HomeMy WebLinkAbout2745-8A----\ SECTION
CONNECT
TO EXIST=
SUMP PIPING
4" FLANGED x VICTAULIC
GROOVED
STD. WT. WSP SPOOL
4" VICTAULIC GROOVE
x PLAIN END
STD. WT. WSP SPOOL
BUTT STRAP
A
t
'
BUTT STRAP
rn
6J
4x4 CHECK VALVE
3
s
GATE VALVE
4" VtCTAULIC GROOVE
VICTAUUC COUPUNC
O6
x PLAIN END
DEHUMIDIFIER
O8
STD. WT. WSP SPOOL
SUMP PUMP
10
4" FLANGED x VICTAUUC
VENTILATION FAN
11
GROOVED
ELECTRICAL CONOWT
STD. WT. WSP SPOOL
cFtmT: UF" TM
LDK JOB is 124-04
.SCALE: 1 "=1'
00
DRY WELL DETAIL
SCALE: 11"=10
Underground Service AI ort
SECTION 4216/4217 OF THE GOVERNMENT
CODE REQUIRES A DIG ALERT IDENTIFICATION
NUMBER BE ISSUED BEFORE A PERMIT TO
EXCAVATE WILL BE VALID
FOR YOUR DIG ALERT I.D. NUMBER CALL
UNDERGROUND SERVICE ALERT
TOLL FREE 1—WO-227-2600
TWO WORKING DAYS BEFORE YOU DIG
CONNECT TO
EXISTING FLANGE
CONNECT TO
EXISTING FLAN
BLAST AND RECOAT THE INTERIOR
AND EXPOSED EXTERIOR DRYWELL
SURFACES IN ACCORDANCE WITH
THE COATING & P"T= TECHWft4L
SPECIFICATIONS.
REMOVE:
AO 4x4 CHECK VALVE
B GATE VALVE
C
DEHUMIDIFIER
VENTILATION FAN
E SUMP PUMP
OF ELECTRICAL CONDUIT (AFTER
NEW SYSTEM IS OPERATIONAL)
OG AIR COMPRESSOR
OH ELECTRICAL PANEL
INSTALL:
1
NEW
4x4 CHECK VALVE
3
NEW
GATE VALVE
O4
VICTAUUC COUPUNC
O6
NEW
DEHUMIDIFIER
O8
NEW
SUMP PUMP
10
NEW
VENTILATION FAN
11
NEW
ELECTRICAL CONOWT
PROTECT IN PLACE:
2 SFIP PUMPMG UNITS
5 4' SUCTION PIPE
1 LADDER -ADD APPROVED NON -SUP
SURFACE TO STEPS AFTER
RECOAl1NG
313 Alit DUCT
14 FORCEMAIN
EDISON SERVICE
120/240
#2137825E
Construction Notes and Legend:
�� ■�� INSTALL CONDUIT (SIZE AS INDICATED)
EXISTING CONDUIT
EO EXISTING SERVICE PEDESTAL TO BE
REMOVED AFTER NEW SYSTEM IS
OPERATIONAL
0 INSTALL SERVICE CABINET WITH
ELECTRICAL COMPONENTS
30 LIFT STATION, SEE DETAIL HEREON
EXISTING PULL BOX
Notes:
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE
LIFT STATION SPECIFICATIONS.
2. CONTRACTOR SHALL MAINTAIN SEWER SERVICE AT ALL TD ES
DURING CONSTRUCTION.
3. CONTRACTOR SHALL PREPARE A DETAILED WORK PLAN PRIOR
TO BEGINNING CONSTRUCTION AND SUBMIT IT TO THE CITY
FOR ACCEPTANCE. THE PLAN SHALL SPECIFY THE CONSTRUCTION
SEQUENCE.
4. CONTRACTOR SHALL SALVAGE OR RECYCLE ALL LIFT STATION
EQUIPMENT REMOVED. CONTRACTOR SHALL FURNISH CITY WRITTEN
DOCUMENTATION THAT SAID EQUIPMENT HAS BEEN SALVAGED
OR RECYCLED.
5. CONTRACTOR TO LOCATE AND REROUTE EXISTING TELEPHONE LINE
TO NEW SERVICE CABINET, AND CONNECT TO EXISTING TELEMETRY
SYSTEM IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
6. CONTRACTOR SHALL COORDINATE NEW ELECTRICAL SERVICE WITH
S.C. EDSION. CONTRACTOR SHALL COMPLETE ALL APPLICATION
7. BUBBLER SYSTEM 3/8" TUBING SHALL EXTEND FROM PANEL TO
EXISTING TUBING WITHIN DRY WELL.. FOR BELOW GROUND INSTALLATION,
INSTALL TUBING WITHIN CONDUIT.
8. ALL CONDUITS SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE (SIZE AND MATERIAL). CONDUITS SHALL BE MOUNTED WITHIN
DRY WELL IN ACCORDANCE WITH STANDARD SPECIFICATION, SECTION 86.
9. REPLACE HATCH SEAL GASKET
3"C PULL ROPE
SIt?EWAtK
.d a.
DIRT
rJ
a `e
PROTECT EXISTING
N DP AGROUND CONDUIT LOCUST STREET
T
3 / EXISTING VET 'LL
a.
LIFT STATION SITE PLAN
SCALE: 1 "=10'
Lr)lcinG SUITE 100B
1 OB n� CENTER WAY
ONTARIO, CA 91764
(909) 937-0200
� No.44228 � Sd
E�.8-30-01 r _ _ A /) /� f / � Ld)'
CF MICHAEL PATRICK THORNTON R.C.E. No. 44226
oA7E ENGR. DATE EXPIRES: 6-30-01
z
3 PHAK 4 IELEPHONE Lpa
120/240 VOLT
MEIER
EMERGENCY MANUAL HP X 746
GENERATOR TRANSFER
RECEPTACLE SNATCH AMM as X E X X X W
180/aP - 7460
1.73 X 220 X 75X X . IEIEMEIERM SYS M0
AMPS - 26
ALTMAIOR
6�/3P RELAY
6ory2P
Tfl
10 CONTROL SYS mm
LLVIL
8� -
60S
II
ALTERNATOR
STA Rm msT 2
3/sr
AIR OM
H
W
W
F-
N
J
O
Z
H
DETAILS
FOR
IMPROVEMemTS
LOCUST AVE. LIFT STATION
ELECTRICAL SCHEMATIC
AS t
v�
>
2ECTIR"",.
G
16-31
SLAT ._. _ _ _.
DATE
CITY OF FONTANA, CALIFORNIA
MARYGOLD AVE. /ALDER AVE. SEWER
CCP UFT STATION DETAILS AS SHOWdw mmm 81f.DATE:
CCP/.N T NOV., 19
0lE0QM W. BY: DATE: MAW= 141L.
DHM • �- o '1% rfm"'/ 27411
1100-5