HomeMy WebLinkAbout4923-17(E) SERVICE ENTRANCE EQUIPMENT "SEE"
600A, 208/120V -30-4W
CT. M
� I 1 600A
600A % 3P
UGPS
� 55 90A 5 225A
o> 50A
3P � 0 3P ❑ o> 3P
� SPARE SPARE SPARE
TO EXISTING UTILITY
COMPANY TRANSFORMER.
d-
o L0
0
N
O
a;
N �
O C�
00
O
CO
j
C) v
U U
00 co
N N
I
w Ld
T
o
N
CU
9
F01
100A5 0l 30A 5 of 30A
2P � 1P f 1P
SPARE SPARE
TO
EXISTING
LOAD
I NEW DISTRIBUTION PANEL "SP"
— — --¢ 40OA-208/12OV-30-4W
BRACED AND RATED FOR 42,000AIC RMS
400A, 120/208V -30-4W
I
I I I PANEL LCP 1
(N) I I "Lp"E0.03
400A 400'A [D200A 100A G 100'A G 100A
3P 3P 3P 3P 2P 3P
I I
I I
06
(E) ,
GROUNDING = IF -1
W z¢
SYSTEM I
N � I � I 00 Da
V�
404
4 100AS 4
PANEL H 90AF i PANEL i
"WP -1" 3P
L_______j k00m"
(BY SLIDE i (BY i SITE
OTHERS) BOOSTER OTHERS) LIGHTING
PUMP _
(BY OTHERS)
BID ALTERNATE
SINGLE, LINE DIAGRAM
SCALE: NONE
CONNECTED LOAD CALCULATION
s
(E) SERVICE ENTRANCE EQUIPMENT "SEE"
PANEL LP
a- FdW 6WFEc2ooW
EXISTING LOAD =
16,640' VA
NEW DISTRIBUTION PANEL "SP" _
.91,758- VA
PANEL "RRB" =
161640 VA
Sub -total =
@ 208/120V -3P =
1089398- VA
301.1 amps
CONNECTED LOAD CALCULATION
s
NEW DISTRIBUTION PANEL "SP"
PANEL LP
a- FdW 6WFEc2ooW
PANEL "WP -1 " =
321354 VA
SLIDE BOOSTER PUMP =
21,384 VA
PANEL "RRB" =
161640 VA
PANEL "LP" =
21,380 VA
VOLT AMP'S
o
Sub -total =
@ 208/120V -3P =
91,758 VA
254.9 amps
o
FEEDER SCHEDULE
s
a- pox aww
PANEL LP
a- FdW 6WFEc2ooW
NC*'
SYMBOL
MAIN MLO
208 /120 VOLTS 3 PHASE 4
WIRE A.I.C. RATING:
SERIES RATING, SEE SLD.
COPPER BUS 100A
OROI ND
VOLT AMP'S
o
Y o
U
Y U
U VOLT AMPS
3/40C-3#12 AWG & 1#8 N
DESCRIPTIONO
30
033
3/44C(3)#10 AWG
034
3/4"C(4)#10 AWG
035
3/4"C(3)#10 AWG &(1)#6 (N)
DESCRIPTION
40
A O B O C
-1
m v v
g
1"C(4)#8 AWG
m
O A O B
O C
50
FLOOD LIGHTS POLE #1
1080
2
20 1
2
20
3 692
60
SECURITY LIGHTPOLE #1 & #2
----
1080
1-1 /4"C(4)#4 AWG
2 3
4
2
692'
073
-----
FLOOD LIGHTS POLE #2
1620
3
20 5
6
20
3
692
SECURITY LIGHT POLE #3 & #4
-----
1620
1-1/2-C(3)#2 & (1)#1 /0 (N)
2 7
8
2
692
104
-----
FLOOD LIGHTS POLE #3
1080
2
20 9
10
20/1
4 248:
2"C(4)#1 /0 AWG
BUILDING LIGHTS
-----
_ 1080
150
2 11
12
20/1 2
2"C(4)#1 /0 AWG
500
LIGHTING CONTROLS
FLOOD LIGHTS POLE #4
16203
173
20 13
14
20/1
2 1000
RECEPTACLES
- - - - -
1620
203
2 15
16
20/1
2 1000
2-1/2-C(5)#3/0 AWG
RECEPTACLES
WALKWAYS LIGHTS
488
4
20/1 17
18
20/1
2
1000
RECEPTACLES
SPACE
3"C(3)#250KCMIL
254
19
20
20/1
#4
SPARE
SPACE
4"C(3)#350KCMIL
304
21
22
20/1
#4
350
SPARE
SPACE..........23
354
4"C(4)#500 KCMIL
355
24
20/1
400
403
SPARE
SPACE
4"C(4)#600 KCMIL
405
25
26
450
453
SPACE
SPACE
(2)2-1/2"C(4)#4/0 AWG
455
27
28
500
503
(2)3"C(3)#250 KCMIL
SPACE
SPACE
505
(2)3"C(5)#250 KCMIL
29
30
603
(2)4"C(3)#350KCMIL
604
SPACE
605
(2)4"C(5)#350KCMIL
#1
31
32
(2)4"C(3)#500 KCMIL
704
(2)4"C(4)#500 KCMIL
705
(2)4"C(5)#500 KCMIL
#1/0
800
33
34
804
(2)4"C(4)#600 KCMIL
805
(2)4"C(5)#600 KCMIL
#1/0
......... .........
1003
35
36
(3)4"C(4)#400 KCMIL
.........
.........
#2/0
1200
1203
(3)4"C(3)#600 KCMIL
.10
39
40
1205
(3)4"C(5)#600 KCMIL
#3/0
1600
1603
(4)4"C(3)#600 KCMIL
1604
41
42
(4)4"C(5)#600 KCMIL
#4/0
2000
2003
O A = 6704 VA O B = 5720 VA
O C =
5380 VA
LCL = 14304 VA
LARGEST MOTOR (LM) _ (N/A)
TOTAL (O A + O B + O.C)
= 17804 VA + 25% LCL +
25% LARGEST MOTOR =
21380 VA OR
59.3
AMPS
HIGH PHASE (O A)
= 6704 VA + 25% LCL +
25% LARGEST MOTOR =
8130 VA OR
67.7
AMPS
o
FEEDER SCHEDULE
s
a- pox aww
8-"X4WFE
a- FdW 6WFEc2ooW
NC*'
SYMBOL
CONDUCTOR
SYIIIBOL
CONDLOTOR
SYMBOL
COI�DLCM
OROI ND
20
023
3/4"C-3#12 AWG
024
3/4"C-4#12 AWG
025
3/40C-3#12 AWG & 1#8 N
#12
30
033
3/44C(3)#10 AWG
034
3/4"C(4)#10 AWG
035
3/4"C(3)#10 AWG &(1)#6 (N)
#10
40
043
3/4"C(3)#8 AWG
044
1"C(4)#8 AWG
045
1 "C(3)#8 & (1)#4 (N)
#10
50
053
1-1 /4"C(3)'#6 AWG
054
1-1 /4"C(4)#6 AWG
055
1-1/4-C(3)#6 AWG & (1)#4 (N)
#10
60
063
1-1 /4"C(3)#4 AWG
064
1-1 /4"C(4)#4 AWG
065
1-1/4-C(3)#4 AWG & (1)#1 (N)
#10
70
073
1-1 /4"C(3)#4 AWG
074
1-1 /4"C(4)#4 AWG
075
1-1/4-C(3)#4 & (1)11 /0 (N)
#8
90
093
1-1 /4"C(3)#2 AWG
094
1-1 /2"C(4)#2 AWG
095
1-1/2-C(3)#2 & (1)#1 /0 (N)
#8
100
103
1-1 /2"C(3)#1 AWG
104
1-1 /2"C(4)#1 AWG
105
1-1 /2"C(3)#1 & (1) #3/0 (N)
#8
125
123
1-1/2-C(3)#1/0 AWG
124
2"C(4)#1 /0 AWG
125
2-C(3)#1/0 & (1)#250 KCML (N)
#6
150
153
1-1/2"C(3)#1/0 AWG
154
2"C(4)#1 /0 AWG
155
2"C(5)#1/0 AWG
#6
175
173
2"C(3)#2/0 AWG
174
2"C(4)#2/0 AWG
175
2"C(5)#2/0 AWG
#6
200
203
2"C(3)#3/0 AWG
204
2"C(4)#3/0 AWG
205
2-1/2-C(5)#3/0 AWG
#6
225
223
2"C(3)#4/0 AWG
224
2-1/2-C(4)#4/0 AWG
225
2-1/2-C(5)#4/0 AWG
#4
250
253
3"C(3)#250KCMIL
254
3"C(4)#250KCMIL
255
3"C(5)#250KCMIL
#4
300
303
4"C(3)#350KCMIL
304
4"C(4)#350KCMIL
305
4"C(5)#350KCMIL
#4
350
353
4"C(3)#500 KCMIL
354
4"C(4)#500 KCMIL
355
4"C(5)#500 KCMIL
#2
400
403
4"C(3)#600 KCMIL
404
4"C(4)#600 KCMIL
405
4"C(5)#500 KCMIL
#2
450
453
(2)2"C(3)#4/0 AWG
454
(2)2-1/2"C(4)#4/0 AWG
455
(2)2-1/2"C(5)#4/0 AWG
#2
500
503
(2)3"C(3)#250 KCMIL
504
(2)3"C(4)#250 KCMIL
505
(2)3"C(5)#250 KCMIL
#2
600
603
(2)4"C(3)#350KCMIL
604
(2)4"C(4)#350KCMIL
605
(2)4"C(5)#350KCMIL
#1
700
703
(2)4"C(3)#500 KCMIL
704
(2)4"C(4)#500 KCMIL
705
(2)4"C(5)#500 KCMIL
#1/0
800
803
(2)4"C(3)#600 KCMIL
804
(2)4"C(4)#600 KCMIL
805
(2)4"C(5)#600 KCMIL
#1/0
1000
1003
(3)4"C(3)#400 KCMIL
1004
(3)4"C(4)#400 KCMIL
1005
(3)4"C(5)#400 KCMIL
#2/0
1200
1203
(3)4"C(3)#600 KCMIL
1204
(3)4"C(4)#600 KCMIL
1205
(3)4"C(5)#600 KCMIL
#3/0
1600
1603
(4)4"C(3)#600 KCMIL
1604
(4)4"C(4)#600 KCMIL
1605
(4)4"C(5)#600 KCMIL
#4/0
2000
2003
(5)4"C(3)#600 KCML
2004
(5)4"C(4)#600 KCML
2005
(5)4"C(5)#600 KCML
250
2500
2503
(6)4"C(3)#600 KCML
2504
(6)4"C(4)#600 KCML
2505
(6)4"C(5)#600 KCML
350
3000
3003
(8)4"C(3)#600 KCML
3004
(8)4"C(4)#600 KCML
3005
(8)4"C(5)#600 KCML
400
4000
4003
(10)4"C(3)#600 KCML
1 4004
�i (10)4"C(4)#600 KCML
4005
(10)47C(5)#600 KCML
500
SHEET NOTES
1 #1/0 CU. EQUIPMENT BOND PER CEC 250-102(c)
LU 3/4"C—#1/0 CU. BOND TO COLD WATER PIPE PER CEC 250-104(A)
3/4"C—#1/0 CU. GROUND PER CEC 250-50, 250-52 (A1-3),
250-53 (C & D)
THERE SHALL BE A UL LISTED SERIES RATING OF 42/10KAIC
BETWEEN THE DISTRIBUTION CIRCUIT BREAKERS IN DISTRIBUTION
PANEL AND ALL DOWNSTREAM BRANCH CIRCUIT BREAKERS IN THE
PANEL. PROVIDE LABELING PER CEC.
PER CITY OF FONTANA, THIS CIRCUIT BREAKER TO REMAIN UNUSED.
L A N D S C A P E
ARCH ITECTU RE
310 N. JOY STREET
CORONA, CA 92879
T: 951.737.1 124
F: 951.737.6551
R E. r
j 9
Q
SIGNATURE rn
C)
9/30/13
EXP. DATE
ur
�9TF OF L \�0��
CA
CONSULTANT STAMP:
PROJECT:
MARTIN TUDOR
AQUATIC CENTER
RENOVATION PROJECT
PREPARED FOR:
C I T Y O F
CITY OF FONTANA
16489 ORANGE WAY
FONTANA, CA. 92335
CONTACT: DAN WEST
PHONE: 909-350-6530
PROJECT TRACKING DATE
1. PROGRESS SET 8-1-11
2. DAB SET 8-18-11
3. FIRST PLAN CHECK 10-3-11
4. 4th PLAN CHECK 01-12-12
5.
6.
7.
8.
DELTA REVISIONS DATE
1. l
2.
3.
4.
5.
6.
7.
8.
DATE PREPARED: 8-16-11
DRAWING SCALE: AS NOTED
DRAWN BY: OMB
DESIGNED BY: MWK
CHECKED BY: VHB
BMLA PROJECT NO: 1001 1210
a.
RD
GENERALNOTES: MNC:I-, r, In
wVVV~ o t
LIGHT LINEWEIGHT REPRESENTS WORK WHICH IS EXISTING TO REMAIN DIAL nVOWORKING
UNDISTURBED. BEFORE DAYOU DIG
RE
YOU DIG
HEAVY LINEWEIGHT REPRESENTS WORK TO BE COMPLETED AS PART OF THIS TOLL FREE 811
PACKAGE. A PUBLIC SERVICE BY
UNDERGROUND SERVICE ALERT
ELECTRICAL CONTRACTOR TO MATCH EXISTING EQUIPMENT MANUFACTURER
A.I.C. RATING (TYP.).
SHEET -
OMB ELECTRICAL ENGINEERS INC. DESCRIPTION
88 vResearch Drive S,INGLE LINE
Irvine, CA 92618
(949) 753-1553 Fax (949) 753-1992
mai*l@ombengrs.com
ail®ombengrs.com
OMB PM: VB DIAGRAM
JOB NO: 11184
CITY OF FONTANA
DRAWN BY: OMB PROJECT NAME
DESIGNEDBY: MARTIN TUDOR WATER PARK DATE
MWK 107
8/18/2011 EOmO2
CHECKED BY: APProuvvi DWG NO. 17
VHB0012-5152 R 4923 3'7
• Sheet 2 Of 9