HomeMy WebLinkAbout3043-1GENERAL NOTES 1. ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD PLANS, THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION UNLESS OTHERWISE NOTED. 2. WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CAN NOT BE RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK," THE CONTRACTOR SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEER FOR RESOLUTION. 3. ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER. 4. CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK. INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE START OF ANY WORK IN PUBLIC RIGHT-OF-WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610. 5. THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST NON -METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER. 6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES. 7. THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF INDUSTRIAL SAFETY. 8. THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS PURSUANT TO THE REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND MOVEMENT. 9. NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY WITHOUT OBTAINING SEPARATE PERMIT FOR THAT PURPOSE. 10. THE LOCA11ONS OF U11UTIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION, HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE, IN THE FIELD, THE TRUE LOCATION AND ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER PRECAUTION TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT AT 1-800-227-2600 TWO WORKING DAYS BEFORE EXCAVATION. 11. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING, BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND CALTRANS. ALL U11UTY COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK AROUND THEIR FACILITIES. 12. THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR VALVE OPERATION AND WATER REQUIREMENTS. 13. STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE NOTED. 14. ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE THE CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING DURING CONSTRUCTION. 15. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER. 16. REMOVAL AND REPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING SURVEY MONUMENTS, MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED CIVIL ENGINEER OR LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF CONSTRUC11ON SHALL BE REPLACED. THE CONTRACTOR SHALL N011FY THE ENGINEER ONE WEEK PRIOR TO THIS CONSTRUCTION SO THAT 11ES TO MONUMENTS CAN BE ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT. 17. THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESSES AT ALL TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUC11ON AREA FOR RESIDENTS AND EMERGENCY VEHICLES. 18. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL, INCLUDING ADEQUATE WATERING, AT ALL TIMES. 19. THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING CONSTRUCTION WITHOUT PRIOR TO WRITTEN APPROVAL 20. NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR. 21. A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE TO OBTAIN THE REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT PORTION OF THE WORK UNTIL THE SPECIFIED DENSITY IS OBTAINED. 22. CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE TEMPORARY NON-ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS. 23. ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH EXISTING CONCRETE. 24. IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A TERMINAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE DOWNSTREAM MANHOLE, SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT. 25. SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS OF THE ASTM DESIGNATION C700 FOR V.C.P. 26. NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL OF THE CITY ENGINEER. 27. SHORT V.C.P. STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE WALLS TO ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT. 28. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND VERIFY ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS TO EXISTING FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCATIONS SHOWN ON THE PLANS. 29. ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS OTHERWISE APPROVED BY THE CITY ENGINEER. 30. TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12" BELOW THE GROUND SURFACE. WHEN- PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE STREET RIGHT OF WAY, THE LATERAL SHALL TERMINATE 3 FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY EASEMENT. AAAAAA ............ CE ...................... TOLL FREE -800-227-2600 A PUBUC SERVICE BY UNDERGROUND SERVICE ALERT 31. THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE LOCATION OF THE SEWER LATERAL 32. IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED IMPROVEMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY. 33. NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN PLACED, INSPECTED AND APPROVED. 34. ALL UNDERGROUND U11UTIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING OF STREETS. 35. APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT PRIOR TO PLACEMENT. 36. ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED TO FINISHED GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING. 37. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING, BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFAC11ON OF THE CITY TRAFFIC ENGINEER. 38. AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF RECORD, WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER. PRIVATE ENGINEER'S NOTICE TO CONTRACTORS THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY: THAT THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE OWNER AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER OR THE ENGINEER. UNDERGROUND UTILITIES & STRUCTURES THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES OR STRUCTURES SHOWN IN THESE PLANS WAS OBTAINED BY A SEARCH OF AVAILABLE RECORDS. TO THE BEST OF OUR KNOWLEDGE, THERE ARE NO EXISTING UTILITIES EXCEPT THOSE SHOWN ON THESE PLANS. THE CONTRACTOR IS REQUIRED TO TAKE ALL PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES SHOWN, AND IS RESPONSIBLE FOR THE PROTECTION OF, AND ANY DAMAGE TO THESE LINES OR STRUCTURES. CAUTION: "THE ENGINEER PREPARING THESE PLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS." NOTICE TO CONTRACTOR: UTILITIES SHOWN HEREON AS "PROPOSED" MAY IN FACT BE EXISTING AT THE TIME OF THIS CONSTRUCTION. THE CONTRACTOR SHALL DETERMINE IF ANY "FUTURE OR PROPOSED" UTILITY HAS BEEN CONSTRUCTED. UTILITY PURVEYORS: SEWER WATER CIN OF FONTANA FONTANA WATER COMPANY 8353 SIERRA AVE. 8440 NUEVO AVE FONTANA, CA. 92335 FONTANA, CA 92335 (909) 350-6632 (909) 822-2201 ATTN: CARLOS NAVARRO ATTN: AL KROHN ELECTRICAL SAN GABRIEL VALLEY WATER COMPANY 5,375 LF PO BOX 6010 SOUTHERN CALIFORNIA EDISON CO. EL MONTE, CA 91734-2010 7951 REDWOOD AVE (626) 448-6183 ext 251 FONTANA, CA 92335 ATTN: LUIS MONTENEGRO ATTN: JAIME AMESZCULA (909) 357-6581 GAS (800) 422-4133 UNDERGROUND: (909) 820-5598 SOUTHERN CALIFORNIA GAS COMPANY TRANSMISSIONS: (909) 820-5137 P.O. BOX 3003, SC8031 REDLANDS, CA 92373-0306 PIPELINES: (213) 657-1233 ATTN: RICKEY REYES DISTRIBUTION: (909) 357-6589 (909) 335-7508 Q� (909) 335 7527 (FAX) TELEPHONE AS SHOWN PA 1P aFi i EMERGENCIES: (800) 427-229 CITY OF FONTANA 73 72 71 70 TRACT- BOUNDARY69 I!i I 68 h 1 671 SEWER TRACT 15843 TRACT 15841 Ilk 80 MH 81 s2�- \ AVEI / Q,-------_�-_-- - _ - 83 ._l yi--------------- ---- --_ / 84 ; SHT 6. _: __.... _ r--. - : -• ` / ! • 1 ., _-2 1 3 , 4 ! 5 , 6 '. 7. .-'. 8 MH #7 ! ► 1MHI ! ► 85 -STREET_- - 10187 I �' O 88 98 t 115 \ 89 ' 90 J i 11 123 ,MH 91 92 93 94 95 96 ' 97 r 99 12 - in #2 I..._ 114 - - - - 122 i = --.-.. l r „7 106 M _ ,t 17MH , 145 I�! 1146--- ! 161 <147 - _- 160 I! 148 I I 159 149 i 158 150 MHS .#2 `f It •.151 ` I -152 153 SERRA____ I, 135 37 38 39 40 52 INDEX MAP SCALE: 1"=200' CONSTRUCTION NOTES &QUANTITIES: 15 i 16 17 I p_ TRACT t.; BOUNDARY ITEM DESCRIPTION QUANTITY M4 O1 INSTALL 8" EXTRA STRENGTH VCP SEWER 6,402 LF 51i O2 CONSTRUCT 48" PRECAST CONCRETE MANHOLE PER CITY STD DETAILS 109 AND 112 24 EA �c O3 INSTALL 4" EXTRA STRENGTH VCP LATERAL PER CITY STD DETAIL 125 5,375 LF ASTM C 131 TEST GRADING O REMOVE STOPPER AND JOIN PIPE 2 EA 00 5O CONSTRUCT SEWER LATERAL CROSSING PER DETAIL ON SHT 8 AND PER APWA STD 7 EA LL_� PLAN 223-1 CASE D ON SHT 11 v� 6 BACKFLOW PREVENTOR (TO BE INSTALLED WITH PRECISE GRADING) 67 EA O7 INSTALL 8" VCP STOPPER _ � 2 EA 15 i 16 17 I p_ TRACT t.; BOUNDARY ' 23 1 MH-- --- I ! #15 24 t J 2. t 2s 5 __j ARKWAY 6" MIN 6" MIN 10" MAX 10" MAX 3" MAX SIZE NATIVE SOIL, COMPACTED 95% 1" MAX. SIZE SELECTED NATIVE SOIL 6" MAX SIZE BEDDING COMPACTED NATIVE SOIL TO 90% COMPACTED 90% Is 1/2" CRUSHED�� ' = �r �= =.�- 04 z STONE BEDDING :1- - - PER STD. SPECS. FOR PUBLIC WORKS CONSTRUCTION • �' `� R �O p12P�\J1�11� Cs ►� TABLE 200-1.2(A) 'j- 3939 E. CORONADO STREET SHOWN AT RIGHT ANAHEIM, CA. 92807 CABLE CO. (714) 666-5500 COMCAST CABLE pQ��FES/0 8" VCP ATTN: LARRY SIGNAIGO 1205 DUPONT AVE. �y6, ONTARIO, CA. 91761 -CIO o (909) 390-4738 ext 3055 C No. 31681 TYPICAL BEDDING FOR REV. REVISION DESCRIPTION REVISED QUANTITIES FOR CONSTRUCTION NOTES 1 AND 2, ADDED CONSTRUCTION NOTE 7, SEE SHEETS 2 & 7 FOR ADDITIONAL REVISIONS. Q 6nRo cQf\w i �) G Ep Iz 2 s� 0, „ 8 VCP 10 OR DEEPER OF CALIF NTS 0�t 3/C:7-0 DATE ENGR. aTY DATE SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT 5-10-0 ' •I •d Qwc -_SS/0 COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL HUf? SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER, � , 3%'%�`� 5• •o THE CITY ENGINEER MAY REQUIRE REVISIONS TO THE PLANS TO = No. 31681 z Q * Exp. 12/31/04 BRING THEM INTO CONFORMANCE WITH CONDITIONS AND -9j• CIVIC- F OF CA`�FO STANDARDS IN EFFECT. N Q TABLE 200-1.2(A) SIEVE SIZE PERCENTAGE PASSING SIEVES 1 1 /2" MH M4 - � L -LY #24 51i 90-100 3/8" 20-60 NO. 4 0-15 NO. 8 0-5 ' 23 1 MH-- --- I ! #15 24 t J 2. t 2s 5 __j ARKWAY 6" MIN 6" MIN 10" MAX 10" MAX 3" MAX SIZE NATIVE SOIL, COMPACTED 95% 1" MAX. SIZE SELECTED NATIVE SOIL 6" MAX SIZE BEDDING COMPACTED NATIVE SOIL TO 90% COMPACTED 90% Is 1/2" CRUSHED�� ' = �r �= =.�- 04 z STONE BEDDING :1- - - PER STD. SPECS. FOR PUBLIC WORKS CONSTRUCTION • �' `� R �O p12P�\J1�11� Cs ►� TABLE 200-1.2(A) 'j- 3939 E. CORONADO STREET SHOWN AT RIGHT ANAHEIM, CA. 92807 CABLE CO. (714) 666-5500 COMCAST CABLE pQ��FES/0 8" VCP ATTN: LARRY SIGNAIGO 1205 DUPONT AVE. �y6, ONTARIO, CA. 91761 -CIO o (909) 390-4738 ext 3055 C No. 31681 TYPICAL BEDDING FOR REV. REVISION DESCRIPTION REVISED QUANTITIES FOR CONSTRUCTION NOTES 1 AND 2, ADDED CONSTRUCTION NOTE 7, SEE SHEETS 2 & 7 FOR ADDITIONAL REVISIONS. Q 6nRo cQf\w i �) G Ep Iz 2 s� 0, „ 8 VCP 10 OR DEEPER OF CALIF NTS 0�t 3/C:7-0 DATE ENGR. aTY DATE SHOULD CONSTRUCTION OF THE REQUIRED IMPROVEMENTS NOT 5-10-0 ' •I •d Qwc -_SS/0 COMMENCE WITHIN TWO YEARS OF THE DATE OF APPROVAL HUf? SHOWN HEREON AND CARRIED FORTH IN A DILIGENT MANNER, � , 3%'%�`� 5• •o THE CITY ENGINEER MAY REQUIRE REVISIONS TO THE PLANS TO = No. 31681 z Q * Exp. 12/31/04 BRING THEM INTO CONFORMANCE WITH CONDITIONS AND -9j• CIVIC- F OF CA`�FO STANDARDS IN EFFECT. N Q TABLE 200-1.2(A) SIEVE SIZE PERCENTAGE PASSING SIEVES 1 1 /2" - 1" - 3/4" 100 1/2" 90-100 3/8" 20-60 NO. 4 0-15 NO. 8 0-5 ASTM C 131 TEST GRADING B iiT.T.. i w M 1. CONTRACTOR TO NOTIFY ENGINEER OF ANY DISCREPANCY WITH THE PLANS PRIOR TO START OF WORK. �c 2. SEE GENERAL NOTE 30. G� GPS 15 � pF � pP�' ,FONTANA a• SUMMIT AVE. /--%/ 1 Y,/SUMMIT O V l•- �� w Q CUR AVENUE Ld U P JECTUj SITE J U> SIERRA V v w Q PARKWAY M 10 HIGHLAND AVE. COUNTY OF SAN BERNARDINO VICINITY MAP NTS BENCH MARK: THE BENCH MARK FOR THIS PROJECT IS CALTRANS BM #8-17. IT IS DESCRIBED AS A BRASS CAP IN THE CONCRETE BASE OF THE SOUTH LEG OF AN SCE TOWER 343' NORTH OF HIGHLAND, 0.2 MI WEST OF SAN SEVAINE RD., 2.65 MI WEST OF SIERRA AVE. ELEVATION IS 1428.609 FEET. BASIS OF BEARINGS: THE BASIS OF BEARINGS FOR THIS DRAWING IS THE LINE BETWEEN THE NW COR. SEC. 25, R6W, T1 N (PT. 61) AND THE NORTHERLY QUARTER COR. OF SAIID SEC. 25 (PT 84). SAID BEARING IS N89'44'05"E AS SHOWN ON RS 30/58-60. LEGEND SEWER LINE BEGIN CURVE SEWER LINE END CURVE PER OTHER SHEET CENTERLINE SEWER LINE MANHOLE PER OTHER PLANS INTERSECTION EX SEWER LINE E -X- S STORM DRAIN LINE __ --SD_-=- WATER -W ------ SEWER MANHOLE O/• DIRECTION OF FLOW WATER UNE 00 RIGHT OF WAY 110+00.001 moor Ha11 &fireman, Inc. mmri Civil Engineering •Planning •Surveying •Public Works DRAWN BY: 1152 N. Mountain Ave. Ste. 100 •Upland, CA 91786-3669.909-982-7777 REF PREPARED UND R THE SUPERVISION OF: DESIGNED BY: ) REF s _ J V _��(�`-�1�0•-'(Qs�-� (f�/ OZ CHECKED BY: HAROLD A. GAR ELON R.C.E. 31681 DATE: RLP BC BEGIN CURVE EC END CURVE CL CENTERLINE MH MANHOLE INT INTERSECTION R/W RIGHT OF WAY EX EXISTING S SEWER LINE SD STORM DRAIN UNE W WATER UNE ST STREET STATION 110+00.001 SEWER STA11ON CITY OF FONTANA, CALIFORNIA SUMMIT HEIGHTS II SEWER PLANS Tln ,P.E sriEEr ---7 m r,nio_ t9is3 .C.E. 51152 DATE: 3 a 00 N 0 t 0 3 �� L _ Qi v � �o LL_� v� M i v � �T Q� Ate: o AS SHOWN N 1 11-21-01 1-," iCD coo 3043