HomeMy WebLinkAbout4919-1SEWER GENERAL NOTES
1 ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD PLANS,
THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS
CONSTRUCTION ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE
LATEST EDITION UNLESS OTHERWISE NOTED.
2 WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CAN NOT BE
RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK", THE CONTRACTOR
SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEER FOR RESOLUTION.
3 ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER.
4 CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY
DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK.
INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE
START OF ANY WORK IN PUBLIC RIGHT-OF-WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610.
5 THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND
PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST
NON -METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER.
6 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS
OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES.
7 THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR
TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF INDUSTRIAL
SAFETY.
8 THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH SHALL BE
GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS PURSUANT TO THE
REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES
LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND
MOVEMENT.
9 NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY WITHOUT
OBTAINING A SEPARATE PERMIT FOR THAT PURPOSE.
10 THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION,
HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE, IN THE FIELD,
THE TRUE LOCATION AND ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER
PRECAUTION TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT AT 1800-227-2600 TWO WORKING DAYS BEFORE EXCAVATION.
11 THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING,
BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE
IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND
CALTRANS. ALL UTILITY COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK
AROUND THEIR FACILITIES.
12 THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT
APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE
WATER COMPANY FOR VALVE OPERATION AND WATER REQUIREMENTS.
13 STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE NOTED.
14 ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE THE
CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING
DURING CONSTRUCTION.
15 THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH
MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER.
16 REMOVAL AND REPLACEMENT OF EXISTING SURVEYCONTROL, INCLUDING SURVEY MONUMENTS,
MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED CIVIL ENGINEER OR
LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS
CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE WEEK
PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER
REPLACEMENT OF THE MONUMENT.
17 THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL TIMES.
A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION AREA FOR
RESIDENTS AND EMERGENCY VEHICLES.
18 THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL,
INCLUDING ADEQUATE WATERING, AT ALL TIMES.
19 THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE
DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING
CONSTRUCTION WITHOUT PRIOR WRITTEN APPROVAL.
20 NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR.
21 A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE TO OBTAIN THE
REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT PORTION OF THE WORK UNTIL THE
SPECIFIED DENSITY IS OBTAINED.
22 CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING STREET
IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE TEMPORARY
NON-ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS.
23 ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH
EXISTING CONCRETE.
24 IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A TERMINAL
CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE DOWNSTREAM MANHOLE,
SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT.
25 SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE
VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS OF
THE ASTM DESIGNATION C700 FOR V.C.P.
26 NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL OF THE
CITY ENGINEER.
BENCHMARK
Elevations as shown hereon
are in terms of the National
Geodetic Vertical Datum of
1929 based locally upon the
following City of Fontana
Bench marks:
#264 ELEV=1321.020'
BASIS OF BEARING.
Bearings and coordinates as shown hereon are in terms of the
California Coordinate System of 1983 (Epoch 2007.00), Zone
5; based locally upon the following Continuously Operating
Reference Stations as published by the NGS:
Name Northing (ft)Easting (ft) Ellipse Hgt.
(ft)Accuracy
EWPP 1860639.42 6705287.17 1084.17
RTHS 1855454.16 6757466.08 1078.27
IN THE CITY OF FONTANA, COUNTY OF SAN BERNARDINO, STATE OF CALIFORNIA
SEWER IMPROVEMENT PLANS
FOR
SIERRA AVENUE
LOCATED WITHIN THE NE % OF THE SE 4 OF SECTION 6, TOWNSHIP 1 SOUTH, RANGE 5 EAST
OF THE.SAN BERNARDINO BASE AND MERIDIAN
MIL
�R
AVENUE
1
11
Li w
D
w
TANGENT
¢ ¢
FAIRFAX
N 89043'45" E
< <
Uj
I
Li_
1
1
MALAGA ST
T SITE
j
REED STREET
REED STREET
VICINITY MAIC
NOT TO SCALE
THE THOMAS GUIDE 2007
SAN BERNARDINO COUNTY, PAGE 574,
COORDINATE J-7
SEWER GENERAL NOTES CONT,:
27 SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE WALLS TO
ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT.
28 PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND VERIFY
ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS TO EXISTING
FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCATIONS SHOWN ON THE PLANS.
29 ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS OTHERWISE
APPROVED BY THE CITY ENGINEER.
30 TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12" BELOW THE
GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE STREET RIGHT OF WAY,
THE LATERAL SHALL TERMINATE 3 FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY
EASEMENT.
31 THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE LOCATION OF
THE SEWER LATERAL.
32 IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED IMPROVEMENTS,
THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY.
33 NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN PLACED,
INSPECTED AND APPROVED.
34 ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING OF
STREETS.
35 APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT PRIOR TO
PLACEMENT.
36 ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED TO FINISHED
GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING.
37 UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING,
BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION OF THE CITY TRAFFIC
ENGINEER.
38 AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF RECORD, WHO
SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER.
REV.
REVISION DESCRIPTION
DATE I ENGR. I CITY I DATE
UTILITY CONTACTS
ELECTRICITY
SOUTHERN CALIFORNIA EDISON CO.
300 N, PEPPER AVE.
RIAL TO, CA 92376
UNDERGROUND: (909) 357-6233
TRANSMISSIONS: (909) 875-5100
PIPELINES: (213) 657--1233
DISTRIBUTION: (909) 357-6233
GAS
SOUTHERN CALIFORNIA GAS CO.
1981 L UGONIA A VE
REDLANDS, CA. 92374
A TTN: JOHN OA TES
EMERGENCIES: (800) 427-2200
WATER
WEST SAN BERNARDINO COUNTY
WATER DISTRICT
855 WEST BASELINE, P.O. BOX 920
RIALTO, CALIFORNIA 92377-0920
(909) 875-1804
PACIFIC BELL
4025 LA PALMA STREET
ANAHEIM, CA. 92807
(714) 237-6146
A TTN: DELIA LERMA
SEWER
CITY OF FONTANA
8353 SIERRA AVENUE
P. 0. BOX 518
FONTANA, CA 92335
(909) 350-6632
COMCAST CABLEVISION
1205 DUPONT AVE
ONTARIO, CA 91761
(909) 3904738
CONTACT JACK HA YES
CONSTRUCTION NOTES
O INSTALL 8" VCP EXTRA STRENGTH SEWER PER CITY OF
FONTANA STANDARDS AND SPECIFICATIONS.
O INSTALL STANDARD CAST IN PLACE MANHOLE FOR
SEWER PER CITY OF FONTANA STANDARD N0. 2001.
O INSTALL 6" SEWER CLEANOUT PER CITY OF FONTANA
STANDARD N0. 2005.
O INSTALL CONCRETE BACKFILL SLURRY TO LIMITS
SHOWN.
LINE/CURVE DATA
TABLE
1
11
RADIUS
LENGTH
TANGENT
1
N 89043'45" E
I
--
1
1
1
j
I
PROFILE_ SCALE:
HORIZ: 1" = 40'
VERT: 1 " = 4'
I
F-7
7_1
F
1
1
1
—1—i7
1
1
_17
jI
I
�
� i
I
I
I
1
FF
1355
I
I
�
,
I�
1355
IW
_FF]
0
_ —
I _
_ :—I
— _._
R
_
o
LO
--I'-
_W) -
PRO'. 1S OVER P1 1 'L E X I PIPE
--
�•III
FS-
---_
.
—TT
ItiI
77ROP. CURB 7_11-17 -r;
- -T
—_>Z�
_5�20'1' ACIP WATER 12" CIP WATER
L 34-
I F
1---
P --- --O---_VEIi
16" WATER WITH 30" ENCASEMENT 4STEEL GAS
----R
--
—j_Lrtea
,I
0Lf
+SIiI
°1 1 1 0 00.00
,- L - - -
- o z j133'9.93 INV!. OUTIS� Y
---
co �o I
bi
� J �nN0 W1
(n o
-ji� Z N �� 133 5
0 rn
-- _
3_-�-o6
. . .—.-----I_V_CP_EXTRA;T_RENGT__-S
SEWER
I
I
;
CONSTRUCTION NOTES
O INSTALL 8" VCP EXTRA STRENGTH SEWER PER CITY OF
FONTANA STANDARDS AND SPECIFICATIONS.
O INSTALL STANDARD CAST IN PLACE MANHOLE FOR
SEWER PER CITY OF FONTANA STANDARD N0. 2001.
O INSTALL 6" SEWER CLEANOUT PER CITY OF FONTANA
STANDARD N0. 2005.
O INSTALL CONCRETE BACKFILL SLURRY TO LIMITS
SHOWN.
LINE/CURVE DATA
TABLE
BEARING/DELTA
RADIUS
LENGTH
TANGENT
1
N 89043'45" E
81.36'
--
SHOULD CONSTRUCTION OF THE REQUIRED
IMPROVEMENTS NOT COMMENCE WITHIN TWO
YEARS OF THE DATE OF APPROVAL SHOWN
HEREON AND CARRIED FORTH IN A
DILIGENT MANNER, THE CITY ENGINEER
MAY REQUIRE REVISIONS TO THE PLANS
TO BRING THEM INTO CONFORMANCE WITH
CONDITIONS AND STANDARDS IN EFFECT.
Q�pF ESS1��
S • S �l �r►
�� A
A0 s
�;
No. 57667
9jF CIVI�-
�F C
■ � r
CONSULTING
PREPARED 14NDER i
0
r -
w
J
Q
U
PLANNING r DMSIE3N r mnNsTkur,' ION
74-130 COUNTRY CLUB DRIVE, SUITE 201
PALM DESERT, CALIFORNIA 92260-4114
760.346.7481 • FAX 760.346.8315 ■ w".RBF.com DRAWN BY:
DSW
E SUPERVISION OF: DESIGNED BY:
MICHAEL S. SUTTON, RCE 57667
10
0-
w
U Q
N
U 0
D ¢ o
(-n c~n 0 0,^
_j Xw • W
• T --
_j w T.-
Y (j BOO
m w x ¢¢W
w 1 cnV)a-
S S S 2
J
w 1 w
Z
a V) ¢
Li
°o w
� w
.0 0
� o
3, oTo--
C.D
-
o �
0 o
Cn 0-
>< w w
En
00
w
DR N0.09-010 R1
CITY OF FONTANA, CALIFORNIA
SEWER IMPROVEMENTS
DSW AP 0
.12-101r-11 CHECKED BY. XzIld
DATE: MSS/DSW T -1-1w r
SIERRA AVENUE
MENOM
SCALE:
AS SHOWN
JOB NUMBER
20-101268
DRAWING N0.
4919 q
0-
0
N
r --
m
N
a
0
0
00
/
I�i_I
LU
C/)
>
0
>
0
d
0
00
U
/
O
0
d
Q
0-
/