HomeMy WebLinkAbout2421A-1GENERAL NOTES:
1. THE ENTIRE WATER SYSTEM SHALL CONFORM TO THE SPECIFICATIONS
AND REQUIREMENTS OF THE WATER PURVEYOR.
2. ALL WATER MAINS SHALL BE INSTALLED WITH 42" MINIMUM COVER.
3. FIRE HYDRANT LOCATIONS SHALL CONFORM TO THE STANDARD DRAWINGS
OF THE FOOTHILL FIRE DISTRICT STANDARDS AND SPECIFICATIONS.
4. WATER CONTRACTOR SHALL ADJUST STREET VALVE BOX AND COVERS TO
GRADE AFTER COMPLETION OF PAVING.
5. ALL WATER LINES SHALL BE WELDED STEEL PIPE OR DUCTILE IRON PIPE
WITH COATINGS AND LININGS PER THE BASIC PIPELINE SPECIFICATIONS.
6. SAND BEDDING AND SAND BACKFILL IN PIPE ZONE IS REQUIRED
UNLESS NATIVE MATERIAL IS SUITABLE AS DETERMINED BY THE
WATER PURVEYOR.
7. CONTRACTOR IS RESPONSIBLE FOR SECURING FROM THE WATER
PURVEYOR COPIES OF THE STANDARD SPECIFICATIONS FOR CORRECT
INSTALLATIONS OF THE PROPOSED WATER SYSTEM.
6. WATER METERS SHALL BE INSTALLED AS NOTED.
9. PRESSURE REGULATING VALVES ARE REQUIRED FOR EACH LOT WHERE THE
WATER SYSTEM PRESSURE EXCEEDS 80 P.S.I. (SEE NOTE #3)
10. SEPARATION BETWEEN WATER MAINS AND SANITARY SEWER MAINS SHALL
CONFORM TO THE STATE OFCALIFORNIA ENVIRONMENTAL HEALTH CODE,
TITLE 22, SECTION 64630-C.
11. PRIOR TO THE ACTIVATION OF ANY NEWLY CONTRUCTED WATER
LINE, TESTING AND DISINFECTION SHALL BE PERFORMED TO COMPLY
WITH WATER PURVEYORS STANDARDS.
12. THE CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH THE SITE AND
SHALL BE SOLELY RESPONSIBLE FOR ANY DAMAGE TO EXISTING
FACILITIES RESULTING DIRECTLY OR INDIRECTLY FROM HIS OPERATIONS,
WHETHER OR NOT SUCH FACILITIES ARE SHOWN ON THESE PLANS.
13. CONTRACTOR SHALL OBTAIN A PERMIT FROM THE CITY OF FONTANA
PRIOR TO ANY CONSTRUCTION WITHIN THE STREET RIGHT-OF-
WAY.
14. ANY CHANGES IN WATER LINE DEPTH OR CHANGES CONCERNING
CONSTRUCTION SHALL BE REPORTED TO AND APPROVED, IN ADVANCE,
BY THE WATER PURVEYOR.
15. APPROVAL OF THESE DRAWINGS BY THE WATER PURVEYOR DOES NOT
CONSTITUTE A REPRESENTATION OF THE ACCURACY OR THE
EXISTENCE OF ANY UNDERGROUND FACILITY.
16. LANDSCAPE SYSTEMS SHALL HAVE AN APPROVED REDUCED PRESSURE
BACKFLOW DEVICE ASSEMBLY INSTALLED AS A MINIMUM BACKFLOW
PROTECTION REQUIREMENT.
17. AT LEAST 10 DAYS IN ADVANCE, OR A MINIMUM OF 1,000 FEET
AHEAD OF TRENCHING, CONTRACTOR SHALL EXCAVATE, EXPOSE, AND
DETERMINE ("POTHOLE") THE EXACT LOCATION AND DEPTH 'OF EACH
AND EVERY POTENTIAL INTERFERENCE AND CONNECTION, INCLUDING,
BUT NOT LIMITED TO, ALL FACILITIES SHOWN SPECIFICALLY (DEPTH
AND LOCATION) ON THESE DRAWINGS, OR WHICH HAVE BEEN MARKED
BY THEIR RESPECTIVE OWNERS. CHANGES OR DELAYS CAUSED BY
CONTRACTOR'S FAILURE TO PERFORM "POTHOLING" AND INTERFERENCE
LOCATION WORK SHALL NOT BE ELIGIBLE FOR EXTRA WORK COMPEN-
SATION OR TIME EXTENSION.
18. DEVELOPER SHALL SUPPLY THE WATER PURVEYOR FIVE SET'S OF
APPROVED DRAWINGS A MINIMUM OF TWO WEEKS PRIOR TO
CONSTRUCTION.
19. DEVELOPER, PIPELINE CONTRACTOR, AND SUPERINTENDENT SHALL.
ATTEND A PRE -CONSTRUCTION MEETING WITH WATER PURVEYOR A
MINIMUM OF TWO WEEKS PRIOR TO BEGINNING CONSTRUCTION.
20. CONTRACTOR SHALL NOTIFY WATER PURVEYOR (909-350-6631) AT
LEAST 48 HOURS PRIOR TO BEGINNING CONSTRUCTION.
21. CONTRACTOR SHALL FURNISH CITY WITH TWO COPIES OF THE
FOLLOWING DATA AND SAID DATA SHALL BE APPROVED BY THE
CITY PRIOR TO BEGINNING OF WATERLINE CONSTRUCTION. ONCE
APPROVED, CONTRACTOR SHALL SUBMIT FIVE COPIES OF APPROVED
DATA TO CITY FOR USE DURING CONSTRUCTION: a) ALL DATA
ON TRENCH PROTECTION, CONSTRUCTION SCHEDULE, AND ENCROACH-
MENT AND EXCAVATION PERMITS. b) ALL DATA ON WATER SERVICE
MATERIALS, PIPE, FIRE HYDRANTS, VALVES, AIR VALVES, FITTINGS,
PORTLAND, CEMENT CONCRETE MATERIALS, AND ASPHALT CONCRETE
PAVEMENT MATERIALS.
22. CONTRACTOR SHALL SOLID WELD OR PROVIDE RESTRAINED GASKETS
FOR ALL JOINTS TROUGHOUT A CURVE IF THE RADIUS IS LESS THAN
455' FOR 40' LENGTHS OF PIPE AND 266' FOR 20' LENGTHS OF PIPE.
23. SEPARATION BETWEEN WATER SERVICES AND SEWER LATERALS
SHALL BE 10 FEET MINIMUM.
24. BEFORE MAKING ANY EXCAVATION OR TRENCH 5 FEET OR MORE
IN DEPTH, CONTRACTOR SHALL SUBMIT TO WATER PURVEYOR A
DETAILED DRAWING SHOWING THE DESIGN OF SHORING, BRACING,
SLOPING, OR OTHER PROVISIONS TO BE MADE FOR WORKER PROTECTION.
IF SAID DRAWING DOES NOT VARY FROM REQUIREMENT OF THE
OSHA CONSTRUCTION SAFETY ORDERS (CAL OSHA OR FED OSHA,
WHICHEVER IS APPICABLE AT THE TIME OF CONSTRUCTION), A
STATEMENT SIGNED BY A REGISTERED CIVIL ENGINEER, ENGAGED
BY CONTRACTOR AT HIS EXPENSE, SHALL BE SUBMITTED CERTIFYING
THEAT THE CONTRACTOR'S EXCAVATION SAFETY DRAWINGS COMPLY
WITH OSHA CONSTRUCTION SAFETY ORDERS. IF SAID DRAWING
VARIES FROM SAID OSHA CONSTRUCTION SAFETY ORDERS, THE
DRAWINGS SHALL BE PREPARED AND CERTIFIED BY A REGISTERED
CIVIL OR STRUCTURAL ENGINEER, AND SAID ENGINEER SHALL AFFIX
HIS SEAL AND SIGNATURE TO EACH OF SAID DRAWING.
CONTRACTOR SHALL NOT EXCAVATE UNTIL CITY HAS RECEIVED AND
ACKNOWLEDGED THE PROPERLY CERTIFIED EXCAVATION SAFETY
DRAWINGS.
HUNTER'S RIDGE
WATER IMPROVEMENT PLANS
TRACT N0. 1457 1 AND 14571- 1
25.
CUT SHEETS SHALL BE PREPARED SHOWING FLOWLINE ELEVATION
QUANTITY
1" X 2" HUB WITH WITNESS LATHE SHALL BE SET ALONG PIPELINE
DESCRIPTION
UNIT
ALIGNMENT. DEVELOPER SHALL FURNISH CITY WITH FOUR SETS OF
TRACT NO. *
CUT SHEETS FURNISHED A MINIMUM OF TWO WORKING DAYS PRIOR
14571
14571-1
TO CONSTRUCTION. CONTRACTOR SHALL NOT BEGIN EXCAVATION
OCONSTRUCT
8" I.D. STEEL PIPE CML do C PER
UNTIL CITY HAS APPROVED SAID CUT SHEETS. CONSTRUCTION
2,432
LF
STAKING SHALL BE AT 50 FOOT MINIMUM INTERVALS, VALVES, FIRE
CITY OF FONTANA STD. SPECIFICATIONS.
HYDRANTS, AIR VALVES, BLOWOFFS, FITTINGS, SERVICES, AND CONNECTION
O2
LOCATIONS. CONTRACTOR SHALL USE THE CONSTRUCTION STAKES
3
7
AND CUT SHEETS FOR CONSTRUCTION. CITY WILL USE THEM FOR
�3
CONSTRUCT 8" TEE.
INSPECTION OF THE WORK. CONTRACTOR SHALL PROTECT ALL
3
EA
SURVEY MONUMENTS AND STAKES DURING CONSTRUCTION.
CONSTRUCT 8" X 45' ELBOW.
26.
ALL CONSTRUCTION REQUIRING CITY INSPECTION SHALL OCCUR
EA
O
7:00 A.M. TO 5:00 P.M. MONDAY THROUGH FRIDAY, EXCEPT HOLIDAYS.
1
2
DEVELOPER SHALL REIMBURSE WATER PURVEYOR FOR ALL INSPECTION
�6
CONSTRUCT 1" A/V RELEASE VALVE PER STD. DWG. If W117.
EXPENSES. ALL MATERIALS AND EQUIPMENT FURNISHED AND ALL
2
EA
WORK PERFORMED SHALL BE SUBJECT TO RIGID INSPECTION BY THE
CONSTRUCT 1" SERVICE LINE PER STD. DWG. # W126.
30
WATER PURVEYOR. WORK PERFORMED IN THE ABSENCE OF THE INSPECTOR MAY
EA
�8
BE REQUIRED TO BE REMOVED AND REPLACED UNDER PROPER IN-
2
5
SPECTION, WITH ENTIRE COST OF REMOVAL AND REPLACEMENT BEING
�9
CONSTRUCT 8" FLANGE AND BLIND FLANGE.
BORNE BY THE CONTRACTOR, EVEN IF SUCH WORK IS NOT DEFECTIVE.
5
EA
WORK COVERED UP WITHOUT AUTHORITY OF THE WATER PURVEYOR SHALL, UPON
REMOVE BLIND FLANGE, THRUST BLOCK, AND JOIN.
4
ORDER OF THE WATER PURVEYOR, BE UNCOVERED TO THE EXTENT REQUIRED TO
EA
G
PERMIT INSPECTION, REPAIR, OR REPLACEMENT AND THEREAFTER
-
-
SHALL BE RECOVERED. N
12
27.
AT LEAST FOUR WORKING DAYS PRIOR TO COMMENCING ANY
2
EA
EXCAVATION, CONTRACTOR SHALL REQUEST UNDERGROUND SERVICE
ALERT (1-800-422-4133) AND ANY AFFECTED NON-MENBER AGENCIES
PIPELINE.
3
TO MARK OR OTHERWISE INDICATE THE LOCATION(S) OF THEIR SUB-
EA
SURFACE FACILITIES INCLUDING, BUT NOT LIMITED TO, STRUCTURES,
VAULTS, MAIN CONDUCTORS OR CONDUITS, AND SERVICE CONNECTIONS.
UPON LEARNING OF THE EXISTENCE OR LOCATION OF ANY UTILITY
FACILITY OMITTED FROM OR SHOWN INCORRECTLY ON THESE DRAWINGS.
/
CONTRACTOR SHALL IMMEDIATELY NOTIFY WATER PURVEYOR AND THE ENGINEER
WHO PREPARED THESE DRAWINGS. SHOULD SAID UTILITY CONFLICT
WITH PROPOSED WATER FACILITIES, SAID ENGINEER SHALL SUBMIT A
DRAWING SHOWING THE PROPOSED SOLUTION TO THE WATER PURVEYOR FOR
APPROVAL. CONTRACTOR SHALL NOT INTERRUPT OR DISTURB ANY
EXISTING UTILITY FACILITY WITHOUT AUTHORIZATION FROM THE AFFECTED
AGENCY. WHERE PROTECTION IS REQUIRED TO ENSURE INTEGRITY
OF EXISTING UTILITY FACILITIES, CONTRACTOR SHALL PROVIDE ALL
NECESSARY PROTECTION.
28.
STREET GRADE SHALL BE BROUGHT TO WITHIN 1 FOOT OF PROPOSED
FINISH GRADE PRIOR TO BEGINNING WATERLINE CONSTRUCTION. CONTRACTOR
SHALL SHOW EXISTING ELEVATIONS OVER CENTERLINE OF PROPOSED
WATERLINE ON THE CUT SHEETS.
29.
DURING CONSTRUCTION OF THE WATERLINE, CONTRACTOR SHALL
PROVIDE A PIPELINE CAP AND TEMPORARY THRUST PROTECTION FOR
TESTING AND DISINFECTION AT A MINIMUM OF 5 FEET FROM CON-
NECTIONS TO EXISTING WATER SYSTEM AFTER NEW PIPELINE AND
APPURTENANCES HAVE DISINFECTED, TESTED, AND ACCEPTED BY
CITY, CONTRACTOR SHALL REMOVE PIPELINE CAP AND TEMPORARY
THRUST PROTECTION AND INSTALL CONNECTION PIPING. THE CON-
NECTION PIPING SHALL BE SWABBED WITH A CHLORINE SOLUTION.
30.
OPEN EXCAVATION WILL BE ALLOWED OVER NIGHT OUTSIDE OF
PUBLIC STREET RIGHT-OF-WAY PROVIDED SITE IS SECURE. A
CONSTRUCTION FENCE, ENTIRELY ENCLOSING SITE, SHALL BE REQUIRED.
31. PIPELINES SHALL BE CONSTRUCTED SO THAT ACTUAL FLOW LINE
ELEVATIONS ARE WITHIN 0.1 FOOT OF DESIGN FLOW LINE ELEVATIONS.
PIPELINES, WHEN INSTALLED, SHALL HAVE CONTINUOUS UPGRADE
OR DOWNGRADE, CORRESPONDING WITH DESIGN SLOPE, WITHOUT
HIGH OR LOW SPOTS. PIPELINES SHALL BE CONSTRUCTED SO THAT
ACTUAL PIPELINE CENTERLINES ARE WITHIN 0.1 FOOT OF DESIGN
PIPELINE CENTERLINES. CONTRACTOR SHALL ASSIST WATER PURVEYOR AS
REQUIRED TO CONFORM COMPLIANCE WITH CONSTRUCTION TOLERANCES.
32. CONTRACTOR IS ADVISED THAT ROCK OR UNACCEPTABLE TRENCH
BACKFILL MATERIAL MAY BE ENCOUNTERED DURING TRENCHING
OPERATIONS. WHERE SUCH MATERIAL IS ENCOUNTERED, CONTRACTOR
SHALL FURNISH AND INSTALL SUITABLE BEDDING AND BACKFILL
MATERIAL IN ACCORDANCE WITH STANDARD DRAWING W 101. BEDDING
AND BACKFILL MATERIAL SHALL BE EITHER COMMERCIAL IMPORTED
MATERIAL OR SELECT NATIVE MATERIAL (SCREENED OR WASHED).
ALL ROCK OR UNACCEPTABLE TRENCH MATERIAL SHALL BE DISCARDED
AT A LEGAL DISPOSAL SITE.
33. A SOILS ENGINEER, APPROVED BY THE WATER PURVEYOR, WILL TAKE COMPACTION
TESTS AS NECESSARY. COMPACTION TESTS SHALL BE MADE IN THE
PIPE ZONE, THE BACKFILL ABOVE THE PIPE ZONE, AND IN THE
SUBGRADE, ALL AT INTERVALS SELECTED BY WATER PURVEYOR. COMPACTION
TESTS WILL BE TAKEN AS TRENCH BACKFILL PROGRESSES OR AFTER
TRENCH BACKFILL HAS BEEN COMPLETED, AS DETERMINED BY WATER PURVEYOR,
CONTRACTOR SHALL PROVIDE TEST HOLES AS DIRECTED BY WATER PURVEYOR
WHERE BACKFILL HAS BEEN COMPLETED TO ALLOW COMPACTION
TESTS. CONTRACTOR SHALL FURNISH ALL EQUIPMENT (INCLUDING
SHORING), LABOR AND MATERIALS TO ASSIST SOILS ENGINEER IN
PERFORMING ALL THE COMPACTION TESTS. WATER FACILITY TESTING
SHALL NOT BEGIN UNTIL CONTRACTOR HAS COMPLETED COMPACTION
EFFORTS AND CITY HAS ACCEPTED COMPACTION TEST RESULTS.
DEVELOPER SHALL PAY ALL COSTS FOR COMPACTION TESTS.
Underground Service Alert
CaN: TOLL FREE
1--800
422--4133
TM WMI DAYS
BEFORE YOU DIC
QROFESS/pN
k.
No.35275 z 0
* Exp.9/30/99
�'A
o� Cx%illllW
INDEX MAS'
SCALE: 1 "=200
BENCHMARK: ELEV. 1313.04
FWE 43 - RAILROAD SPIKE IN E.P. BY
PP#1536663E S'LY. SIDE OF BASELINE
220' E'LY. OF CHERRY AVE.
CONSTRUCTION SITE
BENCHMARK: ELEV. 1534.50
SET CHIS SQUARE ON CATCH BASIN
AT THE N.W. CURB RETURN
BRIDLEPATH DR. & CHERRY AVE.
50 FT. N.E. CABRIDLEPATH DR.
36 FT. N. W. C/'L CHERRY AVE.
34. IF MONUMENTS OR BENCHMARKS MUST BE REMOVED OR DISTURBED TO
ACCOMODATE CONSTRUCTION, CONTRACTOR SHALL HAVE A
REGISTERED CIVIL ENGINEER OR LICENSED LAND SURVEYOR REPLACE
SAME.
t
35. THE DEVELOPER SHALL PROVIDE WATER PURVEYOR WITH ONE SET OF RECORD
DRAWING MYLARS. SAID DRAWINGS SHALL BE APPROVED BY WATER PURVEYOR
PRIOR TO ACCEPTANCE OF WATER FACILITIES BY WATER PURVEYOR.
UNDERGROUND UTILITIES & STRUCTURE
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES OR
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF
AVAILABLE RECORDS. TO THE BEST OF OUR KNOWLEDGE, THERE ARE NO
EXISTING UTILITIES EXCEPT THOSE SHOWN ON THESE PLANS: THE
CONTRACTOR IS REQUIRED TO TAKE ALL PRECAUTIONARY MEASURES TO
PROTECT THE UTILITIES SHOWN, AND IS RESPONSIBLE FOR THE PROTECTION
OF, AND ANY DAMAGE TO THESE LINES OR STRUCTURES
"CAUTION: THE ENGINEER PREPARING THESE PLANS WILL NOT BE
RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES OR USES OF
THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND
MUST BE APPROVED BY THE PREPARER OF THESE PLANS."
PRIVATE ENGINEER'S NOTICE TO CONTRACTORS
THE CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE
RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF
CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS
AND PROPERTY: THAT THIS REQUIREMENT SHALL APPLY CONTINUOUSLY
AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR
SHALL DEFEND, INDEMNIFY, AND HOLD THE OWNER, WATER PURVEYOR, AND THE
ENGINEER HARMLESS FROM ANY AND ALL LIABILTY, REAL OR ALLEGED,
IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT,
EXCEPTING FOR LIABILITY ARISING FORM THE SOLE NEGLIGENCE OF THE
OWNER, WATER PURVEYOR, OR THE ENGINEER.
ASIS OF BEARINGS:
THE NORTH LINE OF THE NORTHWEST ONE
HALF OF SECTION 23, TOWNSHIP 1 NORTH,
RANGE 6 WEST, S.B.M. BEING N89 -50'00"E
PER TRACT NO. 13750 RECORDED IN BOOK
250, PAGES 48 THROUGH 66 OF MAPS,
RECORDS OF SAN BERNARDINO COUNTY.
AL DESCRIPTION:
LOT 13 OF TRACT NO. 13750 IN THE CITY
OF FONTANA, COUNTY OF SAN BERNARDINO,
CALIFORNIA, PER AMENDING MAP RECORDED
BOOK 250, PAGES 48 TO 66, INCLUSIVE,
RECORDS OF SAN BERNARDINO COUNTY.
UTILITY PURVEYORS:
SOUTHERN CALIFORNIA EDISON CO.
DISTRIBUTION PLANNING
7951 REDWOOD AVENUE
FONTANA, CA 92336
(909) 357-6562
CONTACT: ARMANDO GONZALES
SOUTHERN CALIFORNIA GAS CO.
DISTRIBUTION PLANNING
16231 VALLEY BOULEVARD
FONTANA, CA 92335
(909) 428-8402
CONTACT: DAVID PADILLA
WATER
CITY OF FONTANA
8353 SIERRA AVENUE
P.O. BOX 518
FONTANA, CA 92335
(909) 350-6685
SEWER
CITY OF FONTANA
8353 SIERRA AVENUE
P.O. BOX 518
FONTANA, CA 92335
(909) 350-7610
OWNER /DEVELOPE
ALPER DEVELOPMENT
6101 CHERRY AVENUE
FONTANA, CA 92336
(909) 899-0156
CONTACT: ROGER HATCH
COIuICAST CABLEVISION
1205 DUPONT STREET
ONTARIO, CA 91761
(909) 988-8322 X3055
CONTACT: JACK HAYES
CONSTRUCTION NOTES de QUANTITIES:
VICINITY MAP
N.T.S.
MARKS OA
FIBER -OPTICS/ TRUNK LINK THROUGH PROJECT
4240 HALLMARK PARKWAY
SAN BERNARDINO, CA 92407
(909) 880-0220 .
CONTACT: JOE DEA'RMAN
,GTE CALIFORNIA. NVG.
CAB20VF
870 NORTH MOUNTAIN AVENUE
UPLAND, CA 91786
(909) 931-2472
CONTACT: DANIEL TUCKER
WILTEL. INC.
FIBER-OPTIC TELECOMMUNICATIONS
LAS VEGAS, NEVADA TO LOS ANGELES, CA
UPLAND, CA 91786
P.O. BOX 21348, MD 26-3
TULSA, OK 741211
918 588-3397
909 947-9441 (LOCAL CONTACT)
LOCAL CONTACT: JERRY KENNEDY
* INCLUDES ALL OF HEDGE ROW COURT
to
1-018
001
N/
N C]
QUANTITY
ITEM
DESCRIPTION
UNIT
fiRACT NO.
TRACT NO. *
14571
14571-1
OCONSTRUCT
8" I.D. STEEL PIPE CML do C PER
1,430
2,432
LF
CITY OF FONTANA STD. SPECIFICATIONS.
O2
CONSTRUCT 8" GATE VALVE PER STD. DWG. # W109.
3
7
EA
�3
CONSTRUCT 8" TEE.
-
3
EA
�4
CONSTRUCT 8" X 45' ELBOW.
-
-
EA
O
CONSTRUCT THRUST BLOCK PER STD. DWG. # W106, W107.
1
2
EA
�6
CONSTRUCT 1" A/V RELEASE VALVE PER STD. DWG. If W117.
1
2
EA
0
CONSTRUCT 1" SERVICE LINE PER STD. DWG. # W126.
30
53
EA
�8
CONSTRUCT 6" FIRE HYDRANT ASSEMBLY PER STD. DWG. # W112.
2
5
EA
�9
CONSTRUCT 8" FLANGE AND BLIND FLANGE.
2
5
EA
10
REMOVE BLIND FLANGE, THRUST BLOCK, AND JOIN.
4
4
EA
G
CONSTRUCT 8" X 11-1/4* ELBOW.
-
-
EA
12
CONSTRUCT 8" ELBOW, ANGLES AS SPECIFIED.
5
2
EA
2 TOP OUTLET FOR TESTING, FLUSHING, AND DISINFECTION
OPROVIDE
13
PIPELINE.
3
2
EA
* INCLUDES ALL OF HEDGE ROW COURT