ELECTRICAL
UCTION 16000
PART I- GENE
1.01 DESCRIPTION
A. Related Requirements: Review the General Conditions,
Standard Specifications and Special Provisions which contain
information and requirements that apply to this Section.
B. Work Included: Provide all electrical work for a complete
and operable system as shown on the drawings and as
specified in this section including, but not limited to the
following:
1. Site investigations prior to bidding to establish
existing conditions.
2. Temporary power and lighting facilities for
construction.
3. Electrical underground service at 120/240 volt, single
phase, three (3) wire services.
4. Service metering and distribution system for lighting
power connections to one hundred -twenty (120) volt
irrigation controller.
5. Lighting fixtures, mounting hardware, poles,
foundations and pull boxes.
6. Provide wire, pull boxes and conduit extensions as
required.
7. Adjustment and test of the electrical work.
8. Guarantee.
C. Related Work in other Sections:
Irrigation - Section 02810 (1.10 Connections To Utilities)
Concrete - Section 201 & 303.
1.02 QUALITY ASSURANCE
A. All products and equipment herein specified or indicated on
the drawings shall be new with UL label and in accordance
with the National Electrical Code, state and local codes.
B. Applicable Standards:
1. General Conditions, Special Provisions, Exhibit "A" and
Appendix 1.
1.03 SITE VISITATIONS
A. Prior to the submission of the bid, the contractor shall
visit the site and make a thorough examination of the
existing conditions and thereby include allowances for this
work in this bid.
1.04 PERMITS AND LICENSES
A. Contractor shall pay for and obtain all necessary permits,
inspections, insurance and licenses required for the
Electrical work.
1.05 COORDINATION
A. Contractor to coordinate the electrical work with other
trades. Review drawings and specifications of all equipment
requiring electrical connections prior to installation of
the electrical system. Verify space, ventilation and
clearances required to install electrical equipment.
1.06 SUBMITTALS
A. Product data sheets for meter pedestal, meter, panelboard,
lighting fixtures poles, wiring devices, and material list.
Make all submittals at one time in booklet form.
B. Record Drawings:
1. Installation Record: During the course of
installation, carefully show in red line on a print of
the electrical system drawings all changes made to the
electrical system during installation.
2. Dimension Standards: Dimension from easily
identifiable permanent features (buildings, monuments,
sidewalks, pavements, etc.) points of connection,
wiring routing, conduit locations, all stub -up
locations and other related equipment as directed by
the Agency's Authorized Representative.
3. Deliverables: Upon completion of the electrical system
installation, submit two (2) sets of redlined record
data prints to the Agency's Authorized Representative
for approval prior to transferring information onto the
signed original mylar.
4. Submittal of Record Set: Upon completion of the
electrical system installation, and as a condition of
its acceptance, deliver to the Agency's Authorized
Representative, in Record Drawings referred to above.
The delivery of the Record Drawings shall not relieve
the Contractor of the Responsibility of furnishing
required information that may have been omitted.
1.07 SUBSTITUTIONS
A. Where manufacturer's name and catalog number are called out,
the phase "or approved equal,, can be assumed except the
burden of providing equality is on the bidder.
1.08 GUARANTEE
A. All electrical work and equipment shall be guaranteed for
one year from the date of acceptance on contractor's
letterhead and turned over to the Agency at the completion
and final acceptance of the job.
PART 2,- PRODUCTS
2.01 UNDERGROUND SERVICE PEDESTAL
A. Meter pedestal "MP" shall be NEMA 3R 120/240 volt, single
phase, three (3) wire with one hundred (100) amp., two -pole
main circuit breaker rated forty-two thousand (42,000) AIC.
The service shall be a free-standing pre -wired pedestal
assembly. Pedestal shall have underground pull section
meter (without test blocks) and main disconnect. Pedestal
shall comply with the requirements of the serving utility.
Install black on white micarta nameplates on all sections,
switches and spaces. Provide rodent screens. Pedestal
shall be Meyars or approved equal, model numbers are
indicated on the drawings. Bolt to concrete pad.
2.02 SWITCHES
A. Switches shall be quick -make, quick -break type QMB rated six
hundred (600) volts with frame size, number of poles and
fuses as shown.
2.03 CIRCUIT BREAKERS
Circuit breakers shall be bolt -on molded case type with
thermal magnetic strips. Provide with rated voltage, frame
size, number of poles and trip setting as shown. NEMA
interrupting capacity shall be 42,000 AIC at 120/240 volts
unless otherwise noted on plans.
2.04 PANELBOARDS
A. Panelboards shall be surface mounted in pedestal, with Bolt-
on circuit breakers type NQOB, with hinged lockable doors
and typewritten directories. All multi -pole breakers shall
be single handle common type. Use "SWD" circuit breakers
for lighting circuits controlled from panels. Manufacturer
shall be G.E., Square D, Westinghouse or Challenger.
2.05 WIRE
A. Conduit shall be six hundred (600) volt insulation type
THWN/THHN copper.
2.06 CONDUIT
A. Conduit shall be rigid steel galvanized for exposed or in
damp locations. Conduit underground shall be PVC schedule
40 with ground wire, minimum twenty-four (24) inches below
grade unless noted otherwise.
2.07 CONDUCTORS
A. Conductors shall be six hundred (600) volt insulation, type
THHN/THWN copper.
2.08 SPLICES
A. Splices on conductors #8 or smaller shall be Skotchloc
spring connectors and for larger size cables use solderless
connectors.
B. Splices below grade shall be epoxy encapsulated "3M" or
approved equal.
2.09 AREA LIGHTING
A. Lighting fixtures shall be two hundred fifty (250) watt,
high pressure sodium, with acord laxan diffuser;
manufactured by Western Lighting Standards (Fixture
Catalogue No.: FXB130) or approved equal.
Paint color: black
B. Poles shall be sixteen (16) feet high, four (4) inch
diameter steel pole, manufactured by Western Lighting
Standards (Pole Catalogue No.: RSS-416 BC) or approved
equal.
Paint color: black
C. Refer to drawing for concrete pole base.
PART 3 - EXECUTION
A. Obstructions: The contractor's attention is directed to the
existence of pipe and other underground improvements which
may or may not be shown on plans. All reasonable
precautions shall be taken to preserve and protect any such
improvements whether shown improvements in order to
prosecute the work, they shall be removed, maintained in
operation, and permanently replaced by the contractor at his
expense.
B. Trenching: Trenches shall be excavated to the lines and
grades established by the engineer. Bottom of trenches
graded and prepared to provide a firm and uniform bearing
throughout the entire length of conduit runs.
1. Trench Bottoms: Made more stable by wetting and
tramping where fills are required and brought to a
uniform grade.
2. Minimum Trench Depth: Sufficient to provide a minimum
cover twenty-four (24) inches above topmost portions of
conduits.
3.02 CONDUIT AND WIRING
A. All conduit and wiring shall be installed underground in
accordance with applicable regulations and the electrical
drawings. Conduit runs are shown diagrammatically. Exact
routing and location of the equipment to be determined in
the field by the Agency's representative. Provide one
thousand two hundred (1,200) lb. test pull cord in each
empty conduit and cap both ends.
3.03 EXTERIOR EQUIPMENT
A. All equipment and wiring to be weatherproof, including
rodent screens.
3.04 GROUNDING
A. All metallic conduits, supports and enclosures shall be
grounded in compliance with the National Electrical Code.
3.05 ELECTRICAL SERVICE FACILITIES
A. Electrical service and metering facilities shall be
installed in compliance with all requirements of the
Southern California Edison Company.
3.06 TESTING
A. All new circuits shall be tested for short and open circuit
to ground with a megger; resistance to ground shall be in
compliance with the requirements of the National Electrical
code.
B. All lighting fixtures with adjustable aiming shall be
verified at night in the presence of the Agency's Authorized
Representative to comply with the manufacturer's aiming
diagram to the satisfaction of the Agency's Authorized
Representative.
***END OF SECTION***
SOCCER
FIELD 1
SMALL
0
PD1
SOFTBALL
FIELD
a
PD4
BASKETBALL
COURTS 1
0
PD4
SOCCER
FIELD 2
LARGE
a
PD2
TENNIS
COURTS 1
0
PD5
BASKETBALL
COURTS 2
0
PD5
BASEBALL
FIELD
a
PD3
TENNIS
COURTS 2
0
P06
EXTENDED
OCCUPANCY
OVERRIDE
0
PD6
SWITCH STATION ELEVATION.
MOUNTED ON PANEL DOOR
NOTE:
1. LIGHTING CONTROL PANEL PL400 AS MANUFACTURED
BY TOMSTAR CONTROLS INC., BRENTWOOD, CA
(510)634-5500
2. LOADS CONTROLLED BY SWITCHES PD1-PD6 SHALL
BE STAGGERED ON IN 1 SECOND INTERVALS.
LOW VOLTAGE
EXTERIOR
PHOTOCELL
4#18
TYPICAL OF
2 OUTPUTS
ARP C-1� GAZEBO / FLAGPOLE / SIGNS
C-13 SNACK BAR LIGHTS
LOW VOLTAGE
SWITCH
�-- 318
TENNIS COURTS 1
LIGHTS
�
3�t4
LIGHTING CONTROL
PANEL
LCP
*AUTO
ZONE
LOW VOLTAGE SWITCH
DESCRIPTION / NOTES
C-597,9,11,13,15,21,23925,2733,35,4,6,8,10
32t34
480
MOUNTED REMOTELY
1
LVSC-1
TENNIS COURTS 2x
LIGHTS
C-17,19, 29, 31, 33,35912A,14A9121B914B,16,
1 8,20 22 36 38,40,42
314
PD2
1
LOW VOLTAGE SWITCH
SOCCER FIELD 2 (LARGE)
C-1,3,5,7,9,1 1,13915,17,19,21923,25927,
29 31 4 6
480
MOUNTED REMOTELY
1
LVSC-1
BASKETBALL COURTS 1�
OVERRRIDE
C-12,14,16,18,20,22,24,26,28,30,
32 34 36 38 40 42 29 31 33 35
3#14
PD4
1
LOW VOLTAGE SWITCH
SOFTBALL FIELD
A-12,14
480
MOUNTED REMOTELY
1
LVSC-1
BASKETBALL COURTS 2
LIGHTS
A-16,18
314
PD6
1
LOW VOLTAGE SWITCH
TENNIS COURTS 2
A-496
480
MOUNTED REMOTELY
1
LVSC-1
CONTACTOR CONTROL
PANEL
CCP
NOTE:
1. EXTENDED OCCUPANCY OVERRIDE PROVIDES FOR SWITCHES
THE ABILITY TO EXTEND NORMAL HOURS MOUNTED ON
OF OPERATION FOR LIGHTING. PANEL DOOR
SEE ELEVATION
DETAIL THIS
SHEET
BREAKER
PANEL
LIGHTING CONTROLS WIRING DIAGRAM +
EQUIPMENT ELEVATION
NO SCALE
CONTROL PANEL - LCP
LOCATIONS: SNACK BAR BUILDING PANEL TYPE: MAIN
CONTROL VOLTAGE: 120V MOUNTING: SURFACE
CONTROL CIRCUIT: C-17 NEMA TYPE: 1
CIRCUIT #
*VOLTS
SW/ZONE
LABEL
*AUTO
ZONE
CONTROL
TYPE
DESCRIPTION / NOTES
C-597,9,11,13,15,21,23925,2733,35,4,6,8,10
32t34
480
PD1
1
LVSC-1
SOCCER FIELD 1 (SMALL)
C-17,19, 29, 31, 33,35912A,14A9121B914B,16,
1 8,20 22 36 38,40,42
480
PD2
1
LVSC-1
SOCCER FIELD 2 (LARGE)
C-1,3,5,7,9,1 1,13915,17,19,21923,25927,
29 31 4 6
480
PD3
1
LVSC-1
BASEBALL FIELD
C-12,14,16,18,20,22,24,26,28,30,
32 34 36 38 40 42 29 31 33 35
480
PD4
1
LVSC-1
SOFTBALL FIELD
A-12,14
480
PD5
1
LVSC-1
TENNIS COURTS 1
A-16,18
480
PD6
1
LVSC-1
TENNIS COURTS 2
A-496
480
PD5
1
LVSC-1
BASKETBALL COURTS 1
A-8,10
480
PD6
1
LVSC -1
BASKETBALL COURTS 2
C-1,3,5,7
480
---
1
LVSC-1
EXTERIOR / PARKING LIGHTS
* REFER TO PANEL AUTOMATIC LIGHTING CONTROL ZONES
** PD =IN PANEL DOOR
*** EACH 480V CIRCUIT TO BE COUNTED AS 2 POLES ON A 4 POLE CONTACTOR.
AUTOMATIC CONTROL SCHEDULE
ZONE
ZONE DESCRIPTION
TIME
CHANNEL
OPERATIONS NOTES
1
BALL FIELDS, SNACK BAR dt
GAZEBO LIGHTS
1
MANUAL ON
AFTER HOURS SHUT-OFF EVERY TWO HOURS
2
SPARE
2
3
EXTERIOR / PARKING LIGHTS
--
PHOTOCELL ON / PHOTOCELL OFF
V
R
a
Z
O
LL
LL
O
H
V
o�
wQ'
�a
W UJ
co
a
X
W
A
U)
N
W
U
W
W
Z
0
Z
W
m �
W U
DATE
SuamInA' 2-1-91
Z.-ZA REv1Ew
r-r7T-,
Mo -
TEL
DAIS
2-25-91
e0AW
NONE
.ion "M
1122
4e