HomeMy WebLinkAbout3079-21- - - . ��4 � ..- , I--,----,_ I - , '- - - - � - � � - - - , � - �---- - - --- - - �- - __ � , ____` -, , '_ -1
- , � . . -_ � I I
I - � . . I
- ,
� '.
. , I - I � � -
. -
-
. .
. .
. I . . I .
I
.
. . -
. .
. � . . � I .
�
.
. � .
.
I
�
-
1. I � /-/ - -sim __ mv� \ � . .. � ___ /
. ,
I
1; _. /,/- .1 I :
/ / �
/ I" �
___ If F
/ It'
/ I .
/ .1
I
I
I i
. I
ELECTRICAL SPECIFICATIONS
.
SECTION 16010 --GENERAL REQUIREMENTS
C0
. .
I Part 1 -GENERAL . � I
.
�_
Z
- '
. 1.1 GENERAL REQUIREMENTS .
.
- A. It is the responsibility of 'the contractor to obtain and thoroughly review
Z
construction drawings and specifications that pertain to this project where
9
i
requirements for electrical construction exist in other drawings and
0
I speciftotions the contractor shall include these in the bid.
U
0
B. The contractor shall furnish and install all material, labor, and equipment
.
. I necessary for a complete and operable electrical system.
<
at
C. The electrical drawings which constitute an integral part of this contract,
��
(ire schematic and they are intended to indicate a general layout of the
r�
electrical system. The actual field, conditions of construction, including the
I
I work of the other trades 'Involved in the construction, will dictate the
-
exact methods and materials to be used. The contractor is responsible
.
I to adequately review the plans and work of the other trades to assure
-0-4
I
that the work is properly coordinated with others. � .
.
(=>
I
ke)
1.2 CODES, STANDARDS, AND PERMITS
. �
A. The construction of the contractor shall be in accordance with all
f
4..,
4 #
applicable codes and standards of governing agencies. As a minimum
construction shall comply with the current adopted edition of the National
�W-4
Electrical Code, State of California Title 24, State Building Standards,
00 -
C-�
Occupational Safety and Health Administration (OSHA) requirements, State
�:)
for California Title 17 and to all local codes having jurisdiction. In the
U
� I
case where codes have different level of requirements, the most stringent
W
regulation shall apply.
0
B. The contractor shall obtain and pay for all permits and inspections that
(74)
\.../
I
are required for completion of the construction. Obtain certific ' ates of
�
I
approval as required by authorities and submit to the architect for final
Z
acceptance of the electrical work.
C. The contractor is responsible to secure all inspections required by the
�.4
governing agency and will be held responsible for any work that is not -
'P,
accepted. .
I
1.3 WORKMANSHIP
kn
The contractor shall be responsible to use experienced personnel who are
fully competent. and familiar with proper installation techniques and with
the manufacturers' recommendations relative to the products that are
used. As a minimum, a standard apply to these personnel shall be
equivalent to that of a licensed electrician. The contractor shall be fully
r ... 4
Ible for the work methods and safety of these personnel. In the
responsi
I
14
acceptance or rejection of the finished installation, no allowance will be
. made for the 1:ack af skill on behalf of 1the personnel.
.
:
. . 1.4 CONSTRUCTION REVIEW -
.
, ves the right to Visit the Job site for the purpose of
i -
determining that the work of the contractor is in general compliance with
the intent of the construction documents. However, the engineer assumes
-no responsibility or liability relative to 'Inspections or approvals of the
work completed or lin progress during such visits.
. - . .
I 1 �5 SCHEDULE OF WORK .
A. The contractor shall be responsible for the scheduling of his work to
meet the required completion date and shall also coordinate with other
contractors so that the overall project can be accomplished on schedule.
. B. When product -submittals are required as defined in subsequent sections
. of this specification, the contractor shall allow (15) calendar days for
the engineer to review the submittals of the specified products. If the
. contractor is seeking a substitution of any products,- he shall allow an
additional (15) calendar days for review time. The contractor is
Ible to arrange these lead times such that they do not delay the
responsi
completion of the project.
-C. .Irnmediately upon the award of contract the contractor shall coordinate
I
the suppliers of intended materials and products to be used in
� ,with .
- . construction to verify that delivery of these materials and products will
not impact the completion date of construction.
1.6 SUBSTITUTIONS .
�
Products -are specified in the drawings by manufacturer and part number
shall be used in the construction unless the contractor receives prior
* i
. written approval for *substitution. In the event that the contractor wishes
to seek approval for substitutions he shall submit the manufacturers'
shop drawings or cut sheet to the engineer allowing at least (15) days
.
review time. The engineer, reserves the right to approve or deny the
substitution request. . ..
. I
1.7 SUBMITTALS
Immediately after award of contract and before ordering any products or
materials, the contractor shall submit the required submittals of products
11
for the review of the engineer as indicated in subsequent sections of this
specification. The review by the engineer of these submittals is for
checking the conformance with the design concept of the pro*eUC.-11..
1.8 AS -BUILT DRAWINGS �
During the progress of the work the contractor shall maintain an accurate
record of the installation of the system on �1 as -built" drawings which will
I be submitted at the completion of the construction. All entries of these
. drawings are to be accurate and shall include -all deviations from the
contract drawings. The final- submittal shall be in reproducible format.
' �
I
I
1.9 CLE ANING
4
All exposed parts of electrical equipment shall be completely and
thoroughly cleaned and free from cement, plaster, paint, etc. All
scratches- are to be reffnished in an acceptable manner.
- �
I 1.10 WARRANTY AND GUARANTEE .
The contractor shall guarantee the entire electrical works are working
Rhout defect within one year from the date of acceptance
properly wi
. of th e work. Any defect related to the contractor's work during the
w.&rantee period shall be at the contractor"s expense.
1.11 UTILITY COMPANY SERVICES
A. As required, the contractor shall coordinate with the utility company to
install temporary power during construction. All costs associated with
. Installation of temporary power are to be included in the bid.
B. All voltage, phases, and ampacity of the electrical service shall be shown
. on the drawings. Other information indicated on drawings relative to
4
utility company requirements is preliminary, and 'is subjected to change
by the utility company. The contractor is fully responsible for the use of
any information that is not in the form of a final construction drawing
*
: issued b the utility company for final use on the project. Prior to the
y i
. . .
I bid of the project, the contra-ctor shall coordinate with the utility
. 4
. .10
company and determine exact materials and equipment required by th.,
I . utility company in order to complete their installation of final services.
this cost shall be included in the bid. If this information is not available
: , to the lbontractor prior to the bid, costs con be estimated and shall be
specified as estimated" In the bid. Under no circumstances will the ...
"
contractor be rilieved from his obligation to provide for the utility
' i
company requirements whether or not they shown -on the drawings.
. Furthermore, the contractor -shall not be eligible for any additional
charges to the owner relative to utility company requirements.
.
. PART 2 -PRODUCTS
* .
V PRODUCT AND MATERIALS
A.- All products and materials used 'in the project shall be new and delivered
.
to the job site in the original packaging. -
f B. All materials used and furnished for which UL Standards have been
: established shall be listed ond bear the label of Underwriters
- laboratories, Inc.
C. Prior to ordering any lighting fixtures, service and distribution equipment,
*.
. transfarhers, wiring devices, dimming cabinets and systems, and/or
; .
! *
! emergency power equipment, the contractor shall submit manufacturers'-
- . catalogs and/or shop drawings to the engineer for approval. this
. requirement is required to check whether or not' the contractor truly
: � Ify proper drawings, equipments, part numbers, and manufacturers,
. speci
etc... . Eight (8) copies are required to be submitted for review. The
: contractor will be when the review 18 completed and at such
�
.notifled
: time, the contractor may order material and produtts.
. . I I .
PART 3 -TESTING AND ADJUSTING OF ELECTRICAL SYSTEM
. . I
. .
.
.
.
. 3.1 SYSTEMS AND EQUIPMENT TESTING .
: Control systems for outdoor lighting, dimming systems for indoor lighting,
.
q -
: master controls for lighting systems, and emergency power systems
: t,gral r
: i . ..(,whether in in fixtures, by 'Inverter/battery sets, and/or generators)
i
i
! I
.. -shall be thoroughly tested during installation, and these systems shall be
I ; I
!
! tested at the completion of construction in the presencd of the owner,
; �
i
, ;
i architect, and, enaineer.
I -
3.2 GROUND TESTING
It is the responsibility of the contractor to assure the 'Integrity of the
grounding system throughout the project and it 'is mandatory that the
entire system be thoroughly tested. It is also mandatory that the main
.. electrical service ground bus be tested by a licensed electrician utilizing
-
� methods and equipment that are acceptable by members of the trade, A
: 'tten record of this testing shall be made by the contractor indicating
,
,
, wri ,
the time and date of the test, the name of the person conduciing the
test, the equipment and method used, and this record shall be kept by
the contractor and made available to the engineer upon request for a
period of (3) years following completion of the construction.
I
�
�
. .
.
3.4 VOLTAGE ADJUSTING .
A. The contractor shall be responsible to coordinate testing of the main
'
service utilization voltage. In the case of 120/240 volt systems the -
,
volt 17 volts +/- 3 volts on each phase to neutral.
in the case of 480Y/277 volt systems the voltage shall test at 270
volts +/- 7 volts on each phase to neutral. This testing shall be
conducted with a main service load of 25% by turning "on",lighting and
I
air conditioning equipment during the test. The actual voltages of each
phase after adjusting and as determined in (3) separate tests shall be
�
0
recorded and reported to the engineer in written form.
B. In the case of 120/240 volt services where the main disconnect exceeds
2000 amps or 480Y/277 volt services where the main disconnect exceeds
1000 amps' the voltage testing shall be conducted with a recording
voltmeter indicating a 24 hour record of the actual voltages on all phases
during the first 24 hour period that the facility is in operation. The
. contractor shall coordinate the time and date of this requirement with the
owner, architect, or engineer, and submit the results of the testing to the
4
engineer. This testing shall verify utilization voltages as indicated in
. "Section A." above.
C. In the case of sub distribution transformers the contractor shall be
ible to assure proper secondary voltage with the same testing
responsi
techniques described in "Section A." above.
...
.
-
15 GFI AND GFCI �QUIPMENT TESTING '
A. All GF1 circuit breakers and GFI convenience outlets shall be thoroughly
tested during install'ation and at the completion of the project.
B. If the main electrical service includes GFCI protection, then the contractor
0
1 . shall test this equipment 'in the presence of the inspector at the
completion of the project. It shall be the responsibility of the contractor
. to notify the inspector when this test will be performed and allow the
inspector at least make arrangements to be present.
SECTION 16100 --BASIC MATERIALS AND METHODS
.
�
PART 1 -GENERAL .
�
1.1 QUALITY ASSURANCE
The contractor is responsible to assure that all material and equipment
delivered to the job site are new and in proper usable condition. All
materials and products used are to be inspected and may be rejected if
found to be defective or flowed. It shall be the responsibility of the
contractor to assure that this' element of the specifications 'is
satisfactorily completed. The owner, architects, and engineers reserve the
'
right to reject any materials or equipment that deem to be flowed or
defective In the finished project. . .
.
1.2 PRODUCT AND EQUIPMENT VERIFICATION
A. The contractor shall be responsible to check all products and equipment
4
that is specified in the drawings when it is received at the job site to
assure that it is in fact compatible with the electrical plans based upon
the enclosed manufacturers' instructions including any instructions or
4
information placed on the products and equipment.
B. In the case of service and distribution equipment the contractor shall
verify that the nameplates agree with the approved shop drawings relative
to voltage, phase, bus ampacity, short circuit and/or AIC rating, and
enclosure type.
C. In the case of sub distribution trans'formers the contractor shall verify
that the nameplates agree with the specified voltage to voltage ratlingk
impedance, heat rise, enclosure type, and sound 'rating.
� I
,D. In the case of lighting fixtures, the contractor shall verify the fixture is
rated for the specified lamp, the specified input voltage, the specified
mounting and/or installation application, and the specified control system.
E. In the case of motors the contractor shall verify the proper input voltage
and phase, FLA, recommended fuse size, and installation application,
based upon the attached nameplate. -
-
PART 2 -PRODUCTS I .
. .
I
. 2.1 CONDUIT GENERAL
A. All conductors and wiring are to be installed in conduit unless the
drawings clearly state that conduit is not required and that the use
of an approved cable is permitted. Conduits are to be concealed in all
finished areas. The conduits shall be continuous terminating only in
4
junction boxes, panels, approved wireways, etc. Where metallic conduits
establish grounds, they shall be installed such that continuity shall be
maintained.
B. Where nonmetallic conduit is used M construction, the contractor shall
include a ground conductor In the run whether or not shown on the
drawings and the conduit shall be sized accordingly.
2.2 RIGID N-ONMETALLIC CONDUIT (RNMC)
RNMC may only be used underground or in or below concrete slabs when
used for conductors of 110 volts or higher. Conduit shall be polyvinyl
chloride schedule 40, electrical conduit, rated 90 degrees C. Only
i
approved electrical fittings may be used. Where run in concrete maintain
a minimum of 4" of cover on all sides, and convert to rigid galvanized
ste'el stubout of concrete. Any conduit and fittings' installed for the use
of a utility company shall meet the requirements of the utility company
for such installations except that in the case of conduit for high voltage
feeders (600 volts or above) the contractor shall take special precaution
- to provide safety to persons excavating around and about the installation.
'it is the responsibility of the contractor to provide for this protection but
It is recommended that one or more of the following methods be utilized:
concrete encasement .of at least two inches of concrete on all sides of
the conduit; concrete or concrete slurry three or more 'Inches deep on
top of conduit; three or more inches of sand on top of conduit and
redwood planks run continuously on sand; a warning tape manufactured
for direct burial placed six inches above the conduits.
2.3 RIGID METAL CONDUIT (RMC) .
A. Steel RMC shall be mild steel, hot dipped galvanized inside and outside,
i connectors shall be tapered pipe thread. running
threads and split couplings are not permitted.
B. When used underground the conduit and fittings and couplings -shall be
i
moisture protected. "Tapecoat CT" protective spiral wrap with
recommended primer treatment.
2.4 ELECTRICAL METALLIC TUBING (EMT)
EMT shall be mild steel, electrically welded and galvanized per ANSI
#C80.3. In damp locations fittings shall be gland compression type -
malleable iron. In dry locations fittings shall be all steel, zinc plated,
screw set type.
2.5 FLEXIBLE METAL CONDUIT (FMC)
FMC shall be steel or aluminum with UL listing. Fittings shall be steel or
. .
malleable iron threaded. I I
.
.
2.6 PULL AND JUNCTION BOXES
A. Boxes are to be installed in all conduit runs 'in sufficient number to meet
the requirements of codes, special requirements of utility companies,
4.
requirements of providers of special equipment and systems, and to allow
for efficient and convenient installation of conductors. It is the
responsibility of the contractor to locate these boxes and size them
according -to code requirements. Boxes shown on the drawings are to be
installed as shown but do not necessarily indicated all boxes necessary
#
for any installation, Boxes 'Installed in outdoor or wet locations shall be
*
of the type approved for the purpose.
B. Boxes instolled indoors shall be coded with gouge steel, galvanized on
all surfaces, with removable covers and secured with machine screws.
-
they shall b' orted by mechanical connection 'to the
structure of the building. They shall be located such -that they are readily
* '
accessible for . -maintenance purposes. All junction boxes in branch circuits
shall be marked on the cover with the circuit identifications. .
Boxes used in the utility site system, covers shall be marked Electrical,
Telephone, or CATV as appropriate. Concrete boxes shall be install on a
6" crushed rock 15ase. The contractor shall coordinate the finished
elevation* with the specific conditions of the 'installation. In general the
cQn1rac1or shall attempt to locate boxes such that they are as visually
-
. -
un.9 "ble.
,0-trusive as possi
.,
. .
-1
;�, I I .- I : I : . �� - . � - I i I I
� . . i
. . � . - ( I . - �
_. � . . __ - _ - .
.
.
.
I
-
.
I
.
I .
. I
-
i . .
. C. Boxes where exposed to weather shall be weatherproof and rain tight and,
shall be fabricated of minimum 14 gouge sh el and hot -dip galvanized
- after fabrication. Covers are to be properly gasketed and set- with
stainless steel screws. Covers are to be stainless steel or brass. Visible
covers are to be left with a clean factory finish.
0
D. Boxes located outdoors in landscape or in traffic areas, shall be precasted
Ith concrete as manufactured by Brooks or Qulkset. The covers of these
wi
ropriate'to their specific location. Boxes used 'in the .
� utility site system, covers shall ' be marked Electric, Telephone, or CATV as.
' i
appropriate. Concrete boxes shal'i be installed on a 6" crushed rock base.
The contractor shall coordinate the finished elevation with the specific
conditions of the installation. In general the contractor shall attempt to
locate boxes such that they are as visually unobtrusive as possible.
I
E. Boxes 'are located in wet areas shall be installed with conduits in boxes
such that they are' protected from intrusion of water. Furthermore, if
there 'is a possibility that water con enter buildings or equipment by
entering into conduits owing to grades and elevations, the contractor
shall make the engineer aware of this field condition prior to completion
of the installation so a engineer to take appropriate
�
actions and protective measures. .
-
. 2.7 OUTLE T BOXE S
'
� A� Outlet boxes shall be installed with extensions and rings properly
coordinated for the surrounding finishes. The final 'installation shall render
all outlet boxes flush and even with the finished surfa.ce. In all cases
these boxes shall have a finished appearance acceptable to the owner,
architect, and engineer. - �
B. The minimum size for outlet boxes is 4"' square by 1.5' deep.
C. Where outlet boxes contain wiring' of different voltages, the contractor
. shall provide approved barriers within the boxes. Where switches are
.
shown adjacent to one another on the drawings, these switches are to .
. be installed in multiple ganged boxes and Ahe finish rings are to be .
coordinated with standard available cover plates. An exception is where
dimmers are shown that Will be provide with their own cover plates
and/or heat sinks. In this event these will be located in separate outlet
*
boxes of appropriate size such that the finished centerline of adjacent
'
cover plates are symmetrical about a horizontal common axis.
D. In the ' event that outlet boxes are to be used to support fixtures the
contractor is responsible to install boxes with adequate structural .
4
integrity to allow for the support of the fixture. If the contractor
I
requires any assistance, he shall notify the engineer of the situation
te time for the engineer * to resolve the structural
problem prior to the completion of the installation.
.
2.8 CONDUCTORS .
A. The contractor shall be responsible to install all conductors used on the
project 'in compliance with Article 310 of the NEC. In the event that
. the contractor receives approval from the inspector to u-11.1lize insulation
types other than those shown on the drawings he shall pay particular
attention to ensure that these conductors are properly sized.
B. Conductors used as service entrance conductors, to subfeed switchboards,
6
panels, transformers, and other equipment, where the wire sizes are #6
and larger shall be installed with the wire size, insulation class, and
voltage rating 'indications on the insulation visible without touching the
. conductors from the front of the connections, .
C1. Where conductors of multiple phases are- pulled through the some
conduit to feed more than one equipment they shall be color coded.
these colors shall be permanent and consistent for the entire run. The
choice of colors is the option of the contractor except that grounds
shall be green and neutrals shall be white. '
D. The contractor may gather runs of conductors based on field decisions,
but shall comply with the applicable code requirements.
E� Conductors #12 AWC and smaller shall be solid. Conductors #8AWG and
larger shall be stranded. The minimum wire size to be used is #1.2 AWG.
the minimum insulation rating shall be 600 volts.
F. In no event may aluminum conductors of #6 AWG and smaller be used.
Where the drawings indicate the use of copper conductors, then only
copper conductors may be used. In cases where the contractor utilizes
aluminum conductors, the contractor shall be responsible to install these
conductors such that he guarantees the some quality of the system as if
he had installed copper conductors. All conductors used in fixture troughs,
stems,and ballast compartments shall be insul-ation type THHN/THWN.
G. Type SE, style SER cable is constructed with XHHW conductors primarily used
as panel feeder in multiple un! ' t dwellings. SER may be used in wet locations
i
eed 75'C and 90'C in dry locations. Voltage rating is - 60OV.
H. NMC (Nonmetallic Sheathed Cable) is primarily used in residential wiring as
branch circuits in one and two family dwellings, multifamily dwelling Ond other
structures, except as prohibited in NEC Section ,336-4
2.9 CONNE CTORS .
A. Copper conductors for wire sizes #10 AWO and smaller shall be spliced
utilizing "spring -lock" connectors, in particular, "Scotch lock"' by 3M or
"Wing Nuts" by Ideal. The contractor is responsible to assure that all
splices are completed in a secure and permanent fashion, maintain - ing
the integrity of the connection without faults or shorts. In cases where
the conductors may be affected by adverse conditions the contractor
shall take special precaution to protect the conductors such as by
wrapping connectors with an appropriate tape.
B. Copper conductors for wire sizes #8 AWC and larger shall be made with
. approved split bolt connectors. These types of uninsulated connections
- shall be thoroughly protected with applied insulation such as 3M #2200
or #2210 vinyl mastic insulating pods.
C. Aluminum conductors when used shall employ as few splices as possible.
This means that the contractor shall be responsible to show suitable
ices within a run. The location of these splices as
installed by the contractor shall be indicated in the "as -built" drawings.
Aluminum conductors shall be terminated or spliced with swage type .
aluminum compression terminals, and shall be accomplished in strict
adherence with the 'Instructions of the manufacturer of the ma-terial. .
connections shall be protected as indicated in "B" above.
D. Connections made in outdoor locations shall be insulated with 3M #2200
or #2210 vinyl mastic insulating pads to protect from moisture.
PART 3 -EXECUTION .
3,1 TRENCHING / E XCAVATI ON .
*
Where specifications appear in the architectural portion of the .
ifications that pertain to trenching and backfilling, the contractor is
sped 1 1 1
ible to review these specifica t ions and comply. In the absence of
responsi I
other specifications, the contractor shall:
1. Comply with the NEC relative to the minimum depths of conduits,
and shall comply with any utility company requirements relative to
these depths,
2. Maintain a minimum of 12 inches separation between: 0-600 volt
feeders, and over 600 volt feeders; and low voltage (telephone, alarm,
$ 1
i
communications, CAT -V, oth4�r Class 2 conductors, etc.); and non
electrical installations (water, gas, drains, sewers, etc.). This condition
-shall apply to joint trench situations and to conditions where trenches
� -
cross.
3. Each layer of backfill shall be compacted to a minimum density of
90% and the top 6" shall be compacted to 95% maximum density.
. It is the responsibility of the contractor to pr�oviide verification that
this condition is accomplished.
4. Upon completion of backfill and compacting the contractor shall leave
the site in the same condition that it was at the commencement of
the work. This requirement 'Includes replacement of any damaged
landscape .materials, asphalt, concrete, other pavements and finish
mdter*ials, fences, lawns, trees, etc. Additionally, the contractor shall
be responsible for any damage to other 'Installations su*ch as sprinkler
. lines, and the like. If the contractor feels that damage to other .
is unavoidable then it is his responsibility to bring this to the -
attention of the engineer prior to any specific work to allow the
II
engineer to designate corrective procedures,
�
5. .Upon completion of the trenching and backfill the contractor is
responsible to remove any excess dirt, rock, and other debris from
the Job site.
SECTION 16400 --SERVICE AND DISTRIBUTION EQUIPMENT
- PART 1- GENERAL .
1.1 EQUIPMENT
'
*
A. The service and distribution equipment shown on the drawings do not
'
i
indicate the names of specific manufacturers, This equipment shall be
manufactured by recognized manufacturers and shall comply with all
applicable codes and standards. The contractor shall study the dimensions
of proposed manufacturers and verify that the equipment will physically-
. fit in the spaces intended. This is to be accomplished prior to bid of
th , e project. If there is a problem discovered relative to the dimensions
of p-roposed equfpry�ent, the contractor shall contact the engineer and -_ - -
develop a solution prior to the bid. If this condition is not met for any
reason then the* contractor shall be responsible to work within the
allowed limitations as indicated on the drawings by utilizing substitude
�
- - .:- - __ 4. : A-_ 4.- 10 .& _*U_ 41k� 0' � __.� .0m% ,ft A 'a t�^ .-% W. ,m ,
lu4u IV' I I c;' I t. In o�IUVf LV I i 1. VY i U I ki IV V,A10 1.11 IV Ulf I I V1 10i1%';1'1G;.
- � .
.
16
.
B. In. cases of remodel construction, the contractor shall make himself
adequately aware of the existing conditions on the Job site relative to
any retro -fit switches, circuit breakers, 'etc., that are required. It is the
. 4
ibility of the contractor to determine what specific equipment W III
responsi 1 1
be required for the Installation and include all such equipment in the bid.
C. The contractor shall be responsible to coordinate with the electric
utility to provide 'equipment that is satisfactory for their requirements.
�
1
1.2 QUALITY ASSURANCE
All service and distribution equipment shall be approved by a testing
laboratory recognized by the code enforcing authority and bear the
'
approval label of that laboratory with a perm nd engraved
placard. Additionally, all service and distribution -equipment shall have
P ermanently placed on it a permanently engraved placard nameplate
indicating the name of the manufacturer, the manufacturers serial number,
the voltage, phase, and ampacity of the specific equipment.
1
1.3 S.UBMITTALS .
The contractor shall submit (8) copies ' of the manufacturers shop
drawings for each main electrical service, distribution board, switchboard,
panel board, load center, transformer, motor control center, and any
other service and distribution equipment. Prior to any fabrication,
manufacturing, or ordering of equipment, the contractor shall have copies
approved by the engineer in his possession. .
1.4 SCHEDULE AND DELIVERY . .
The contractor is responsible to obtain approvals and secure delivery
of all contractual related works (i.e. drawings, equipment, etc...) in
conformance with the construction schedule.
PART 2 -PRODUCTS
.
.
2A MAIN SERVICE EQUIPMENT
Unless indicated otherwise on the drawings, the main service equipment
shall be a freestanding, deadfront, deadrear, sheetmetal assembly with
factory applied paint finish. The contractor is responsible to verify size
of pull section-, and other utility requirements, with the serving utility
11
and provide the required equipment. The equipment will utilize fuses or
circuit breakers as shown on the drawings unless the contractor obtains
the written permission of the engineer to utilize alternative configurations.
If there is no short circuit. rating indicated on the drawings, the.
*
contractor shall coordinate the required rating with the serving utility.
If the utility indicates, 'in writing, a short circuit rating less than that
I
shown on the drawings then the contractor may provide for the lesser
I .
requirement but he is responsible to .submit to the engineer a copy of
the written verification proVided by the utility. The main, and all subfeed
I breakers 'and switch,es are to be identified with a permanently affixed
"I
engraved phenolic no m-eplate and all switches and breakers are to be
lockable "off'. Any equipment shown outdoors shall be rated for wet
. location. Where fuses are shown in the main service, the contractor shall
spare fuses in each size to the owner at the
i
conclusion of the work.
.
.
2.2 PANEL BOARDS AND LOAD CENTERS . '
A. When the drawings *Indicate the use of panel boards then th
0
included. Otherwise load centers may be used. All panels used on a
particular job shall be of the same manufacturer. If there is no indication
spaces that is to be provided on the panel then it
shall be a full size 42 spaces panel. Circuit breakers shall be full size
breakers, tandem type breakers are not to be used. All panels shall bear
the label of a code enforcing authority approved test laboratory, and shall
have affixed by the manufacturer a permanently engraved and attached
*
nameplate indicating the panel rating. Additionally, there shall be affixed
to the panel a phenolic engraved nameplate indicating the panel name
.
and voltage/phase (i.e., ."Pl-120/24OV-1 PH"). A typewritten circuit
schedule shall be prepared and mounted in a plastic cover in the panel.
B. Circuit breakers shall be molded case, quick make, quick break, with trip
indicator, and interrupting rating shall equal the rating of the load
.
-
1
2.3 OTHER EQUIPMENT I
I
Other equipment which includes transformers, disconnect switches, motor
control centers, transfer switches, inverters, generator sets, dimming
panels, custom control cabinets, and motor starters, shall bear the label
of a recognized test lob, and have nameplates as indicated in B. above.
PART 3 -EXECUTION
.
�
'
3.1 EQUIPMENT INSTALLATION
In all cases the contractor shall install service and distribution equipment
'
�
in such a manner that the equ � ipment is reasonably protected from
adverse conditions and damage. Main service equipment that is shown
- outdoor shall be installed on a concrete pad at least four inches thick,
and at a finished elevation above the water level (which shall be at or
above the elevation of man doors into the structure). When the main
4
service equipment is not located on or adjacent to a structure, the
finished elevation of the pad shall be field verified to be above anticipated
water levels and the pad shall be set four inches above the finished
adjacent surface. All main service equipment shall be bolted tp the pad
or floor on which it Is located.
.
3.2 GROUNDING
A. The main service ground bus shall be grounded in compliance with the
i
requirements of the code enforcing autho"rity and by the following methods.-
*
1. Metallic cold water pipe .-- 250-81(c)
1
'
2. 20 feet of #4 bare copper wire -- 250-81(c) I
. 3. If metal frame building to the structural frame !--- 250-81(b)
B. The resistance measured from the main service neutral bus to the I
asured with dry ground conditions,
C. The secondary side of transformers shall be grounded per section 250-26.
D. Non metallic conduits shall contain a . ground conductor per 250-95.
E. Flexible metal conduits shall contain a ground conductor equal in size
to the largest conductor,
SECTION 16600- -LIGHTING- FIXTURES -
.
*
PART 1 -GENERAL
1.1 E QUIPME NT
Lighting fixtures as indicated in the drawings shall be furnished by the
contractor, except as indicated in the "SUBSTITUTIONS" section that
1 4 1 '
follows. The contractor is responsible to coordinate with the manufa
of specified fixtures and assure that submittals for approvals and
subsequent orders and delivery dates will not conflict with the Job
�
schedule. The contractor shall apply the following procedure to the
ordering of light fixtures: 11
1. If the contractor is planning to request substitution of light fixtures
he shall discuss this in detail with the engineer before the -bid. At that
#
time the engineer will inform the contractor if there are any restriction
to substitution of particular fixtures. However, no approval of substitution
ill be made until all conditions of the "SUBSTITUTION" section that
wi I I
follows are met. .
. 2. The contractor shall maintain complete and accurate documentation of
communications with the suppliers. 1
3. The contractor shall request fixture submittals for the approval of the
11
engineer within (5) days of notification of the award of , contract and
shall verify that the submittals hove been received by the engineer,
and allow for (15) days review time.
4. The confirmed order for the purchase of the fixtures shall be placed
'thin an adequate time period to allow for the timely delivery of the
wi 1 1
fixtures. If there is to be a delay in the delivery the contractor shall
�
make every reasonable attempt td' inform the engineer of the delay
at the soonest possible time. As a minimum, the contractor 'is to
secure a confirm delivery date from the manufacturer at the time of
ordering and follow up on this delivery date periodically until the order
0 i
is received by the contractor.
5. In the event that there is to be a delay in delivery the contractor is
to make available to the engineer all of the written records pertaining
to the order.- � .
.-
.
1.2 - SUBSTITUTIONS .
A. Request for $ substitution of light fixtures requires the prior approval
of the engineer. The contractor shall furnish the engineer with (8) copies
4
of the intended fixture catalog sheets and allow the engineer (15) days
i
review time, The engineer reserves the right to refuse the submittals.
B. Fixtures submitted for substitution shall be of the same general
pecified, The -engineer reserves the right to make this
determination. Any special characteristics of the specified fixture shall be
included in the proposed substitution such as special lenses, reflectors, -
ballast, etc.
.
0. In the case of outdoor pole mounted fixtures there may exist a
0
.1
requirement for submittal of site photometry which shall depict a point -
by point light level summary on centers approved by the engineer, � and
indication of the minimum maintained average footcandle level for the
is submittal shall be made concurrently with the \
'
submittal of the manufacturers catalog sheets if required by the engineer,
and it Is the responsibility of the contractor to account for this
i
requirement relative to the.timing. .
.
SECTION 16000 -- ELECTRICAL SPECIFICATIONS �
1.3 QUALITY ASSURANCE . : _ .. . ... . . -
A. Lighting fixtures shall be *manufactured by a 'r600gnilzed mariufa�Nrer
and bear the approval label of a test lob recognized by th i e c a�-d e
� enforcing agency. Additionally, this label shall conform to the specific
location of 'Installation such as "damp" or "wet". . /
B. Where fixtures are 'Installed on a surface of-loW dem§ity mat, ' brials they
shall -be approved for such installation or be spaced a minimum of
1 Inch from the surface. The contrac.tor is responsib-le to field verify
this requirement. .
C. Where fixtures such as open strip fluorescence are installed in
architectural features such as coffers, valences, and the like, the
contractor shall install the fixtures such that the lamps are not Visible
from view. If this condition cannot be met based on field conditions,
the contractor shall notify the engineer -allowing sufficient time for
corrective action before the completion of the installation.
D. All fixtures shown on the drawings are to be furnished with all necess&y
i v nd accessories, In all cases the contractor Is
responsible to install fixtures with proper and appropriate structural
support. . I
E. Lamps shall be provided for all fixtures. Where spocific lam,.ps are
indicated in the drawings these lamps shall be pr6vided. 'W -here general
specification of lamps are given they shall be General Electric or a
manufacturer approved by the engineer prior to purchase.
F. The contractor shall exercise care when handling and 'Installing fixtures
to protect finishes and lenses and other visible components. The owner,
architect, and engineer reserve the right to reject any damaged- or
.
flawed materials and products. I .
I
-
I
I .
;
.
2.1 HIGH INTENSITY DISCHARGE FIXTURES
Ballast for the fixtures shall be:
Mercury Vapor -.- constant wattage autotransformer (CWA)
Metal Halide -- CWA
High Pressure 'Sodium -_ high power factor or CWA
Low Pressure Sodium -- high power factor
For outdoor applications, the minimum starting temperature rating
shall be at least -20 degrees F. The ballast shall be manufactured by
a recognized manufacturer and bear the label of an approved*test lab
'
appropriate to the location of the fixture, Ballast will be considered
faulty if the noise emitted exceeds that of other fixtures of I the some
type installed on the job and will be replaced at the directive of the
I
# .
engineer. The engineer reserves the right to reject lamps that show
noticeable color shifts,
-
1
2.2 FLUORESCENT LIGHT FIXTURES -
Fluorescent fixtures shall contain "P" rated ballast with "A" sound
rating I un - less specified otherwise, they shall be manufactured by a
-recognized manufacturer and bear the label .of an approved test lab
1
4
appropriate to the location of the fixture, and be certified by Certified
Ballast Manufacturers Association (COM).'The ballast shall be considered -
faulty if the sound emitted exceeds that of other fixtures of the some
type on the job and will be replaced at the directive of the engineer.
unless specified otherwise the lens shall be acrylic plastic. For fixtures
�
located in wet or damp locations the ballast shall be low temperature
with a rating olf 0 degrees F or lower. Power factors shall be at least.
9 unless specified otherwise.
END
Im
1�t __
I 1-, �, - _-Qk_Z _1
I � ., _:�,"__ .1% __
11 X � "3 ";" ".", ,-
, , A X 1 --,.-
,- NKIV D -S 11 40 "' , I
'. - I A
""' - , N , � r.�r,,
,,rr' Iffl tf, __ -_ - I ,2
.. 5) lle�i!�� -, Z Jir - �� -
X,
1, r, I - V - -, -,cerg--,-kz�z --Z-
_ -kl 14-- , "
� - 2M I .
� 411% ���_ I- jA . 'If , V� , � .
� � rre, .4 � -,
i I 6 , � J!,
F <_ 9 , � � I
- � 1 1_,_7!7�� I, 11 .1 I i �� '.
" �� , : _N - .. awl, , .
"I . , - � V 01 -� 'I,
I
_P11 9 94 g)-789 . I � I
I 1, I I Z. , � . 1
4, �Z ��
, A -/! - , 2b I -Z�
1. ,
r� f .- ��� 1 (:__7 ;
!, I
11 I I I %-,r . ,
-,-_� �,�-,� 14
�, a �- . -- *. - ,�,
I .. ` - �, i
�' �__ ______ "
�, ,, ,4�',V, �
� -
� - I
. - 'I ,
. �
. -
,
- 1 J
, �� "I * F � / "
I Z r) I
. .
.
r
'
Landscape Architecture
and Planning I
La '
nd
T
SCI
'E
13
ndP -
5
e
F ,
I �J
19762 MOcArthur Blvd., Ste. 130
Irvine, CA. 92,612
, 3
Richard Polhamus, License CA -#2782
�
(949) 644-9370 (949) 476-1432 FAX
��
I
-
0
41!�
C0
U
�_
Z
;Z
W
�_
4_�
U
Z
a
9
1.10
0
C/�l
T1
U
0
0
�>
00
r,
_<� I
<
at
10.4
��
r_=4
0�
r�
-C!�
0
iw-4
0
0 r-,
Cd
Cd
. P..q
t ---
C-�
��
Q
0
-0-4
I
�0
(=>
I
ke)
f
4..,
U�0
�W-4
. V.-4
Cd
00 -
C-�
�:)
rl:�
U
,,.�
C� ,
C)
W
Zr-4
0
r6
0
-
(74)
\.../
��
lm�
Z
M
� V)
�.4
�10
'P,
I
kn
�)
I
I
r___4
r ... 4
I
I � - 11-
1�1 I - , , 1 ,-- 1) I
, ,� .
- - .1 wal�_ - � - ___ � ____
"
�r_.,, ', 10� 0 f; � 1) - , -, r' DWN CHK
� -i ____'_ . " I ,- .1-
I -4 ..... I-- - - N_ .. �� ,
,
"
''I'll, IP'N,-, - .,N&O VIT I " 11
. , m V, _.
',N� I IV- ., CB/HD/MM SS/RP
J - ... � I I
_- __ Z� ,� -, It
, -,, - /11 - - - Alv , �
- - -- -
. , ____ - _ -
I
,
�
11; - r. ,r, �
",.--;-;., �. 0� Z _.;:�_ -
� _A �,
-
''. I 1'__ iF.0,t- r � V 1) , ,_ -
- ". � -IN ,�--,.
� I � _ I � DATE
, I _-
, _
___:�, I Ili - I - -1 ,
, � . J
I _ � I ___ -------- " V,,_ I
.� _1__,!______11�_
:__
.i -:2" : � � 10/12/00
1
1 - �
�
-
I
�
. "I * 00-019
�
.
.
�
I
.
(CATY OF FONTANA I
.
.
I
.
.
.
-
I .
.
.
.
�
. .
i
DRAWN BY, . SCALE, I I
�
�
.
.
.
I -
. ,- �
DESIGNED BY, DATE,
.
.
I
/J) A09 r � . I
I M
�
I I - � � - - _ . .. .
01 I �
I I I CHECKED BY, 111_� - Ail I D BY, 41 an ar-0 M. No., . - - I
. I .Z �� 1P DATEi
�; \ 00 V10 - 3 bll of 2Q,_.1'J I
10* � �N EER R.C.E. P5126 EXP. DATE 12/31/9 - . [ , . _ I -_ --- .. . .
- I r%0 -1 � � I I
�_,__ C I , 11 q Ty, ,ql� . 11. .. . -11
.. , - . !�. k��Jw ` " �. , . . . . . . - � -
.
� " .L�r'.,,�,,pj�k �" . . I
I k__ I . . Tr �-
N � I
I
I . I . �: ,; , � .
, I � �', 2'12
_ I , . . . I Ij I . � - ;� I I .
- 11 ..�� �
�W_�2 I I -,'I � . , .
. .- I .1 � � - � .
11� .� i i, � " � _.�, I �_,, I I I - _; , - I
- , , _ .1 I . . - I . -
� �. ,',� I I �,, , �) - I . _:_ T, � -, I � ) - . � I �� 1
- �, . - � " . ___. . ,,,, � . _ - - �, �, - I
� .1 - 4W, �, , - j , �,
I
, , X", - �� - __ - - _� -,��' �___ - - _L�_ - � �, " 011A IZZ: " . i_ .--: ,�, .- .
, , -
I - _16--.1- 6 � ,_,�'A_ , ._,?�-�,�,, ,;�. , , � � .
lm�
F-01
41!�
C0
U
�_
Z
10_�
4-ol
W
�_
4_�
U
Z
4�
0
P-ol
0
U�
Z
�
lo -4
�:
_<� I
<
at
- U
a
� �
� F -0i
U *
W
. I __
-
lo -4
� . . ,
- W
I � - 11-
1�1 I - , , 1 ,-- 1) I
, ,� .
- - .1 wal�_ - � - ___ � ____
"
�r_.,, ', 10� 0 f; � 1) - , -, r' DWN CHK
� -i ____'_ . " I ,- .1-
I -4 ..... I-- - - N_ .. �� ,
,
"
''I'll, IP'N,-, - .,N&O VIT I " 11
. , m V, _.
',N� I IV- ., CB/HD/MM SS/RP
J - ... � I I
_- __ Z� ,� -, It
, -,, - /11 - - - Alv , �
- - -- -
. , ____ - _ -
I
,
�
11; - r. ,r, �
",.--;-;., �. 0� Z _.;:�_ -
� _A �,
-
''. I 1'__ iF.0,t- r � V 1) , ,_ -
- ". � -IN ,�--,.
� I � _ I � DATE
, I _-
, _
___:�, I Ili - I - -1 ,
, � . J
I _ � I ___ -------- " V,,_ I
.� _1__,!______11�_
:__
.i -:2" : � � 10/12/00
1
1 - �
�
-
I
�
. "I * 00-019
�
.
.
�
I
.
(CATY OF FONTANA I
.
.
I
.
.
.
-
I .
.
.
.
�
. .
i
DRAWN BY, . SCALE, I I
�
�
.
.
.
I -
. ,- �
DESIGNED BY, DATE,
.
.
I
/J) A09 r � . I
I M
�
I I - � � - - _ . .. .
01 I �
I I I CHECKED BY, 111_� - Ail I D BY, 41 an ar-0 M. No., . - - I
. I .Z �� 1P DATEi
�; \ 00 V10 - 3 bll of 2Q,_.1'J I
10* � �N EER R.C.E. P5126 EXP. DATE 12/31/9 - . [ , . _ I -_ --- .. . .
- I r%0 -1 � � I I
�_,__ C I , 11 q Ty, ,ql� . 11. .. . -11
.. , - . !�. k��Jw ` " �. , . . . . . . - � -
.
� " .L�r'.,,�,,pj�k �" . . I
I k__ I . . Tr �-
N � I
I
I . I . �: ,; , � .
, I � �', 2'12
_ I , . . . I Ij I . � - ;� I I .
- 11 ..�� �
�W_�2 I I -,'I � . , .
. .- I .1 � � - � .
11� .� i i, � " � _.�, I �_,, I I I - _; , - I
- , , _ .1 I . . - I . -
� �. ,',� I I �,, , �) - I . _:_ T, � -, I � ) - . � I �� 1
- �, . - � " . ___. . ,,,, � . _ - - �, �, - I
� .1 - 4W, �, , - j , �,
I
, , X", - �� - __ - - _� -,��' �___ - - _L�_ - � �, " 011A IZZ: " . i_ .--: ,�, .- .
, , -
I - _16--.1- 6 � ,_,�'A_ , ._,?�-�,�,, ,;�. , , � � .