Loading...
HomeMy WebLinkAbout4854E-8CERTIFICATE OF COMPLIANCE (Page 1 of 4) OLTG-1C Project Name Date FONTANA CAMPUS PARKING LOT 02/03/10 Project Address Total Illuminated Area FONTANA, CA 331779 General Information Phase of Construction: ❑ New Construction ❑ Addition 56 Alternation Documentation Author's Declaration Statement • 1 certify that this Certificate of Compliance documentation is accurate and complete. Name Signature MICHAEL REED A Company Unto REEDCORP ENGINEERING XXXXXXXXX Address EA# 2061 BUSINESS CENTER DRIVE, SUITE 110 CEP# City/State/Zip Phone: IRVINE, CA 92612 949/752-1278 Principal Lighting Designer's Declaration Statement • I am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design. • This Certificate of Compliance identifies the lighting features and performance specifications required for all outdoor lighting design. Title 24, Pages 1 and 6 of the California Code of Regulations. • The design features represented on this Certificate of Compliance are consistent with the infomation provided to document this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. Name Signature THOMAS E. HARTMAN Field Inspector 2 Company Phone: REEDCORP ENGINEERING 949/752-1278 Address License # 2061 BUSINESS CENTER DRIVE, SUITE 110 7531 City/Statef'Zip Date IRVINE, CA 92612 XXXXXXXXX Principal Lighting Designer's Declaration ❑ i certify that this Certificate of Compliance documentation is accurate and complete, and accounts for all outdoor lighting power, including building mounted, pole mounted, as well as all other outdoor lighting designed for the site, and that Additional Lighting Power Allowances for Specific Applications or Additional Lighting Power Allowances for Ordinance Requirements have not been counted more than one time for the same area, in accordance with Section 147 of the Standards. LIGHTING COMPLIANCE FORMS R. WORKSHEETS (check box if worksheet is included) For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the ir'onresidential Manual published by the California Energy Commission. oil OLTG-1C Certificate of Compliance. All 4 pages required on plans for all submittals 5� OLTG-2C (Page I of 3) Lighting Wattage Allowances for Per Application or per Area. Optional on plans. Lighting Optional Plans. fi� OLTG-2C (Page 2 of 3) Lighting Wattage Allowances for Per Application or per Area. Optional on plans. ❑ OLTG-2C (Page 3 of 3) Additional Lighting Power Allowance for Ordinance Requirements. Optional on plans. 2008 Nonresidential Compliance Forms December 2008 CERTIFICATE OF COMPLIANCE (Page 2 of 4) OLTG-1C COMPLIANCE FIXTURE / LIGHTING CONTROL SCHEDULE and FIELD INSPECTION CHECKLIST Project Namc FONTANA CAMPUS PARKING LOT Date 1 02/03/10 Function Type ❑ Function Type ❑ Indoor Signs INSTALLATION CERTIFICATE, OLTG-I-INST (Retain a copy and verify form is complete and signed) Project Address Field InsIxMion ❑ CERTIFICATE OF ACCEPTANCE, OLTG-2A (Retain a copy and verify form is complete and signed',Field ❑ Maximum Allowed Lightiag Power ❑ Alternate Lighting Sources Repletion ❑ Luminaire Schedule Installed Watts Principal Lighting Designer's Declaration Statement • i am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design. A B C D E F G H I Name or Item Tag Luminaire Description See footnote below (ic: lamp pole - to shoe box 400 watt metal halide) v a 'g % a a � '= f I low Wattage wax determined g �i=_ 7__J a sy Field Inspector 2 x z.n o Ute= b�, u � � < 2 IRVINE, CA 92612 • A POST—TOP 10' POLE 150 WATT CUT OFF 196 ❑ ❑ 56 33 6468 ❑ ❑ B POST—TOP 250 WATT CUT OFF 296 ❑ ❑ M 15 4440 ❑ ❑ BB POST—TOP 2 HEAD POLE 250 WATT CUT OFF 592 ❑ ❑ 1A 1710064 Luminaire Type El El [Exception to § 133(a)4. The EMC is required by a health or life safety statute, ordinance, or regulation, including limited Y N N/A ❑ but not to exit signs and traffic signs. ❑ I ❑ Nf ❑ ❑ Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length: x ❑ ❑ ❑ WATTAGE ALLOWANCE ❑ ❑ ❑ Total Sign Are: A Also enter Total Sign Area above C J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc. 2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary. The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above) F 1 I High pressure sodium lamps H 2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient J Enter total into OLTG-1: Page 4 of 4; Row H, Total installed Watts: 20972 Wattage Allowance (B x C) EXEMPT LUMINAIRES I Field Inspection ❑ Luminaire Type Name or Symbol Description for exempt luminaires in accordance with §147 Watts per 7 Light emitting diodes (LEDs) with a power supply with > /o et iciency Allowed Watts Minimum of Dori 8 Single voltage LED external power supplies designed to convert 120 volt AC input into lower voltage DC or AC output, having a nameplate output power less titan or equal to 250 watts, and certified to the Energy Commission as complying with the applicable requirements of the Appliance Efficiency Regulations (Title 20) 9 Compact fluorescent lamps that do not contain a medium screw base sockets (E24/E26) 10 1 Electronic ballasts with a fundamental output frequency > 20 kHz MANDATORY CONTROLS FField Inspection ❑ Field Inspector Notes or Discrepancies # Description Location # Description Location ATS NORTH PARKING NEAR ATS SOUTH PARKING NEAR SPECIAL FEATURES INSPECTION CHECKLIST (See Page 2 Of ofOLTG-1C) Enter total into OLTG-I C; Page 4 0174; Row C; Specific Application Wattage Allowance for Ornamental Lighting: The local enforcement agency should pay special auenlion to the items specified in this checklist. These items require special written justification and doctuneruatiotr, and special verification. The local enforcement agency determines the adequacy of 1he justification and may reject a building or design that othenrise complies based vn Me adequac3, of the special justification and documentation submitted Field Inspector Notes or Discrepancies: 1 Tvpe of luminaire (i. e.: post top, wall pack, surface, shoe box): for non -incandescent hrntinaires, indicate nominal lamp trattage and lamp ri pe (ie.:,Jluoreseent, incandescent. HID). ballast t)pe (i.e.: electronic or magnetic): number of lumps and number of ballmis per luminaire. For incandescent luminaires, the luminaire watlage listed in column D shall be the marinmm relamping rated srallage on a permanent factory - installed label on the ltminaire, ,VDT the iratlage of the lamp (bidb) itsed in accordance with Section 130(d or e). IfI ail then describe on Page 2 of the hispection Checklist Form and take appropriate action to correct. Perp, building plaits if necessan� 2008 Nonresidential Compliance Forms CERTIFICATE OF COMPLIANCE (Sign Lighting) PAGE 1 OF 2 SLTG-1 C Project Name Phase of Construction ❑ Phase of Construction ❑ Addition 10 Alternation Date FONTANA CAMPUS PARKING LOT Function Type ❑ Function Type ❑ Indoor Signs ❑ Project Address Compliance Method Used 16- FONTANA, CA ❑ Maximum Allowed Lightiag Power ❑ Alternate Lighting Sources Documentation Author's Declaration Statement • I certify that this Certificate of Compliance documentation is accurate and complete. Name Signature §133(a)l. All signs with permanently connected lighting are controlled with an automatic time switch control MICHAEL REED ❑ TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE Company Date REEDCORP ENGINEERING xxxxxxx Address EA# 2061 BUSINESS CENTER DRIVE, SUiTE 110 CEP# Clt}'lStatC/Llp Phone:IRVINE, CA 92612 949/752-1278 Principal Lighting Designer's Declaration Statement • i am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design. • This Certificate of Compliance identifies the lighting features and performance specifications required for compliance with Title 24 , Pages 1 and 6 of the California Code of Regulations. • The design features represented on this Certificate of Compliance are consistent with the information provided to document this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. Name Signature THOMAS E. HARTMAN §133(a)3. All outdoor signs are controlled with a dimmer that provides the ability to automatically reduce Company Phone: REEDCORP ENGINEERING 949/752-1278 Address Liccnw # 2061 BUSINESS CENTER DRIVE, SUITE 110 7531 CitytStntcll_ip Datc IRVINE, CA 92612 xxxxxxx Mandatory Sign Lighting Controls Yes No Mandatory Sign Lighting Controls Yes No I §133(a)l. All signs with permanently connected lighting are controlled with an automatic time switch control 5( ❑ TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE that complies with the applicable requirements of § 119. 41206.81 Maximum Allowed Lighting Power Specific application lighting wattage allowance per unit length § 133(a)2. All outdoor signs are controlled with a photo control or outdoor astronomical time switch control. A ❑ B. ADDITION LIGHTING POWER ALLOWANCE FOR ORDINANCE REQUIREMENTS G Are additional lighting power allowances for ordinance in Table 147-C used? ❑ Yes No I 2 Exception to §(a)2. Outdoor sighs are in tunnels or large covered areas that require illumination during daylight hours. ❑ ❑ Design Wattsl §133(a)3. All outdoor signs are controlled with a dimmer that provides the ability to automatically reduce ❑ ❑ The following Acceptance Forms shall be submitted to the building department before an occurpanCy permit is grantedfor a newly constructed building or space. All control devices serving the building or space shall be certified as meeting at Acceptance Requirements for Code Compliance. List all equipment requiring testing, and indicated required acceptance documents. sign power by a minimum of 65 percent during nighttime hours. -C ! ¢ :=1 W. Luminaires Controlled OLTG-2A Exception I to § 133(a)3. Signs are illuminated for less than one hour per day during daylight hours. 56❑ Description 3 Exception 2 to § 133(a)3. Outdoor signs are in tunnels or large covered areas that require illumination during 1:1 ❑ ATS daylight hours. 1 NORTH PARKING ❑ Exception 3 to § 133(a)3. Only metal halide, high pressure sodium, cold cathode, or neon lamps are used to ❑ ❑ 1 illuminated signs or parts of signs. ❑ ❑ Nf Yes § 133(a)4. An Electronic Message Center (EMC) having a new connected lighting power load greater than 15 kW Y N N/A D has a control installed is capable of reducing the lighting power by a minimum of 30 percent when receiving a ❑ ❑ 5d 4 demand response signal that is sent out by the local utility. Name or Symbol Luminaire Type Luminaire Quantity Watts per Luminaire [Exception to § 133(a)4. The EMC is required by a health or life safety statute, ordinance, or regulation, including limited Y N N/A ❑ but not to exit signs and traffic signs. ❑ I ❑ Nf 2008 Nonresidential Compliance Forms December 2008 December 2008 CERTIFICATE OF COMPLIANCE (Page 3 of 4) OLTG-1 C Project Name FONTANA CAMPUS PARKING LOT Date 02/03/10 Project Name FONTANA CAMPUS PARKING LOT A. OUTDOOR LIGHTING ZONE Total Sign Area N/A OUTDOOR LIGHTING ZONE: ❑ OLZ 1 ❑ OLZ 2 56OLZ 3 ❑ OLZ 4 TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE Is the Outdoor Lighting Zonc4 Default in accordance with § 10-114 or ❑ Amended by JHA 41206.81 Maximum Allowed Lighting Power Specific application lighting wattage allowance per unit length Complete the information below if the default Outdoor Lighting Zone has been amended by the local jurisdiction having authority (JHA): ❑ The site is a government designated park, recreation area, wildlife preserve, or portion thereof, and has been designated as LZ2 or LZ3, in accordance with Table 10-114-A, because the site is contained within such a zone. ❑ The local jurisdiction having authority has officially adopted a change to the State Default Lighting Zone and has notified the Energy Commission by providing the materials required in § 10-114(d) to the Executive Director. ❑ The adopted change is posted on the Energy Commission website. A B B. ADDITION LIGHTING POWER ALLOWANCE FOR ORDINANCE REQUIREMENTS G Are additional lighting power allowances for ordinance in Table 147-C used? ❑ Yes No I J .o O U 0 E Complete the information below if additional lighting power allowances for ordinance requirements are used: ❑ The local jurisdiction having authority has officially adopted specific outdoor light levels, which are expressed as average or minimum footcandle levels, by following a public process that allowed for formal public notification, review, and comment about proposed change. ❑ The local jurisdiction having authority which adopted specific outdoor light levels and has notified the Commission by providing the following materials required in § 10-114(f) to the Executive Director. Allowed Watts Design Wattsl Complies ? Y/N C. ACCEPT FORMS Field Ins ector2 The following Acceptance Forms shall be submitted to the building department before an occurpanCy permit is grantedfor a newly constructed building or space. All control devices serving the building or space shall be certified as meeting at Acceptance Requirements for Code Compliance. List all equipment requiring testing, and indicated required acceptance documents. Certificate of Acceptance -C ! ¢ :=1 W. Luminaires Controlled OLTG-2A OLTG-3A Equipment Requiring Testing Description = E Z'5 U Location Outdoor Motion Sensors Controls Outdoor Lighting Shut-off Controls ATS TIME CLOCK 1 NORTH PARKING ❑ ❑ ATS TIME CLOCK 1 SOUTH PARKING ❑ ❑ Nf Yes ❑ No E wattage in row G ❑ D 3 ❑ ❑ ❑ E 3' SIGN W EXTERNAL 2 LAMPS Name or Symbol Luminaire Type Luminaire Quantity Watts per Luminaire Design Watts (G x H) Allowed Watts Minimum of Dori 3 ❑ ❑ ❑ ❑ O ❑ ❑ Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length: x C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING DETERMINE WATTAGE ALLOWANCE ❑ ❑ ❑ Total Sign Are: A Also enter Total Sign Area above C J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc. 2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary. The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above) F 1 I High pressure sodium lamps H 2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient J 3 Pulse start metal halide lamps that are > 320 watts, are not 250 watt or 175 watt lamps, and are served by a ballast with > 80% efficient Square feet of Hardsca 4 Neon or cold cathode lamps with transformer or power supply efficient > 75% with rated output current < 50 mA 2008 Nonresidential Compliance Forms CERTIFICATE OF COMPLIANCE (PAGE 2 OF 2) CHECK LIST SLTG-1C COMPLIANCE METHOD AND FIELD INSPECTION ENERGY CHECKLIST Date 02/03/10 Project Name FONTANA CAMPUS PARKING LOT Phase of Construction ❑ New Construction 10 Addition ❑ Alternation Function Tv �Outdoor5igns ❑Indoor Signs Total Sign Area N/A Date 02/03/10 TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE Compliance Method 41206.81 Maximum Allowed Lighting Power Specific application lighting wattage allowance per unit length E A B C D E F G H I J .o O U 0 E Description or location and plan location Allowed Watts Design Wattsl Complies ? Y/N Light Source Field Ins ector2 ^ 0 w = -C ! ¢ :=1 W. CA 'S7 Q it to O i— 3 v U w &n Li. m H W U. a. U. C INTERNAL LED SIGN 0 G Total allowed Wattage = Sum of rows A through F: 41206.81 H Total installed watts (from Compliance Fixture Schedule, 7 ❑ ❑ ❑ D 12' SIGN W EXTERNAL 4 LAMPS Nf Yes ❑ No E wattage in row G G H 3 ❑ ❑ ❑ E 3' SIGN W EXTERNAL 2 LAMPS Name or Symbol Luminaire Type Luminaire Quantity Watts per Luminaire Design Watts (G x H) Allowed Watts Minimum of Dori 3 ❑ ❑ ❑ Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length: x C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING DETERMINE WATTAGE ALLOWANCE ❑ ❑ ❑ Total Sign Are: A Also enter Total Sign Area above C J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc. 2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary. The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above) F 1 I High pressure sodium lamps H 2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient J 3 Pulse start metal halide lamps that are > 320 watts, are not 250 watt or 175 watt lamps, and are served by a ballast with > 80% efficient Square feet of Hardsca 4 Neon or cold cathode lamps with transformer or power supply efficient > 75% with rated output current < 50 mA Wattage Allowance (B x C) 5 Neon or cold cathode lamps with transformer or power supply efficiency > with rated output current < 50 mA Luminaire Type 6 Fluorescent lam s with a minimum color rendering index CRi of 80 Watts per 7 Light emitting diodes (LEDs) with a power supply with > /o et iciency Allowed Watts Minimum of Dori 8 Single voltage LED external power supplies designed to convert 120 volt AC input into lower voltage DC or AC output, having a nameplate output power less titan or equal to 250 watts, and certified to the Energy Commission as complying with the applicable requirements of the Appliance Efficiency Regulations (Title 20) 9 Compact fluorescent lamps that do not contain a medium screw base sockets (E24/E26) 10 1 Electronic ballasts with a fundamental output frequency > 20 kHz Field Inspector Notes or Discrepancies 2008 Nonresidential Compliance Forms December 2008 December 2008 CERTIFICATE OF COMPLIANCE (Page 4 of 4) OLTG-1C Project Name Date FONTANA CAMPUS PARKING LOT 02/03/10 2008 Nonresidential Compliance Forms December 2008 OUTDOOR LIGHTING WORKSHEET Pae 1 of 3 OLTG-2C Lighting Wattage Date 02/03/10 Power Allowance A Lighting power allowance for general hardscape INITIAL WATTAGE ALLOWANCE TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE (from OLGT-2C Page 1 of 3) 41206.81 B Specific application lighting wattage allowance per unit length E F (from OLGT-2C Page 1 of 3) 0 C Speck is application wattage allowance for ornamental lighting ANVA (A x B) PERIMETER LENGTH OF GENERAL HARDSCAPE (from OLGT-2C Page I of 3) 0 D Specific application wattage allowance per application 331797 0.092 (from OLGT-2C Page 2 of 3) 0 E Specific application lighting wattage allowance per area 770 41206.81 (from OLGT 2C Page 2 of 3) 0 F Additional lighting power allowance for ordinance requirements (from OLGT-2C Page 3 of 3) 0 G Total allowed Wattage = Sum of rows A through F: 41206.81 H Total installed watts (from Compliance Fixture Schedule, LUMINAIRE TYPE DESIGN (from OLGT-1C Page 1 of 4) 20972 A Complies if wattage in row H is less than or equal to the Nf Yes ❑ No E wattage in row G G H 2008 Nonresidential Compliance Forms December 2008 OUTDOOR LIGHTING WORKSHEET Pae 1 of 3 OLTG-2C Project Name FONTANA CAMPUS PARKING LOT Date 02/03/10 A. LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE AREA WATTAGE ALLOWANCE (AWA) LiNER WATTAGE ALLOWANCE (LWA) INITIAL WATTAGE ALLOWANCE TOTAL GENERAL HARDSCAPE LIGHTING ALLOWANCE A B C D E F G H ILLUMINATED HARDSCAPE AREA AWA PER SQUARE FOOT ANVA (A x B) PERIMETER LENGTH OF GENERAL HARDSCAPE LWA PER LINER FOOT LWA (D x E) IWA (WATTS) C + F t G 331797 0.092 30523.67 10775.15 0.92 9913 770 41206.81 Enter total into OLTG-i C; Page 4 Of 4; Row A; Lighting Power Allowance for general Hardscape: 41206.81 ❑ Yes AWA, LWA, and IWA from Table 147-A was used as appropiate for the Outdoor Lighting Zone B. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER UNIT LENGTH (Available only for sale frontage) DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Linear feet of Fronts a Sales Frontage allowance for OLZ (watts per if) Wattage Allowance (B x C) Name or Symbol Luminaire Type Luminaire Quantity Watts per Luminaire Design Watts (G x H) Allowed Watts Minimum of Dori Outdoor Sales Frontage Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length: x C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING DETERMINE WATTAGE ALLOWANCE LUMINAIRE TYPE DESIGN WATTS A B C D E F G H I J Specific Lighting Application Square feet of Hardsca Ornamental Lighting Allowance for OLZ , (watts per ft-) Wattage Allowance (B x C) Name or Symbol Luminaire Type Luminaire QuantityLuminaire Watts per Design Watts (G x H) Allowed Watts Minimum of Dori Hardscape Ornamental Lighting Enter total into OLTG-I C; Page 4 0174; Row C; Specific Application Wattage Allowance for Ornamental Lighting: 2008 Nonresidential Compliance Forms DESIGN DATE: 4-06-10 REEDCORP PROJECT NO. 09-399-2296 December 2008