W. 4130914-
4
`Q,
7;
r 2
MH I4
CITY OF FONTANA
OFF SITE
SEWER IMPROVEMENT PLANS
TRACT NO 1627
FONTANA HIGH
SCHOOL #4
--
s
77?4e7, 11-642-7_i
t
i 4 i C . k 4
w w w
Oj
CURTIS
T
SHT. 4
3
MH
I;
M
MH
j16
Stozrater
w
SIERRA LAKES
71, r-
VENUES8
ol�lw
PARKWA Y
INDEX MAP
NOT TO SCALE
LAKES PKWY.
TABLE: 200-1.2 [A]
SIEVE SIZE
PERCENTAGE
PASSING SIEVES
1 1‘2"
-
1
3/4"
100
1/2"
90-100
3/8"
20-60
NO. 4
0-15
NO. 8
0-5
ASTM C 131
TEST GRADING
B
PRIVATE ENGINEER'S NOTICE TO CONTRACTORS
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES OR STRUCTURES
SHOWN ON THESE PLANS ARE OBTAINED BY A SEARCH OF AVAILABLE RECORDS;
TO THE BEST OF OUR KNOWLEDGE, THERE ARE NO EXISTING UTILITIES EXCEPT
THOSE SHOWN ON THESE PLANS. THE CONTRACTOR IS REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN ON THESE
DRAWINGS THE CONTRACTOR FURTHER ASSUMES ALL LIABILITY AND RESPON-
SIBILITY FOR THE UTILITY PIPES, CONDUITS OR STRUCTURES SHOWN OR NOT
SHOWN ON THESE DRAWINGS.
THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONS-
IBILITY FOR THE JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION
OF THIS PROJECT; INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT
THIS SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS;
AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE OWNER
AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED,
IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING
FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER 01? THE
ENGINEER.
CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AND SHALL REPORT
ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK.
CONSTRUCTION NOTES:
QUANTITIES:
INSTALL 8" EXTRA STRENGTH V.C.P. SEWER. 97 L.F.
INSTALL 15" EXTRA STRENGTH V.C. P. SEWER. 3,612 L. F.
CONSTRUCT PRECAST CONCRETE MANHOLE PER CITY OF 9 Ea.
FONTANA STD. DWG. NO. 112 (ID=48').
INSTALL 8" SEWER PLUG. 2 Ea.
INSTALL 15" SEWER PLUG. 2 Ea.
REMOVE PLUG AND CLEAN-OUT, JOIN AT EXISTING SEWER.
CONSTRUCT PRECAST CONCRETE MANHOLE PER CITY OF
FONTANA STD. DWG. NO. 112 OD= 60 ").
REMOVE EXIST. 15" SEWER MAIN & CLEANOUT
INSTALL 10" EXTRA STRENGTH V.C.P. SEWER.
INSTALL 10" SEWER PLUG.
REMOVE AND REPLACE EXIST. A.C. PAVEMENT, AND REPAIR
TRENCH PER CITY OF FONTANA STD DWG. NO. 131.
(SEE KNOX AVE. STORM DRAIN PLAN, DWG. 3401, FOR
PAVEMENT RECONTRUCTION).
CONSTRUCT CONCRETE ENCASEMENT PER DETAIL ON SHT. NO. 4.
INSTALL 4" V.C.P. SEWER LATERAL AND PLUG PER CITY OF
FONTANA STD. DWG. NO. 125.
�t'VSTALL 4" �9W. mrb AI I'EK car srp(04 17 NO. 2elas ZOPCr
1 Ea.
8 Ea.
60 L.F.
1,283 L.F.
2Ea.
15,360 S.F.
14 L.F.
718 L.F.
EA.
CITRUS AVE
VICINITY MAP
NOT TO SCALE
6" MIN.
10" MAX.
3" MAX. SIZE
NATIVE SOIL
COMPACTED 95%.
6" MAX. SIZE
NATIVE SOIL
COMPACTED 90%.
V.C.P.
10' OR DEEPER USE 1/2"
VARIES
f y
SUMMIT
AVE.
6" MIN.
10" MAX.
1" MAX. SIZE
SELECTED NATIVE
BEDDING COMPACTED
TO 90%.
Y - 1 `-i. 4
�i i-� f
CRUSHED STONE BEDDING
PER STD. SPECS. FOR
PUBLIC WORKS CONSTRUCTION
TABLE 200 1.2 [A].
BENCH MARK: # 8_17
CALTRANS BENCHMARK 8-17. A
BRASS CAP IN THE CONCRETE BASE OF
THE SOUTH LEG OF AN SCE TOWER
OASARD2.6IWESTFSNEVNE 5 MES
OF SIERRA AVE.
ELEVATION: 1 1428.609
BASIS OF BEARINGS:
THE BASIS OF BEARINGS FOR THIS MAP
IS
CL N00'12435�E ON RECORD
OF SURVEY MAP FILED IN
R.S.B. 111/99-103
!
TYPICAL BEDDING DETAIL
NOT TO SCALE
CITY OF FONTANA UTILITY NOTIFICATION LIST
CITY OF FONTANA
ATTN: CARLOS NAVARRO
8353 SIERRA AVENUE
FONTANA, CA 92335
(909) 350-6632
SO. CALIFORNIA GAS COMPANY
ATTN: GREG GASPAR
16231 VALLEY BLVD.
FONTANA, CA. 92335
(909) 428-8411
EMERGENCIES: (800) 427-2200
SO. CALIFORNIA EDISON COMPANY
7951 REDWOOD AVE.
FONTANA, CA. 92335
(909) 820-5598 - UNDERGROUND
(909) 875-5100 - TRANSMISSIONS
(213) 637-1233 - PIPELINES
(909) 357-6233 - DISTRIBUTION
(800) 422-4133
CRAWFORD CANYON MUTUAL WATER CO.
ATTN: BASIL J. FABRIZIO
(909) 463-9580
PACIFIC BELL CO.
ATTN: VIRGINIA BECKER
3939 E.CORONADO STREET
ANAHEIM, CA 92807
(714) 666-5467
COMCAST (CABLE TV)
ATTN: JACK HAYES
1205 DUPONT AVENUE
ONTA 'IO, CA. 91761
(909) 390-4738
GENERAL TELEPHONE COMPANY
ATTN: STEVE HOCK
1400 E. PHILLIPS BLVD.
ONTARIO, CA. 91766
(800) 422-4133
FONTANA WATER COMPANY
ATTN: MICHAEL J. McGRAW
8440 NUEVO AVENUE
FONTANA, CA 92335
(909) 822-2201
FAX: (909) 823-5046
RECORD DPAWiNG
THESE PECOPO Da VNINGS HAVE VEIN PREPARED, IN
PART, ON TME Ba► .'S OF INFORMATION COMPILED AND
FURNISHED BY OTHERS. THE ENGINEER WILL NOT b''E
RESPON . , E FOR A.:0' ERRORS CR O S,`ONS WHICH
HAA RESULTVE 6EENTfI:EPEO 2 TED INTO THE DOCUMENTS AS
4CEC%
DIAL
BEFORE
YOU DIG
RT
TWO WORKING
DAYS BEFORE
YOU DIG
TOLL FREE "` 1-800-227-2600
A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT
REV.
REVISION DESCRIPTION
DATE
ENGR.
CITY
INSTALL 421 sta i -r. vx caV sit). zoos e1 Ztoti 142114
RECoeo •D)46
2.v7.75
kr,
DATE
SHOULD CONSTRUCTION OF THE REQUIRED
IMPROVEMENTS NOT COMMENCE WITHIN TWO YEARS
OF THE DATE OF APPROVAL SHOWN HEREON AND
CARRIED FORTH IN A DILUENT MANNER, THE ',CITY
ENGINEER MAY REQUIRE REVISIONS TO THE PLANS TO
•IG'tcf . BRING THEM INTO CONFORMANCE WITH CONDITIONS
110.01 -AND STANDARDS IN EFFECT.
Prepared Under The Supervision Of :
PREPARED IN THE OFFICE OF
MADOLE AND ASSOCIATES, INC.
10601 CHURCH STREET , STE. 107
RANCHO CUCAMONGA, CA 91730
PHONE (909) 948-1311
Date : V•Z93
R.C.E. 62183V EXP. 9-30-05
CITY OF FONTANA, CALIFORNIA
SEWER IMPROVEMENT PLANS
DRAWN BY:
MA
DESIGNED BY:
EF
TRACT NO. 16427
TIT Sir ET
CITY
'g-3-03
ENGINEER R.C.E. 51152 DATE
SCALE:
AS SHOWN
DATE:
JULY 2003
DRAWING NO.:
3400 / 7
up
N
co
O
V
AK
co
00
co
co
J:\126-1662\sewer\Sew0l.dwa. 09/02/2003 09:19:49 AM. GB.GB