ELECTRICAL NOTES AND 5PEG I P I CAT I ONS
GENERAL
I. CONTRACTOR SHALL PERFORM ALL WORK AS TO CONFORM TO LOCAL,
STATE AND NATIONAL GODE5 AND THE REQUIREMENTS OF LOCAL
AUTHORITIES HAVIN6 JURI5DIGTION.
2. CONTRACTOR TO EXAMINE THE 51TE TO DETERMINE THE EXACT
CONDITIONS EFFEGTIN6 THE ELECTRICAL WORK.
3. DRAWINGS INDICATE THE 6ENERAL SCHEME OF THE INSTALLATION AND ARE
DIA6RAMMATIG IN 5GOPE. THE ENGINEER RESERVES THE RIGHT TO GHAN6E THE
LOCATION OF OUTLETS, CONDUIT, EQUIPMENT, APPARATUS, ETC. TO A
REA50RABI F EXTENT A5 THE CONDITIONS MAY DICTATE PRIOR TO THEIR
INSTALLATION WITHOUT EXTRA G05T TO THE OWNER. THE EXACT LOCATION AND
ARRAN6EMENT OF ALL EQUIPMENT AND PARTS SHALL BE DETERMINED AS THE
WORK PR06RE55E5.
4. DETAILS OF CONSTRUCTION AND OF WORKMAN5HIP WHERE NOT
SPECIFICALLY DE5GRIBED HEREIN OR INDICATED ON THE PRMIN65
SHALL BE SUBJECT TO THE ENGINEER'S APPROVAL. IT 15 THE INTENT
OF THESE SPECIFICATIONS TO PROVIDE COMPLETE SYSTEMS, LEFT IN
6000 WORKING ORDER, READY FOR OPERATION.
5. SCRAP AND DEBRIS, EXCEPT A5 OTHERWISE SPECIFIED, SHALL BE
REMOVED FROM THE 51TE AND DISPOSED OF BY THI5 CONTRACTOR.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR 5TART-UP OF ALL
SYSTEMS.
1. ALL WORK SHALL BE DONE WITH A MINIMUM OF DUST AND DIRT.
PROVIDE SUFFICIENT FIREPROOF TARPAULINS AND COVER ALL
EQUIPMENT IN WORK AREA WITH SAME DURING WORK OPERATIONS.
8. CONTRAGTOR SHALL FURNISH SHOP DRANIN65 AND EQUIPMENT GUTS TO
THE ARGHITEGT FOR APPROVAL (MINIMUM (5) COPIES).
q. COORDINATE CONNEGTION5 TO METERING PEDESTALS WITH LOCAL UTILITY
GOMPANY(5).
10. CONTRACTOR SHALL FILE, SECURE AND PAY FOR ANY NEGE55ARY
APPROVALS, PERMITS AND INSPECTIONS.
II. ALL WORK SHALL BE GUARANTEED TO BE FREE FROM DEFECT FOR ONE
YEAR AFTER ACCEPTANCE OF WORK.
12. ALL WORK BE IN 5TRIGT CONFORMANCE WITH THE STATE OF CALIFORNIA
BUILDING CODE AND THE STATE OF CALIFORNIA E1 EGTRIGAL CODE.
13. PRIOR TO TE5TIN6, CONTRACTOR SHALL MAKE ALL 5Y5TEM ADJU5TMENT5
REQUIRED FOR PROPER OPERATION. ADJU5TMENT5 SHALL INCLUDE
TRANSFORMER TAPS, CIRCUIT BREAKER MACNETIG 5ETTIN65, 6ROUND
FAULT RELAY TRIP 5ETTIN65, BALLAST TAP 5ETTIN65, ETC.
14. ALL El EGTRIGAL 5Y5TEM5 SHALL BE TESTED IN ACCORDANCE WITH THE
CALIFORNIA Fl ECTRIGAL CODE. CONTRACTOR TO COORDINATE TE5T5 WITH.
LOCAL AUTHORITY HAVIN6 JURISDICTION.
15. CONTRACTOR SHALL BE RESPONSIBLE FOR 015GONNEGTIN6 AND MAKING
SAFE ALL El EGTRIGAL FACILITIES IN AREAS OF EXCAVATION PRIOR TO
5TARTIN6 THE WORK.
Underground Service Alert
SECTION 4216/4217 OF THE GOVERNMENT
ORE roG CODE REQUIRES A DIG ALERT IDENTIFICATION
o NUMBER BE ISSUED BEFORE A PERMIT TO
EXCAVATE WILL BE VALID
1�1�I FOR YOUR DIG ALERT I_D_ NUMBER CALL
UNDERGROUND SERVICE ALERT
TOLL FREE 1-800-227-2600
TWO WORKING DAYS BEFORE YOU DIG
fi{
104+00
1
SITE SERVICES
I. ALL UNDER6ROUND RAGEWAY5, SHALL BE TYPE DB, 5GHEDULE 40 PVG,
RIC71D NON-METALLIC CONDUIT, AD MANUFACTURED BY GARLON OR
APPROVED EQUAL AND SHALL BE INSTALLED IN AGGORDANGE WITH GEG
ARTICLE #341.
3. NON-METALLIG RIC71D CONDUIT SHALL BE MANUFACTURED IN STRICT
CONFORMANCE WITH UL #651 AND NEMA #TG -2.
4. FITTINC75 FOR RIC71D NON-METALLIG CONDUIT SHALL BE OF THE
SOLVENT CEMENTED TYPE AND SHALL BE MANUFACTURED IN 5TRIGT
CONFORMANCE WITH UL 3514 AND NEMA #TG -3. SOLVENT GEMENT
PROCEDURES SHALL BE IN AGGORDANGE WITH THE MANUFACTURERS
RECOMMENDATIONS.
5. WHEREVER POSSIBLE, RIC710 NON-METAH IG CONDUIT ELBOW5, OFFSETS,
ETC. SHALL BE MADE U51N6 30 DE6REE, 45 DE6REE AND q0 DE6REE
FACTORY ELBOW5. WHERE FACTORY ELBON5 CANNOT BE AGGOMMODATED,
FIELD BENDING 5HALL USE HEATING BOXES, END PLU65 AND FORMIN6
6UIDE5 A5 REGOMMENDED BY THE MANUFACTURER. CASE SHALL BE
EXERG15ED TO ENSURE THAT THE INTERNAL DIAMETER OF
GONDUIT5 15 NOT EFFECTIVELY REDUCED BY FIELD BENDIN6.
6. MINIMUM BENDING RADIUS FOR R161D NON-METALLIG CONDUIT SHALL
NOT BE LE55 THAN PERMITTED BY GEG #346-10.
1. MINIMUM BURIAL DEPTH FOR UNDERGROUND RIGID NON-METALLIG
RAGEWAY SHALL BE 2'-6" BELOW FIN15HED 6RADE. WHERE LE55ER
DEPTHS ARE REQUIRED CUE TO 5UB5URFAGE ROCK, ENCASE RAGEWAY5
IN MINIMUM 3", 3000 P51 CONCRETE ENVELOPE.
8. ALL PENETRATIONS THROU6H MANHOLES, HANDHOLE5, FOUNDATIONS,
ETC. SHALL BE MADE U51N6 HOT -DIPPED 6ALVANIZED, RIGID STEEL
(6R5) CONDUIT. MAKE TRANSITION FROM RI610 NON-METALLIC, TO
6R5 AT 5-0" FROM PENETRATION U51N6 APPROVED TRANSITION
GOUPLIN6. PROVIDE 3" CONCRETE ENVELOPE AROUND TRAN51TION
GOUPLIN6 EXTENDING 5-O" IN EITHER DIRECTION TO MINIMIZE SHEAR
FORGES AT TRANSITION GOUPLIN6.
q. WHERE THE SERVICES ARE TO BE OF THE SECONDARY TYPE SUPPLIED
FROM EXISTING LOW VOLTA6E DISTRIBUTION OR POLE MOUNTED POWER
COMPANY TRANSFORMERS, CONTRACTOR SHALL FURNI5H AND INSTALL
5ERVIGE GONDUGTOR5 517ED A5 INDICATED ON THE DRAWIN65, FROM
THE METERIN6 PEDESTAL TO THE RISER POLE. PROVIDE ADEQUATE GABLE
SLACK, COILED AT TOP OF R15ER CONDUIT FOR FINAL GONNEGTION5 BY
THE POWER COMPANY.
10. GOORDINATE R15ER POLE LOCATIONS AND THE LOCATION OF R15ER
GONDUIT5 OF THE POLE (QUADRANT) WITH THE POWER COMPANY.
RACEWAis
1. UNLE55 OTHERN15E NOTED, RAGENAY TYPES SHALL BE A5 INDICATED
BELON:
LOCATION RAGENAY
UNDER6ROUND TYPE "DB", SCHEDULE 40 RI61D
(PVG), NON METALLIC CONDUIT
FOOTHILL BLVD
LANDSCAPE MEDIAN
FROM CHERRY AVENUE
TO HEMLOCK AVENUE
Robert J. Hatch, P.E.
CA # E16118
QRpF ESS
J.
c� 1 8 rn
sj9TF� CTR p
OF CALF
EXP. 12/31 /11
105+00
1
CONDUCTORS
I. UNLE55 OTHERWISE NOTED, GONDUGTOR TYPES SHALL BE AS INDICATED
BELOW:
LOCATION CONDUGTOR5
A. UNDERGROUND OUTDOORS RHW/THW/THWN
B. UNDER6ROUND SERVICE FEDER5 RHW/U5E
G. FIXTURE CONNECTIONS 5F-2
2. ALL WIRE AND GABLE SHALL BE COPPER GONDUGTOR5. CONDUCTORS
#IOAN6 AND SMALLER MAY BE SOLID. CONDUCTORS LAR6ER THAN
#IOANG SHALL BE STRANDED.
3. CONDUCTORS #8AW6 AND SMALLER MAY BE SPLICED U51N6 NYLON 5E1 F-
IN5ULATED WIRE NUT5 AS MANUFACTURED BY 3M "5GOTHLOK", IDEAL
"WIRE -NUT" OR APPROVED EQUAL.
4. GONDUCTOR5 LAR6ER THAN #8AW6 SHALL BE SPLICED U51N6 SPLIT BOLT
CONNECTORS WITH TAPED JAGKET, PREMANUFAGTURED SPLICES BY IL5G0
OR MAG PRODUCTS OR BY HYDRAULICALLY APPLIED GOMPRE55ION
SPLICES. MANUFAGTURERS TOOLING, DYES AND RECOMMENDATIONS
SHALL GOVERN HYDRAULICALLY APPLIED GOMPRE55ION SPLICES.
5. EXCEPT WHERE EQUIPMENT, SUCH A5 MOLDED CASE CIRCUIT BREAKERS
ARE SUPPLIED WITH FACTORY INSTALLED SET 5GREW LU65, ALL
CONNECTIONS FOR GABLES 4/0 AND LAR6ER SHALL BE MADE U51N6 NEMA
2 BOLT COMPRESSION LU65. LU65 SHALL BE HYDRAULICALLY APPLIED
U51N6 MANUFAGTURER'5 TOOLING, DIE5 AND RECOMMENDED PROCEDURES.
6. CONDUCTOR IN5ULATION5 SHALL BE COLOR CODED AS FOLLOW5:
120/208V
PHASE A BLUE
PHASE B RED
PHA5E G BLACK
NEUTRAL WHITE
6ROUND GREEN
WHERE GONDUGTOR5 ARE NOT AVAILABLE WITH COLOR CODED
INSULATION, APPLY COLORED TAPES TO THE ENTIRE EXPOSED LENGTH
OF GABLES IN PULL BOXES, SWITGHBOARD5, EQUIPMENT, ETC.
CITY OF FONTANA
CALIFORNIA, 92335
106+00
106+00
1
GROUNDING
I. SERVICE ENTRANCE GROUNDING ELECTRODES SHALL INCLUDE THE
FOLLOWING:
A. REINFORGIN6 BARS IN FOOTIN65.
B. AT LEAST TWO 3/4" X 10' GOPPERWELD 6ROUND ROD DRIVEN
OUTSIDE BUILDING A5 NEAR TO METER PEDE5TAL5 A5 P0551BI E.
2. 6ROUNDIN6 ELECTRODE GONDUGTOR5 5HALL BE 51ZEP IN ACCORDANCE
WITH GEG TABLE #250-q4 AND NEC 3250-1q(D).
3. ALL 6ROUNDIN6 CONNECTIONS TO REINFORGIN6 BARS AND 6ROUND ROD5
AND ALL UNDER6ROUND 6ROUNDIN6 GABLE SPLICES SHALL BE
EXOTHERMIC NELDS BY GADNELD OR APPROVED EQUAL.
4. THE FOLLOWING COMPONENTS SHALL BE BONDED WITH A BARE COPPER
CONDUCTOR 51ZED IN ACCORDANCE WITH GEG TABLE #250-q4.
A. SERVICE RAGEWAY5.
B. METER ENGLOSURE5.
G. SERVICE DISCONNECT.
D. 6ROUNDIN6 ELEGTRODE5.
SERVICE RAGEWAY5 SHALL BE BONDED BY USE OF 6ROUNDIN6 BU5HIN65
AT ALL TERMINATIONS UP TO AND INGLUDIN6 THE SUPPLY 51DE OF
SERVICE D15GONNEGT(5).
5. THE FOLLOWING ITEMS SHALL BE BONDED TO THE SERVICE EQUIPMENT
6ROUND BU5 U51N6 GABLE5 51ZED IN ACCORDANCE WITH GEG TABLE
#250-q4:
A. METERING PEDESTAL FRAME.
O
3 #S &
#8 GROUND
O
3 #10 &
#10 GROUND
O
3 #6 8
#6 GROUND
LINWOOD ENGINEERING
ASSOCIATES, P.C.
Consulting Mechanical & Electrical Engineers
210 Main Street
151 Kalmus Drive Suite B-200
New Milford, New Jersey
Costa Mesa, California
07646
92626
t: 201.261.5398
t: 714.424.0001
f: 201.261.7652
f: 714.424.0004
www.linwoodengineering.com
l 7+n
107+00
1
1110-151-28
CAIARENA JR SANTOS
FOOTHILL BLVD. (WESTBOUND)
FOOTHILL BLVD.
(EASTBOUND)
LIGHTING
1. COORDINATE FIXTURE LOCATIONS WITH IN5TALLED LAND5GAPIN6
AND MONUMENT FEATURES.
2. ALL BALLASTS FOR REGE55ED HID FIXTURE5 SHALL BE UL L15TED AND
SHALL BE THERMALLY PROTECTED.
3. PROTECT ALL LAMPS, LEN5E5 AND LOUVERS DURING CONSTRUCTION. ALL
LAMPS, FIXTURE HOU51N6, LEN5E5 AND LOUVERS SHALL BE GLEANED
UPON COMPLETION OF WORK BY ALL TRADES. REPLACE DEFECTIVE OR
DAMA6ED LAMPS, LENSES, LOUVERS AND BALLA5T5 AS REQUIRED AT THE
TIME OF GLEANING.
4. BALLA5T5 FOR HID FIXTURES SHALL BE POWER FACTOR CORRECTED.
PANELBOARD5 AND CIRCUIT BREAKERS
I. EQUIPMENT INTERRUPTING RATIN65 5HOWN ON 5GHEDULE5 ARE BASED
ON UL L15TED SERIES RATING FOR 50,000A AVAILABLE SHORT CIRCUIT
CURRENT AT THE SERVICE. CONTRACTOR SHALL INCREASE
INTERRUPTING RATIN65 A5 REQUIRED FOR NON-5ERIE5 RATED
EQUIPMENT.
2. PANELBOARD5 SHALL BE OF DEAD FRONT GON5TRUGTION WITH AUTOMATIC,
OVERCURRENT DEVICES. VOLTA6E AND CURRENT RATIN65 AS 5HONN.
GIRGUIT BREAKERS SHALL BE BOLT -ON TYPE UNLE55 OTHERN15E
NOTED. PANELBOARD5 SHALL BE UL LISTED AS MANUFACTURED BY
SQUARE D, 6E OR WE5TIN6HOU5E.
L%CT EANK ICY TA65-
1� [fl : REFER TO DUGTBANK SECTIONS
❑MB
L-
a
r
m
103+00
=-MAW
108+00
N
O R T H
CITY OF FONTANA
PARTIAL SITE ELECTRICAL PLAN
DRAWN BY: FOOTHILL BOULEVARD
RJH
DESIGNED BY. FROM CHERRY AVENUE
RJH TO HEMLOCK AVENUE
CHECKED BY:
REV REVISION DESCRIPTION DATE CITY DATE SG
CITY DRAWING FILE NO.
4883
SCALE:
1°=20'
DATE:
01-17-11
DRAWING NO_: 33
E-3 38