HomeMy WebLinkAbout4854E-8CERTIFICATE OF COMPLIANCE (Page 1 of 4) OLTG-1C
Project Name
Date
FONTANA CAMPUS PARKING LOT
02/03/10
Project Address
Total Illuminated Area
FONTANA, CA
331779
General Information
Phase of Construction: ❑ New Construction ❑ Addition 56 Alternation
Documentation Author's Declaration Statement
• 1 certify that this Certificate of Compliance documentation is accurate and complete.
Name
Signature
MICHAEL REED
A
Company Unto
REEDCORP ENGINEERING XXXXXXXXX
Address EA#
2061 BUSINESS CENTER DRIVE, SUITE 110 CEP#
City/State/Zip Phone:
IRVINE, CA 92612 949/752-1278
Principal Lighting Designer's Declaration Statement
• I am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design.
• This Certificate of Compliance identifies the lighting features and performance specifications required for all outdoor lighting design.
Title 24, Pages 1 and 6 of the California Code of Regulations.
• The design features represented on this Certificate of Compliance are consistent with the infomation provided to document
this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this building permit application.
Name
Signature
THOMAS E. HARTMAN
Field
Inspector 2
Company
Phone:
REEDCORP ENGINEERING
949/752-1278
Address
License #
2061 BUSINESS CENTER DRIVE, SUITE 110
7531
City/Statef'Zip
Date
IRVINE, CA 92612
XXXXXXXXX
Principal Lighting Designer's Declaration
❑ i certify that this Certificate of Compliance documentation is accurate and complete, and accounts for all outdoor lighting power, including
building mounted, pole mounted, as well as all other outdoor lighting designed for the site, and that Additional Lighting Power Allowances for
Specific Applications or Additional Lighting Power Allowances for Ordinance Requirements have not been counted more than one time for the
same area, in accordance with Section 147 of the Standards.
LIGHTING COMPLIANCE FORMS R. WORKSHEETS (check box if worksheet is included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance forms, please refer to the ir'onresidential Manual
published by the California Energy Commission.
oil OLTG-1C Certificate of Compliance. All 4 pages required on plans for all submittals
5� OLTG-2C (Page I of 3) Lighting Wattage Allowances for Per Application or per Area. Optional on plans.
Lighting Optional Plans.
fi� OLTG-2C (Page 2 of 3) Lighting Wattage Allowances for Per Application or per Area. Optional on plans.
❑ OLTG-2C (Page 3 of 3) Additional Lighting Power Allowance for Ordinance Requirements. Optional on plans.
2008 Nonresidential Compliance Forms
December 2008
CERTIFICATE OF COMPLIANCE (Page 2 of 4)
OLTG-1C
COMPLIANCE FIXTURE / LIGHTING CONTROL SCHEDULE and FIELD INSPECTION CHECKLIST
Project Namc
FONTANA CAMPUS PARKING LOT
Date
1 02/03/10
Function Type ❑ Function Type ❑ Indoor Signs
INSTALLATION CERTIFICATE, OLTG-I-INST (Retain a copy and verify form is complete and signed)
Project Address
Field InsIxMion ❑
CERTIFICATE OF ACCEPTANCE, OLTG-2A (Retain a copy and verify form is complete and signed',Field
❑ Maximum Allowed Lightiag Power ❑ Alternate Lighting Sources
Repletion ❑
Luminaire Schedule
Installed Watts
Principal Lighting Designer's Declaration Statement
• i am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design.
A
B
C
D
E
F
G
H
I
Name
or
Item
Tag
Luminaire Description
See footnote below
(ic: lamp pole - to shoe box 400 watt metal halide)
v a
'g
% a
a
� '=
f I low Wattage
wax determined
g
�i=_
7__J
a
sy
Field
Inspector 2
x
z.n o
Ute= b�,
u � � < 2
IRVINE, CA 92612
•
A
POST—TOP 10' POLE 150 WATT
CUT OFF
196
❑
❑ 56
33
6468
❑
❑
B
POST—TOP 250 WATT
CUT OFF
296
❑
❑ M
15
4440
❑
❑
BB
POST—TOP 2 HEAD POLE 250 WATT
CUT OFF
592
❑
❑ 1A
1710064
Luminaire Type
El
El
[Exception to § 133(a)4. The EMC is required by a health or life safety statute, ordinance, or regulation, including
limited
Y
N
N/A
❑
but not to exit signs and traffic signs.
❑
I ❑
Nf
❑
❑
Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length:
x
❑
❑ ❑
WATTAGE ALLOWANCE
❑
❑
❑
Total Sign Are:
A
Also enter Total Sign Area above
C
J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc.
2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary.
The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above)
F
1 I High pressure sodium lamps
H
2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient
J
Enter total
into OLTG-1: Page 4 of 4; Row H, Total installed Watts:
20972
Wattage
Allowance
(B x C)
EXEMPT LUMINAIRES I Field Inspection ❑
Luminaire Type
Name or Symbol Description for exempt luminaires in accordance with §147
Watts per
7 Light emitting diodes (LEDs) with a power supply with > /o et iciency
Allowed Watts
Minimum of
Dori
8 Single voltage LED external power supplies designed to convert 120 volt AC input into lower voltage DC or AC output, having a nameplate output power less titan or equal to 250 watts, and
certified to the Energy Commission as complying with the applicable requirements of the Appliance Efficiency Regulations (Title 20)
9 Compact fluorescent lamps that do not contain a medium screw base sockets (E24/E26)
10 1 Electronic ballasts with a fundamental output frequency > 20 kHz
MANDATORY CONTROLS FField Inspection ❑
Field Inspector Notes or Discrepancies
# Description Location
# Description
Location
ATS NORTH PARKING NEAR
ATS SOUTH PARKING NEAR
SPECIAL FEATURES INSPECTION CHECKLIST (See Page 2 Of ofOLTG-1C)
Enter total into OLTG-I C; Page 4 0174; Row C; Specific Application Wattage Allowance for Ornamental Lighting:
The local enforcement agency should pay special auenlion to the items specified in this checklist. These items require special
written justification and doctuneruatiotr, and special verification. The local enforcement agency determines the adequacy of 1he
justification and may reject a building or design that othenrise complies based vn Me adequac3, of the special justification and
documentation submitted
Field Inspector Notes or Discrepancies:
1 Tvpe of luminaire (i. e.: post top, wall pack, surface, shoe box): for non -incandescent hrntinaires, indicate nominal lamp trattage and lamp ri pe
(ie.:,Jluoreseent, incandescent. HID). ballast t)pe (i.e.: electronic or magnetic): number of lumps and number of ballmis per luminaire. For
incandescent luminaires, the luminaire watlage listed in column D shall be the marinmm relamping rated srallage on a permanent factory -
installed label on the ltminaire, ,VDT the iratlage of the lamp (bidb) itsed in accordance with Section 130(d or e).
IfI ail then describe on Page 2 of the hispection Checklist Form and take appropriate action to correct. Perp, building plaits if necessan�
2008 Nonresidential Compliance Forms
CERTIFICATE OF COMPLIANCE (Sign Lighting) PAGE 1 OF 2 SLTG-1 C
Project Name
Phase of Construction ❑ Phase of Construction ❑ Addition 10 Alternation
Date
FONTANA CAMPUS PARKING LOT
Function Type ❑ Function Type ❑ Indoor Signs
❑
Project Address
Compliance Method Used
16- FONTANA, CA
❑ Maximum Allowed Lightiag Power ❑ Alternate Lighting Sources
Documentation Author's Declaration Statement
• I certify that this Certificate of Compliance documentation is accurate and complete.
Name
Signature
§133(a)l. All signs with permanently connected lighting are controlled with an automatic time switch control
MICHAEL REED
❑
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
Company Date
REEDCORP ENGINEERING xxxxxxx
Address EA#
2061 BUSINESS CENTER DRIVE, SUiTE 110 CEP#
Clt}'lStatC/Llp Phone:IRVINE,
CA 92612 949/752-1278
Principal Lighting Designer's Declaration Statement
• i am eligible under Division 3 of the California Business and Professions Code to accept responsibility for the lighting design.
• This Certificate of Compliance identifies the lighting features and performance specifications required for compliance with
Title 24 , Pages 1 and 6 of the California Code of Regulations.
• The design features represented on this Certificate of Compliance are consistent with the information provided to document
this design on the other applicable compliance forms, worksheets, calculations, plans and specifications submitted to the enforcement
agency for approval with this building permit application.
Name
Signature
THOMAS E. HARTMAN
§133(a)3. All outdoor signs are controlled with a dimmer that provides the ability to automatically reduce
Company
Phone:
REEDCORP ENGINEERING
949/752-1278
Address
Liccnw #
2061 BUSINESS CENTER DRIVE, SUITE 110
7531
CitytStntcll_ip
Datc
IRVINE, CA 92612
xxxxxxx
Mandatory Sign Lighting Controls
Yes No
Mandatory Sign Lighting Controls
Yes
No
I
§133(a)l. All signs with permanently connected lighting are controlled with an automatic time switch control
5(
❑
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
that complies with the applicable requirements of § 119.
41206.81
Maximum Allowed Lighting Power
Specific application lighting wattage allowance per unit length
§ 133(a)2. All outdoor signs are controlled with a photo control or outdoor astronomical time switch control.
A
❑
B. ADDITION LIGHTING POWER ALLOWANCE FOR ORDINANCE REQUIREMENTS
G
Are additional lighting power allowances for ordinance in Table 147-C used? ❑ Yes No
I
2
Exception to §(a)2. Outdoor sighs are in tunnels or large covered areas that require illumination during daylight hours.
❑
❑
Design
Wattsl
§133(a)3. All outdoor signs are controlled with a dimmer that provides the ability to automatically reduce
❑
❑
The following Acceptance Forms shall be submitted to the building department before an occurpanCy permit is grantedfor a newly
constructed building or space. All control devices serving the building or space shall be certified as meeting at Acceptance
Requirements for Code Compliance. List all equipment requiring testing, and indicated required acceptance documents.
sign power by a minimum of 65 percent during nighttime hours.
-C !
¢ :=1 W.
Luminaires Controlled
OLTG-2A
Exception I to § 133(a)3. Signs are illuminated for less than one hour per day during daylight hours.
56❑
Description
3
Exception 2 to § 133(a)3. Outdoor signs are in tunnels or large covered areas that require illumination during
1:1
❑
ATS
daylight hours.
1
NORTH PARKING
❑
Exception 3 to § 133(a)3. Only metal halide, high pressure sodium, cold cathode, or neon lamps are used to
❑
❑
1
illuminated signs or parts of signs.
❑
❑
Nf Yes
§ 133(a)4. An Electronic Message Center (EMC) having a new connected lighting power load greater than 15 kW
Y
N
N/A
D
has a control installed is capable of reducing the lighting power by a minimum of 30 percent when receiving a
❑
❑
5d
4
demand response signal that is sent out by the local utility.
Name or
Symbol
Luminaire Type
Luminaire
Quantity
Watts per
Luminaire
[Exception to § 133(a)4. The EMC is required by a health or life safety statute, ordinance, or regulation, including
limited
Y
N
N/A
❑
but not to exit signs and traffic signs.
❑
I ❑
Nf
2008 Nonresidential Compliance Forms
December 2008
December 2008
CERTIFICATE OF COMPLIANCE (Page 3 of 4) OLTG-1 C
Project Name
FONTANA CAMPUS PARKING LOT
Date
02/03/10
Project Name
FONTANA CAMPUS PARKING LOT
A. OUTDOOR LIGHTING ZONE
Total Sign Area
N/A
OUTDOOR LIGHTING ZONE: ❑ OLZ 1 ❑ OLZ 2 56OLZ 3 ❑ OLZ 4
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
Is the Outdoor Lighting Zonc4 Default in accordance with § 10-114 or ❑ Amended by JHA
41206.81
Maximum Allowed Lighting Power
Specific application lighting wattage allowance per unit length
Complete the information below if the default Outdoor Lighting Zone has been amended by the local jurisdiction having authority
(JHA):
❑ The site is a government designated park, recreation area, wildlife preserve, or portion thereof, and has been designated as LZ2
or LZ3, in accordance with Table 10-114-A, because the site is contained within such a zone.
❑ The local jurisdiction having authority has officially adopted a change to the State Default Lighting Zone and has notified the
Energy Commission by providing the materials required in § 10-114(d) to the Executive Director.
❑ The adopted change is posted on the Energy Commission website.
A
B
B. ADDITION LIGHTING POWER ALLOWANCE FOR ORDINANCE REQUIREMENTS
G
Are additional lighting power allowances for ordinance in Table 147-C used? ❑ Yes No
I
J
.o
O
U
0
E
Complete the information below if additional lighting power allowances for ordinance requirements are used:
❑ The local jurisdiction having authority has officially adopted specific outdoor light levels, which are expressed as average or
minimum footcandle levels, by following a public process that allowed for formal public notification, review, and comment
about proposed change.
❑ The local jurisdiction having authority which adopted specific outdoor light levels and has notified the Commission by
providing the following materials required in § 10-114(f) to the Executive Director.
Allowed Watts
Design
Wattsl
Complies
? Y/N
C. ACCEPT FORMS
Field
Ins ector2
The following Acceptance Forms shall be submitted to the building department before an occurpanCy permit is grantedfor a newly
constructed building or space. All control devices serving the building or space shall be certified as meeting at Acceptance
Requirements for Code Compliance. List all equipment requiring testing, and indicated required acceptance documents.
Certificate of Acceptance
-C !
¢ :=1 W.
Luminaires Controlled
OLTG-2A
OLTG-3A
Equipment Requiring Testing
Description
=
E
Z'5 U
Location
Outdoor
Motion
Sensors
Controls
Outdoor
Lighting
Shut-off
Controls
ATS
TIME CLOCK
1
NORTH PARKING
❑
❑
ATS
TIME CLOCK
1
SOUTH PARKING
❑
❑
Nf Yes
❑ No
E
wattage in row G
❑
D
3
❑
❑
❑
E
3' SIGN W EXTERNAL 2 LAMPS
Name or
Symbol
Luminaire Type
Luminaire
Quantity
Watts per
Luminaire
Design
Watts
(G x H)
Allowed Watts
Minimum of
Dori
3
❑
❑
❑
❑
O
❑
❑
Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length:
x
C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING
DETERMINE
WATTAGE ALLOWANCE
❑
❑
❑
Total Sign Are:
A
Also enter Total Sign Area above
C
J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc.
2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary.
The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above)
F
1 I High pressure sodium lamps
H
2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient
J
3 Pulse start metal halide lamps that are > 320 watts, are not 250 watt or 175 watt lamps, and are served by a ballast with > 80% efficient
Square feet of
Hardsca
4 Neon or cold cathode lamps with transformer or power supply efficient > 75% with rated output current < 50 mA
2008 Nonresidential Compliance Forms
CERTIFICATE OF COMPLIANCE (PAGE 2 OF 2) CHECK LIST SLTG-1C
COMPLIANCE METHOD AND FIELD INSPECTION ENERGY CHECKLIST
Date
02/03/10
Project Name
FONTANA CAMPUS PARKING LOT
Phase of Construction ❑ New Construction 10 Addition ❑ Alternation
Function Tv �Outdoor5igns ❑Indoor Signs
Total Sign Area
N/A
Date
02/03/10
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
Compliance Method
41206.81
Maximum Allowed Lighting Power
Specific application lighting wattage allowance per unit length
E
A
B
C D E F
G
H
I
J
.o
O
U
0
E
Description or location and plan location
Allowed Watts
Design
Wattsl
Complies
? Y/N
Light
Source
Field
Ins ector2
^
0
w =
-C !
¢ :=1 W.
CA
'S7
Q it
to
O
i— 3
v
U w
&n
Li. m
H
W U.
a.
U.
C
INTERNAL LED SIGN
0
G
Total allowed Wattage = Sum of rows A through F:
41206.81
H
Total installed watts (from Compliance Fixture Schedule,
7
❑
❑
❑
D
12' SIGN W EXTERNAL 4 LAMPS
Nf Yes
❑ No
E
wattage in row G
G
H
3
❑
❑
❑
E
3' SIGN W EXTERNAL 2 LAMPS
Name or
Symbol
Luminaire Type
Luminaire
Quantity
Watts per
Luminaire
Design
Watts
(G x H)
Allowed Watts
Minimum of
Dori
3
❑
❑
❑
Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length:
x
C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING
DETERMINE
WATTAGE ALLOWANCE
❑
❑
❑
Total Sign Are:
A
Also enter Total Sign Area above
C
J. Design 11'atls= total connected lighting load imtalled in the sign, including power used by lamps, ballasts, transformers, power supplies etc.
2. !f Fail then describe on Page 2 of!!re Inspection Checklist Form and take appropriate action to correct. Verif building plaits if necessary. Use Additional Sheets if necessary.
The Sign(s) identified above use one or more of the following technologies: (list all numbers that apply in column above)
F
1 I High pressure sodium lamps
H
2 Pulse start or ceramic metal halide lamps served by a ballast with > 88% efficient
J
3 Pulse start metal halide lamps that are > 320 watts, are not 250 watt or 175 watt lamps, and are served by a ballast with > 80% efficient
Square feet of
Hardsca
4 Neon or cold cathode lamps with transformer or power supply efficient > 75% with rated output current < 50 mA
Wattage
Allowance
(B x C)
5 Neon or cold cathode lamps with transformer or power supply efficiency > with rated output current < 50 mA
Luminaire Type
6 Fluorescent lam s with a minimum color rendering index CRi of 80
Watts per
7 Light emitting diodes (LEDs) with a power supply with > /o et iciency
Allowed Watts
Minimum of
Dori
8 Single voltage LED external power supplies designed to convert 120 volt AC input into lower voltage DC or AC output, having a nameplate output power less titan or equal to 250 watts, and
certified to the Energy Commission as complying with the applicable requirements of the Appliance Efficiency Regulations (Title 20)
9 Compact fluorescent lamps that do not contain a medium screw base sockets (E24/E26)
10 1 Electronic ballasts with a fundamental output frequency > 20 kHz
Field Inspector Notes or Discrepancies
2008 Nonresidential Compliance Forms
December 2008
December 2008
CERTIFICATE OF COMPLIANCE (Page 4 of 4) OLTG-1C
Project Name Date
FONTANA CAMPUS PARKING LOT 02/03/10
2008 Nonresidential Compliance Forms
December 2008
OUTDOOR LIGHTING WORKSHEET Pae 1 of 3 OLTG-2C
Lighting Wattage
Date
02/03/10
Power Allowance
A
Lighting power allowance for general hardscape
INITIAL
WATTAGE
ALLOWANCE
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
(from OLGT-2C Page 1 of 3)
41206.81
B
Specific application lighting wattage allowance per unit length
E
F
(from OLGT-2C Page 1 of 3)
0
C
Speck is application wattage allowance for ornamental lighting
ANVA
(A x B)
PERIMETER LENGTH OF
GENERAL HARDSCAPE
(from OLGT-2C Page I of 3)
0
D
Specific application wattage allowance per application
331797
0.092
(from OLGT-2C Page 2 of 3)
0
E
Specific application lighting wattage allowance per area
770
41206.81
(from OLGT 2C Page 2 of 3)
0
F
Additional lighting power allowance for ordinance requirements
(from OLGT-2C Page 3 of 3)
0
G
Total allowed Wattage = Sum of rows A through F:
41206.81
H
Total installed watts (from Compliance Fixture Schedule,
LUMINAIRE TYPE
DESIGN
(from OLGT-1C Page 1 of 4)
20972
A
Complies if wattage in row H is less than or equal to the
Nf Yes
❑ No
E
wattage in row G
G
H
2008 Nonresidential Compliance Forms
December 2008
OUTDOOR LIGHTING WORKSHEET Pae 1 of 3 OLTG-2C
Project Name
FONTANA CAMPUS PARKING LOT
Date
02/03/10
A. LIGHTING POWER ALLOWANCE FOR GENERAL HARDSCAPE
AREA WATTAGE ALLOWANCE (AWA)
LiNER WATTAGE ALLOWANCE (LWA)
INITIAL
WATTAGE
ALLOWANCE
TOTAL GENERAL
HARDSCAPE LIGHTING
ALLOWANCE
A
B
C
D
E
F
G
H
ILLUMINATED
HARDSCAPE AREA
AWA PER
SQUARE
FOOT
ANVA
(A x B)
PERIMETER LENGTH OF
GENERAL HARDSCAPE
LWA PER
LINER
FOOT
LWA
(D x E)
IWA
(WATTS)
C + F t G
331797
0.092
30523.67
10775.15
0.92
9913
770
41206.81
Enter total into OLTG-i C; Page 4 Of 4; Row A; Lighting Power Allowance for general Hardscape:
41206.81
❑ Yes AWA, LWA, and IWA from Table 147-A was used as appropiate for the Outdoor Lighting Zone
B. SPECIFIC APPLICATION LIGHTING WATTAGE ALLOWANCE PER UNIT LENGTH (Available only for sale frontage)
DETERMINE WATTAGE ALLOWANCE
LUMINAIRE TYPE
DESIGN
WATTS
A
B
C
D
E
F
G
H
I
J
Specific Lighting Application
Linear feet
of Fronts a
Sales Frontage
allowance for OLZ
(watts per if)
Wattage
Allowance
(B x C)
Name or
Symbol
Luminaire Type
Luminaire
Quantity
Watts per
Luminaire
Design
Watts
(G x H)
Allowed Watts
Minimum of
Dori
Outdoor Sales Frontage
Enter total into OLTG-IC; Page 4 Of 4; Row B; Specific Application Lighting Wattage Allowance Per Unit Length:
x
C. SPECIFIC APPLICATION WATTAGE ALLOWANCE FOR ORNAMENTAL LIGHTING
DETERMINE
WATTAGE ALLOWANCE
LUMINAIRE TYPE
DESIGN
WATTS
A
B
C
D
E
F
G
H
I
J
Specific Lighting Application
Square feet of
Hardsca
Ornamental
Lighting Allowance
for OLZ ,
(watts per ft-)
Wattage
Allowance
(B x C)
Name or
Symbol
Luminaire Type
Luminaire
QuantityLuminaire
Watts per
Design
Watts
(G x H)
Allowed Watts
Minimum of
Dori
Hardscape Ornamental
Lighting
Enter total into OLTG-I C; Page 4 0174; Row C; Specific Application Wattage Allowance for Ornamental Lighting:
2008 Nonresidential Compliance Forms
DESIGN DATE: 4-06-10
REEDCORP PROJECT NO. 09-399-2296
December 2008