HomeMy WebLinkAbout2880-13GENERAL M
1. VERIFY EXISTING SITE CONDITIONS, SERVICE REQUIREMENTS (ELECTRICAL, T.V,, AND
TELEPHONE) AND EXACT LOCATIONS OF SERVICE FACILITIES BEFORE SUBMITTING BID.
SUBMITTAL OF BID INDICATES CONTRACTOR IS COGNIZANT OF ALL JOB SITE CONDITIONS,
ACTUAL PHYSICAL LOCATIONS, AND WORK TO BE PERFORMED.
2. CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, INSURANCE, EQUIPMENT,
INSTALLATION, CONSTRUCTION TOOLS, TRANSPORTATION, ETC. FOR A COMPLETE AND
PROPERLY OPERATING ELECTRICAL SYSTEM.
3. CONSTRUCTION TERMINOLOGY, AND THE STANDARDS AND ACCEPTABLE METHODS OF
INSTALLATION REQUIRED BY THESE CONTRACT DOCUMENTS ARE BASED ON PUBLISHED
STANDARDS OF N.E.C.A. (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION), NATIONAL
ELECTRICAL SAFETY CODE, AMERICAN NATIONAL STANDARDS INSTITUTE DOCUMENTS,
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION, UNDERWRITERS LABORATORIES,
AND THE CALIFORNIA ELECTRICAL CODE. SUBMITTAL OF BID INDICATES THE CONTRACTOR
IS COGNIZANT OF THESE STANDARDS AND THE REQUIREMENTS NECESSARY TO PERFORM
ALL THE WORK AS SET FORTH IN THESE CONTRACT DOCUMENTS.
4. ELECTRICAL CONTRACTOR SHALL SECURE ALL NECESSARY BUILDING PERMITS, UTILITY
CHARGES AND PAY FOR SAME. COORDINATE AND PAY FOR ALL TEMPORARY ELECTRICAL
SERVICE CHARGES WITH THE BUILDING DEPARTMENT, SERVING' UTILITY, AND OWNER.
COORDINATE TEMPORARY CONSTRUCTION REQUIREMENTS WITH ALL TRADES PRIOR TO
CONSTRUCTION.
5. THESE PLANS ARE DIAGRAMMATIC ONLY, FOLLOW AS CLOSELY AS POSSIBLE AND REFER
TO ARCHITECTURAL DRAWINGS FOR DETAILS, STRUCTURAL DETAILS, EXACT EQUIPMENT
AND OUTLET LOCATIONS. ALTHOUGH NOT SHOWN, CONTRACTOR SHALL PROVIDE ALL
J -BOXES, PULL BOXES, ELLS, OFFSETS ETC., FOR A COMPLETE CODE APPROVED
INSTALLATION. FOOTAGE SHOWN ON ELECTRICAL SINGLE LINES AND RISER DIAGRAMS ARE
FOR CALCULATION PURPOSES ONLY AND ARE NOT FOR BIDDING PURPOSES OR MATERIAL
TAKEOFF. ALL LOCATIONS OF EVERY OUTLET SHALL BE VERIFIED PRIOR TO ROUGH -IN.
6. THE CONNECTION METHOD OF VARIOUS APPLIANCES IS SHOWN AS A RECEPTACLE, AND
IS FOR BIDDING PURPOSES. THIS CONTRACTOR SHALL COORDINATE AND PROVIDE, FROM
ACTUAL SHOP DRAWINGS, THE CONNECTION SHOWN ON THOSE DRAWINGS.
7. EACH CONDUCTOR OF EVERY SYSTEM SHALL BE PERMANENTLY TAGGED IN COMPLIANCE
WITH OSHA.
8. ALL MATERIALS SHALL BE NEW, AND OF THE SAME MANUFACTURER FOR EACH CLASS OR
GROUP OF EQUIPMENT. MATERIALS SHALL BE LISTED AND APPROVED BY UNDERWRITER'S
LABORATORIES FOR THE USE AND ENVIRONMENT, AND SHALL BEAR THE INSPECTION LABEL
WHERE SUBJECT TO SUCH APPROVAL.. MATERIALS SHALL MEET WITH THE APPROVAL OF
THE DIVISION OF INDUSTRIAL SAFETY, AND ALL GOVERNING BODIES HAVING JURISDICTION.
MATERIALS SHALL BE MANUFACTURED IN ACCORDANCE WITH APPUCABL.E STANDARDS
ESTABLISHED BY A.N.S.I., U.L., N.E.M.A. AND N.B.F.U. INSTALL PER MANUFACTURERS'
RECOMMENDATIONS.
9. SUBSTITUTIONS OF SPECIFIED MATERIALS ARE IN ACCORDANCE WITH THE GENERAL
CONDITIONS. APPROVAL OF EQUAL MATERIALS PRIOR TO BID ARE BY WRITTEN ADDENDUM
ONLY OR AS STATED ON THE PLANS.
10. SUBMIT SHOP DRAWINGS FOR ALL MAJOR PIECES OF ELECTRICAL EQUIPMENT INCLUDING
BUT NOT LIMITED TO: SWITCHGEAR, PANELBOARDS, TRANSFORMERS, LIGHTING FIXTURES,
AND CONTROL PANELS AND TIME SWITCHES. ALL SWITCHGEAR FOR UTILITY METERED
SERVICES SHALL BE SUBMITTED BY THE CONTRACTOR, TO THE SERVING UTILITY, AND
APPROVED PRIOR TO FABRICATION. THE CONTRACTOR SHALL SUBMIT, ALONG WITH THE
SHOP DRAWINGS, A SCALED, 3/8" = V-0" MINIMUM, FLOOR PLAN OF HIS PROPOSED LAYOUT
0� THE ELECTRICAL ROOM USING SIZE OF ACTUAL EQUIPMENT FROM THE SHOP
DRAWINGS.
11. CONTRACTOR SHALL PERFORM HIS WORK IN ACCORDANCE WITH ALL GOVERNING STATE,
COUNTY, LOCAL CODES, O.S.H.A. AND THE PRESENTLY ADOPTED NATIONAL ELECTRICAL
CODE (N.E.C.).
12. THE COMPLETE ELECTRICAL SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH THE
PRESENTLY ADOPTED EDITION OF THE N.E.C., ART. #250, AND ALL APPLICABLE ARTICLES.
13. PENETRATIONS TO FIRE -RATED MATERIALS SHALL BE RESTORED TO EQUAL RATING AS
REQUIRED BY LOCAL ENFORCING AGENCY.
14, CONDUCTORS SHALL BE CODE GRADE, 600 VOLT CLASS, COPPER, MARKED 24" ALONG IT'S
LENGTH SHOWING MANUFACTURER'S NAME, MAXIMUM ALLOWABLE VOLTAGE AND SIZE.
CONDUCTORS SHALL BE TYPE "THWN" (WET) OR "THHN" (DRY). DELIVER THE WIRE TO THE
SITE IN UNBROKEN PACKAGES.
15. ALL CONDUIT SHALL BE INSTALLED CONCEALED WHERE PHYSICALLY POSSIBLE.
16. CONDUIT SHOWN AS EXPOSED OR APPROVED FOR EXPOSED INSTALLATION SHALL BE
INTERMEDIATE METALLIC CONDUIT, I.M.C. SECURED WITH TWO HOLE MALLEABLE PIPE
STRAPS AND SCREWS. ALL BOXES AND FITTINGS SHALL BE SUPPORTED AND SECURED IN
COMPLIANCE WITH N.E.C. ARTICLE 370.
17. P.V.C. CONDUIT, WITH CODE SIZED GROUND, SHALL BE USED UNDERGROUND ONLY, IF
APPROVED BY LOCAL CODE. INSTALL PER LOCAL CODE REQUIREMENTS. ALL CONDUIT
SWEEPS AND RISERS AND STUBS ABOVE GRADE SHALL BE I.M.C. WITH HALF -LAPPED TAPE
COVERING OR PVC COATING. ROUTE UNDERGROUND CONDUITS AROUND PROPOSED
I
BUILDING LOCATIONS.
18. ALL CONDUIT ONLY (C.O.) SHALL HAVE A 3/16" PULL WIRE OR ROPE.
19. USE ONLY COMPETENT AND SKILLED PERSONNEL AND PERFORM ALL WORK, INCLUDING
AESTHETIC AS WELL AS ELECTRICAL AND MECHANICAL ASPECTS TO STANDARDS
CONSISTENT WITH THE BEST PRACTICES OF THE TRADE.
20. PROVIDE MAIN UNDERGROUND PULL SECTION, METERING, MAIN DISCONNECT DEVICE,
DISTRIBUTION SECTION(S) AND BRANCH CIRCUIT LOADCENTERS WITH RATINGS,
COMPONENTS AND FEATURES IN STRICT ACCORDANCE WITH THE SERVING UTILITIES AND
CODE ENFORCING AGENCY, ELECTRICAL DRAWINGS AND SPECIFICATIONS. THE MAIN
SWITCHBOARD AND DISTRIBUTION PANELS CONSIST OF A COMPLETELY ENCLOSED SELF
SUPPORTING FLOOR STANDING STRUCTURE, OF THE REQUIRED NUMBER OF FORMED
VERTICAL PANEL SECTIONS. PROVIDE BOLTED FRAMES AND INSULATING BLOCK TO
SUPPORT THE MAIN HORIZONTAL BUS FOR SHORT CIRCUIT STRESSES AS INDICATED ON
THE DRAWINGS. ALL BUSSING IS 100% RATED, MADE WITH COPPER HAVING A CURRENT
DENSITY OF 1,000 AMPS PER SQUARE INCH, PROVIDED WITH SILVER PLATED BUS
CONNECTIONS. PROVIDE A 1/4 INCH THICK BY 2 INCH HIGH BY FULL LENGTH GROUND BUS
WITHIN 12 INCHES OF NEUTRAL BUS AND CONNECT WITH A REMOVABLE LINK (CONNECTED
IF SHOWN ON SINGLE LINE DIAGRAM). BOLT ALL FASTENINGS BETWEEN VERTICAL PANEL
SECTIONS TO PROVIDE FLEXIBILITY DURING INSTALLATION. VENTILATED ENCLOSURE WITH
NEMA 3R EXTERIOR ENCLOSURE IF REQUIRED, SHALL BE RUST PROOF PRIOR TO PAINTING
2 COATS GREY ENAMEL.
21. FUSIBLE SWITCHES, 800 AMP AND GREATER, SHALL BE BOLTED PRESSURE TYPE, 100%
RATED IN FULL COMPLIANCE WITH U.L. 977.
22. PROVIDE TRANSFORMERS, DRY TYPE , WITH THE RATINGS SHOWN ON THE DRAWINGS.
PROVIDE STANDARD TAPS (2) FCAN/ (4) FCBN. ADJUST ALL TAPS TO NOMINAL VOLTAGES
USED, AND AS CLOSE AS PRACTICABLE. PROVIDE INSULATION WITH TEMPERATURE RISE
NOT EXCEEDING 115 DEGREES C., UNDER FULL LOAD, IN AN AMBIENT TEMPERATURE OF 40
DEGREES C.
23. PROVIDE ALL LAMPS, HANGERS AND SEISMIC SUPPORTS PER UNIFORM BUILDING CODE,
LENSES, ETC., FOR A COMPLETE LIGHTING FIXTURE.
24. WHERE IT BECOMES NECESSARY TO DRILL INTO OR CUT THROUGH ANY EXISTING FLOORS,
WALLS OR CEILINGS TO PERMIT THE INSTALLATION OF ANY WORK UNDER THIS CONTRACT,
OR TO REPAIR ANY DEFECTS THAT MAY APPEAR PRIOR TO THE EXPIRATION OF THE
WARRANTY, SUCH CUTTING AND PATCHING SHALL BE PERFORMED BY TRADESMEN
EXPERIENCED IN THE WORK REQUIRED. CONTRACTOR SHALL PAY FOR ALL COSTS
REQUIRED FOR - CUTTING OR REPAIRING. ALL FINISHES SHALL MATCH EXISTING OR NEW
ADJACENT SURFACES.
25. CONTRACTOR SHALL FURNISH AND INSTALL ALL POWER, CONTROL WIRES, CONDUITS AND
OUTLETS TO RENDER MECHANICAL EQUIPMENT OPERATIVE. REFER TO MECHANICAL
DRAWINGS FOR CONTROL SCHEMATICS.
26. PROVIDE ENGRAVED PLASTIC NAMEPLATES FOR ALL SWITCHBOARDS, PANELBOARDS,
LOADCENTERS, TRANSFORMERS, AND TERMINAL CABINETS. PLATES SHALL BE 3 PLY,
BLACK FACE, WHITE CORE WITH 1/4- HIGH CONDENSED GOTHIC LETTERING. SCREW -ON
ATTACHMENT OR PERMANENT ADHESIVE TAPE AS MANUFACTURED BY 3M IS REQUIRED.
27. HAND THE OWNER ONE SPARE SET OF EACH SIZE AND TYPE OF FUSE INSTALLED ON THIS
PROJECT.
28. PROVIDE THE OWNER WITH ONE . (1) SET OF COMPLETE ELECTRICAL "AS -BUILT -
REPRODUCIBLE DRAWINGS AT THE COMPLETION OF THE JOB, SHOWING ACTUAL DEPTHS
OF UNDERGROUND RUNS AND ALL LOCATIONS. ALL BROCHURES, OPERATING MANUALS,
CATALOGS, SHOP DRAWINGS, ETC. SHALL BE TURNED OVER TO THE OWNER AT JOB
COMPLETION.
29. COMPLETE JOB SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR AFTER DATE OF
ACCEPTANCE BY OWNER. ANY WORK, MATERIAL OR EQUIPMENT FOUND TO BE FAULTY
DURING THAT PERIOD SHALL BE CORRECTED AT ONCE, UPON WRITTEN NOTIFICATION, AT
THE EXPENSE OF THE ELECTRICAL CONTRACTOR.
30. WHERE A CONFLICT OCCURS BETWEEN THESE NOTES AND ELECTRICAL SPECIFICATION
ISSUED AS A PART OF THESE DOCUMENTS, THE MORE STRINGENT REQUIREMENT SHALL
PREVAIL.
• •�...urm s `ww�� • wows • �• ♦ .��� • o • ��w •
• M 42 KAIC * •
100 AS
AF
100A LOADCENTER
Ink Ift
1,3 2,4 5 6 .
20 A 20 A 20 A 20 A (2)2OA/1 P
2P 2P 1P 1P SPACE
I
L. .J
• s
C
1.9 kW k 0.5 kW CONNECT TO
UTILITY PARK IRRIGATION
SERVICE
PER SCE 1.7 kW LIGHTING CONTROLLER
PROVIDE 24HR. TIME
SWITCH; PHOTO CELL "ON"
SINGLE LINE DIAGRAM
12'-0"
20N
* CONTRACTOR TO PROVIDE SCE
LETTER FOR LOWER A.I.C. RATING.
tE AND POLE BY SPAUL.DING
k SERIES
150HPS-1 1 1-240-BLK
3S
ROUND STRAIGHT STEEL POLE
# 12 RA PVA
W.P. HANDHOLE
BOND GROUND
CONDUCTOR TO
POLE.
BUSH END
BOLT COVER
(4) 3/4" X 30" ANCHOR BOLTS.
CHAMBER EDGE
FINISHED GRADE
ELECTRICAL CONDUIT
SEE PLANS
LIGHTING DETAIL
SCALE .. %
N.T.S. `
SCALE
N.T.S.
SYMBOLS LIST
❑ RECESS MOUNTED DOWN LIGHT FIXTURE - REFER TO FIXTURE SCHEDULE.
0 SURFACE MOUNTED LIGHT FIXTURE - REFER TO FIXTURE SCHEDULE.
-•- POLE MOUNTED LIGHT FIXTURE - REFER TO FIXTURE SCHEDULE.
-Q JUNCTION BOX, WALL MOUNTED. FIELD VERIFY MOUNTING HEIGHT PRIOR TO ROUGH -IN.
METER PEDESTAL REFER TO SINGLE LINE DIAGRAM.
CONDUIT RUN CONCEALED, IN WALLS, FLOOR, OR ABOVE CEILING.
- - - CONDUIT RUN CONCEALED BELOW GRADE, 3/4"C MINIMUM.
X CONDUIT RUN EXPOSED
FA 3/4" CONDUIT WITH FIRE ALARM CONDUCTORS. SEE FIRE ALARM RISER DIAGRAM
CONDUIT STUB OUT, CAP & MARK.
PROVIDE METER PEDEST
BRANCH CIRCUIT WIRING, 2 #12 IN 1/2" CONDUCT OR AS NOTED OR SYMBOLIZED
z.
1/2"C-3 #12
1/2"C-6 #12
1/2"C-4 #12
3/4"C-7 #12
--{{-}•---- 1/2"C-5 #12
3/4"C-8 #12
3
E-1
DETAIL CALLOUT, "3" INDICATES DETAIL
NUMBER "E-1" INDICATES SHEET NUMBER.
PHOTO CELL
PLAN NOTE REFERENCE.
•• N
w_
Q
REVISION REFERENCE.
CO
CONDUIT ONLY, WITH PULL ROPE.
MH
MOUNTING HEIGHT
WP
WEATHERPROOF, NEMA 3R
in
PROVIDE
FURNISH, INSTALLED AND CONNECTED,
COMPLETE.
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
o
I
EM
EMERGENCY
NL
NIGHT LIGHT
¢
C
CONDUIT
E/G
EQUIPMENT GROUND (GREEN)
UG
UNDERGROUND
GEC
GROUNDING ELECTRODE CONDUCTOR
N.E.C.
NATIONAL ELECTRICAL CODE
U.O.N.
UNLESS OTHERWISE NOTED
Q�OF�SS/
O
T.
No. E6122
Exp. 9/30/02
FOF,Fo4'
J�as_4,
ELECTRICAL * ENERGY CONSULTANTS
JDSA JOB NUMM 98-471
CONTACT NAME CHRIS • JENNINGS
3780 Twelfth Street * Suite B * Mmmide, CA. 92501
Telephone (909) 787-1957 * Fox (909) 787-8602
PROVIDE METER PEDEST
L
z.
PANEL, PACIFIC UTILITY ODUCTS
WITH SPACE FOR (1 ANNEL
24 H TIME SWITC
AND 1) 20A -1P
�
PHOTO CELL
CONTACTOR.
•• N
w_
ti.
100A R SOCKET S.C.E.
Q
120/ OV., 10, 3W WITH TEST
in
.
N
Q
o
I
�
•
•
N
� W
V
OA "T" TYPE FUSED SWITCH.
¢
6 CIRCUIT PANEL.
ZW
INSTALL DETACHABLE PAD MOUNT
W
1/2m x 10' COPPER
FINISHED GRADE
GROUNDING ROD.
PROVIDE CLAMP &
as
BOND TO PEDESTAL
GROUND BUS.
;'
'.
: . is
s:
m
®
o
J�as_4,
ELECTRICAL * ENERGY CONSULTANTS
JDSA JOB NUMM 98-471
CONTACT NAME CHRIS • JENNINGS
3780 Twelfth Street * Suite B * Mmmide, CA. 92501
Telephone (909) 787-1957 * Fox (909) 787-8602
PROVIDE 4' C.O. TO EDISON VICE
PUILBOX. INSTALL PER UTILI
COMPANY REQUIREMENTS
"MPA" DETAIL
ti
J
O
V
w
c
SCALE
N.T.S. Z File N0.
l7 _14-2880 13 of 1L{
PROVIDE METER PEDEST
PANEL, PACIFIC UTILITY ODUCTS
WITH SPACE FOR (1 ANNEL
24 H TIME SWITC
AND 1) 20A -1P
PHOTO CELL
CONTACTOR.
100A R SOCKET S.C.E.
120/ OV., 10, 3W WITH TEST
BL
o
I
OA "T" TYPE FUSED SWITCH.
¢
6 CIRCUIT PANEL.
INSTALL DETACHABLE PAD MOUNT
SLEEVE IN CONCRETE.
1/2m x 10' COPPER
FINISHED GRADE
GROUNDING ROD.
PROVIDE CLAMP &
BOND TO PEDESTAL
GROUND BUS.
;'
'.
: . is
ON
• o
1
w
BRANCH CIRC CONDUITS.
PROVIDE CONCR E. 2000 #
Ir
AT 28 DAYS PER R IREMENTS OF
EQUIPMENT MANUFACT R SIZE VERIFY EXACT
SIZE OF FOUNDATION P TO ROUGH -IN.
PROVIDE 4' C.O. TO EDISON VICE
PUILBOX. INSTALL PER UTILI
COMPANY REQUIREMENTS
"MPA" DETAIL
ti
J
O
V
w
c
SCALE
N.T.S. Z File N0.
l7 _14-2880 13 of 1L{