Loading...
HomeMy WebLinkAbout3063LT-2c� a N O 0 N N U 0 a 0 0 CL 4~ - Aw Southern California Edison SCOPE CONDUIT 1.0 CONDUIT 1.1 Uniess'otherwise specified on the working drawing, all of the below listed conduit types are approved for use on the. Edison system. Conduit Type Application Concrete Encased Direct Buried Semi -Rigid Plastic (PVC) EF$ -20, EB -35 X - Semi -Rigid Plastic (PVC) DB -601 013-100 X X Rigid Plastic (PVC) Schedule 40-80 X X [Hot Dipped Galvanized Steel 1 Standard X X NOTE: Q:J Includes Intermediate metal conduit (IMC). 1.2 All conduit shall be installed per UGS 100.1 and shall be watertight. In known water or slubsidence areas, semi-rigid plastic conduit shall be used. 1.3 The correct cements as recommended by the manufacturer, shall be used on each plastic conduit type so as to obtain a watertight connection. 1.4 Horizontal Bends and Sweeps a. The difference between bends and sweeps is determined by their radii. Minimum radius for all bends is 36" and the maximum radius for all bends is 60". The radius of each bend is determined by conduit size, as follows: - 36" for conduit 3" in diameter and smaller - 48" for conduit 4" and 5" in diameter - 60" for conduit 6" in diameter The minimum radius for all sweeps of all size conduits is 121/2'. b. Bends and sweeps for EB and DB conduit shall be made from semirigid.: DS -68 or DB -11 00 conduit. Bends and sweeps made from DS -60 condui are intended for use with EB -20 and EB -35 conduit. Bends and sweeps made from 06-_100 conduit are intended for use with DB -60 and DB -100 conduit. 1.5 Short lengths of conduit, properly coupled, may be used in rigid conduit installations to form sweeps of a radius. not normally supplied by • manufacturers. The maximum deflection per length of conduit shall be: - 1/2" for lengths 2'/2' and shorter - 1 " for lengths over 2'/2' 1.6 All plastic (PVC) conduit must be manufactured by an Edison approved manufacturer (See UGS 115.1) and comply to Edison requirements. 1.7 EB -20 semi-rigid PVC conduit is preferred and should be utilized for standard installations requiring encasement. EB -35 PVC conduit can be installed in lieu of EB -20 conduit at the contractor's discretion. 1.8 For direct buried installations, DB -60 conduit may be used for all sizes smaller than 4". DB -100 conduit is required when 4", 5" or 6" conduit is installed. REV. 4-8-91 Completely Revised APPROVED BY: I UNDERGROUND STRUCTURES . CONDUITS AND FITTINGS u6s. 1 1 0 1.1 drAF Souther California Edison SCOPE TYPICAL CONDUIT AND RISER BEND INSTALLATION FOR HANDHOLE THROUGH SERVICE TO STREETLIGHT STANDARDS I � Precast Concrete (D Concrete Footing 11 ' je� or Plastic Handhole CL Aj 0" " C} Conventional Underground 324(Curb Conduit or CIC State Highway 15" (Sidewalk) =30" Squarer - Requirement T p I Face of Curb or Inside Edge of Sidewalk (Property Side) PLAN Light1 j I Flow Line Standard I I I r- Finish Grade / of Gutter A. I -5' (MIN) 45" (MIN) ISI 30 (MIN) Commercial I Below Gutter Grade or Residential I for Conventional for CIC i I Conduit Underground- Conduit Riser Bends ELEVATION. CIC NOTES: 1. Handhole loop through service is used when a 2" or larger conduit is required: 2. Typical locaton. for streetlight standard: a. With parkway - place behind inside edge of curb. b. Without parkway - place behind inside edge of sidewalk when curb and sidewalk do not exceed 51/z' in width, or per local inspection agency. 3. A semi-rigid or rigid conduit bend DB THICKNESS MINIMUM shall be used when a conventional conduit system is installed. See working drawing for size and material. 4. No encasement required unless otherwise specified. 5. In a rigid conduit installation,. short.lengths of properly coupled conduit maybe used to form sweeps of a radius not normally supplied by manufacturers. In trench runs, the maximum deflection allowed shall be 1/2' for lengths 2' or shorter, and 1" for lengths over 2'. 6. For riser bends, the minimum radius permitted shall be 24"; for horizontal bends,. a minimum radius of 36". 7. A pull rope shall be installed in each empty.conduit. 8. Five-foot clearance to be maintained from fire hydrant. 9. Four -foot clearance to be maintained from top of slope of commercial driveway and 2' clearance from residential driveway. 10. On state highway, the streetlight centerline location shall be 6" behind sidewalk when sidewalk is less than 7' wide. 1137See t7G�'$9a �1 4 or o n a ion;de ills. .k-.-....-- - :.�._.: -..a.. - - Indicates Latest Revision Changed REV. 7-26-94 Note #11 _3_ UNDERGROUND STRUCTURES A9PpOVEO BY 175,2 UG� AND RISER BENDTINSOTALlATION HANDHOiLE RE10WRE1r1ENTS The following tabulation snows the size and type of various handholes, manufacturers' names and an arbitrarily assigned item number. This item number will be the identification used when listed on the "List of Materials" on the working drawing. Concrete Item Na. Nominal Size Inside ( )Concrete Manufacturers' Numbers Brooks Products :`.. ;._:.:.:.. Christy `- Brooks Prod. Products inc. J&R Concrete Prod. HH -1' 10 1/2 X 17" X 12" {N091�T '= "=�- PB -31/2 JR -31'2 6 HH -2' 1 Ch/2" X 17" X 24" ' N09RT72WX - PB -31/2 E JR -31/2 BC HH -3 3a" X 12"-N36RT72:�;"-;-�:' PB -66 JR 6A HH -4 E7" 30" x 24" Na6FiT72WX.*. PB -66 E JR -6 AS ' Limited to street light only Non -Concrete (Polymer Concrete; Fiberglass Reinforced Plastic, Reinforced Plastic Mortar, Plastic) Item No. Normal Size Amorcast (Inside) Products Associated Plastics Brooks Products Carson Ind. CDR Systems Quazite Corp' HH -5 12" X 24" X 15" 600-1946A 1324-3 13BBX1516G 1324-12L 3460AE PX -1324 -BC HH -6 17" X 30" X 15- 600-1640A 1730 15-1. 17ABX1816G 1730-12L 3465AE. PX -1730 -BC HH -7 17" X 30" X 30" -- 1730115-4 17ABX3016G 1730E.12L -- PX -1730 -BCF ' Quazite Corporation (formerly Power and Communication Systems Company - PBC). NOTES: 1. See UGS 205 for typical Installation. 2_ Handholes are for nontraffic installation only. (Exception: Arrnorcast Products 600-1946A and 130&- 1640A, CDR Systems 3460AE and 3465AE. and Quazite Corporation PX-1730BC may be used in residential driveways and other areas with similar loads.) 3. Slight variations may occur between manufacturer's products. Southern California Edison UNDERGROUND STRUCTURES REV. 12-88 0 Indicates Latest Revision Removed Associated - Added Christy UGS 1 2001 p O o DIAL TWO WORKING BEFORE DAYS YOU DIG Y❑UBDI ORE TOLL FREE - -F 1 800 227-2600 A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT REV. REVISION DESCRIPTION DATE ENGR. CITY DATE SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER, THE CITY ENGINEER MAY REQUIRE REVISIONS TO THE PLANS TO BRING THEM INTO CONFORMANCE WITH CONDITIONS AND STANDARDS IN EFFECT. OFESS� oQR �. °"q� ��, �oNo q� Q- ?� �' Z 0 No. 36052 m w m � Exp. � sf C I V I �- ��� T � OF CAL�FC R �' -__ ._: Prepared By: ? :J ,-.� ALLARD ENGINEERING z.� Civil Engineering Land S Land Planning F` r g - Surveying - g ;:._ _ _ 8253 Sierra Avenue __ - �� Fontana, California 92335 (909) 356-1815 Fax (909) 356-1795 ' ( , p Z and . Allard, A.C.E. 36052 Date (expires 6/30/2004) CITY OF FONTANA, CALIFORNIA BASELINE . AVENUE DRAWN BY. MAG STREET LIGHT D TAILS SCALE: 1"=100' DESIGNED BY DBW DATE: AUGUST, 2002 CHECKED BY: RJA AP BY: tar - zs / -Q2 CI ENGINEER R.C.E. 51152 DATE: DRAWING NO.: 3063-Ltg. 2 2 Filename: M:\DWG\14902\EXHIBIT\ST-LIGHT-2.DWG