HomeMy WebLinkAbout2367-M-1EOUIVr%IVIVEIN'T LIST
CARRIER Model: 48 DJD 005 EER = 8.5
1 Cooling Cap. - 45,200 BTU/Hr. Total, 30,000 BTU/Hr. Sensible
@ Ent. Evap. Cond. of 750F DB, 650F WB & 110°F Amb. Air Temp.
Heating Cap. - 74,000 BTU/Hr. input, 58,500 BTU/Hr. output
Fan Cap. - 1600 CFM @ 0.7" E.S.P.
Electrical - 3/4 HP, 22 FLA, 208/230 volt, 3 phase, 60 cycle
Operating Wt. - 600 lbs.
Provide with Aconomizer cycle.
CSA
1-5 OF MI
CARRIER Model: 48 DJE 007
Cooling Cap. - 67,500 BTU/Hr. Total, 53,000 BTU/Hr. Sensible
2 @ Ent. Evap. Cond. of 760F DB, 660F WB & 110°F Amb. Air Temp.
Heating Cap. - 115,000 BTU/Hr. input, 91,000 BTU/Hr. output
Fan Cap. - 2600 CFM @ 0.7" E.S.P.
Electrical - 1 1/2 HP, 32 FLA, 208/230 volt, 3 phase, 60 cycle
Operating Wt. - 700 lbs.
Provide with conomizer cycle.
015A-_ 615iolf� ti I KI .
f✓ Central Restroom Exhaust
I LOREN COOK Model - 135 C3B
Capacity - 1000 CFM @ 3/4" S.P.
Electrical - 1/4 HP, 120 volt, 1 phase, 60 cycle
Operating Wt. - 100 lbs.
Interlock with light switch.
Apparatus Room Exhaust
2 LOREN COOK Model - 180 C8B
Capacity - 4600 CFM @ 3/4" S.P.
Electrical - 1 1/2 HP, 208 volt, 3 phase, 60 cycle
Operating Wt. - 150 lbs.
Interlock with light switch. (Reference Detail 1, Sheet E5.)
Apparatus Room Heater
REZNOR Model CXE-75
Z �04. Capacity - 75,000 BTU/Hr. input, 60,000 BTU/Hr. output.
Fan - 1/3 HP, 120 volt, 1 phase, 60 cycle
,Operating Wt. - 400 lbs.
k�r1v�►a Ef b•Jc��.1'tpv..�'rt'ro, L.. f�L� G1a � R Cwt'! L.pt.worr� S Lti.J �..t3'F �,,�'�,'i'ti
s AT Wv..04 HgA79Y . .
V V T SCHEDULE
SYMBO'
MFGR. &
INLET
®C.
B YKBOL
MODEL NO.
B ISS A
AIRFLOW
RETURN AIR REGISTER
CARRIER
E.A.R.
EXHAUST AIR REGISTER
®S.
35 PSA -06
10 x 9
290 cfm
'"'V u T - 2
CARRIER
®E.
A.
EXHAUST AIR DUCT
35 PSA -06
10 x 9
170 cfm
VVT`.�
CARRIER
4 -WAY THROW PATTERN
(�
O.L.
35 PSA -06
10 x 9
170 cfm
VV T_ 4
CARRIER
A.V.O.
AUTOMATIC VOLUME DAMPER
•
35 PSA -06
10 x 9
170 cfm
L.D.
CARRIER
ROOM THERMOSTAT
35 PSA -06
10 x 9
220 cfm
CARRIER
35 PSA -06
10 x 9
170 cfm
VVT- 7
CARRIER
35 PSA -06
10 x 9
430 cfm
,V u T_ 8
CARRIER
35 PSA -08
16 x 10
600 cfm
,%/v T._ 9
CARRIER
35 PSA -10
16 x 10
1050 cfm
CARRIER
35 PSA -06
10 x 9
365 cfm
CARRIER
35 PSA -08
16 x 10
515 cfm
VV T I z
CARRIER
oo ROoIo
35 PSA -10
16 x 10
1280 cfm ,
CARRIER
o r4 Rroo r
35 PSA -10
16 x 10
2080 cfm
IJOYa MIPIMLIN A4f?-- FLOH of:$ VVT I-VVT II o5 elL. 5a 5o/a OP
- D E-� I el 0 0&1 F, FL.d 0.
DRESCO REPRODUC71014 INC. 141679
1
MECHANICAL L
SYMBO'
At BRE!'.'DESCRIPTION
®C.
D.
CEILIIJG DIFFUSER
KRUEGER MODEL 1600 TYPE 4
FASTENING W/OBD
R.A.R.
RETURN AIR REGISTER
®
E.A.R.
EXHAUST AIR REGISTER
®S.
A.
SUPPLY AIR DUCT
KRUEGER MODEL EGC-5 W/OBD
MP► -.do. Brio
R. A.
RETURN AIR DUCT
®E.
A.
EXHAUST AIR DUCT
C.F.M.
CUBIC FEET/MINUTE OF AIR
'4 W
4 -WAY THROW PATTERN
(�
O.L.
DOOR LOUVER
M.V.D.
MANUAL VOLUME DAMPER
T
A.V.O.
AUTOMATIC VOLUME DAMPER
•
A.F.D.
AUTOMATIC FIRE DAMPER
- -
L.D.
LINED DUCT
ROOM THERMOSTAT
5M6 Ir -e D EYI!M
T"YPIo-LLY 6,F-0,
►�I R�
--l.I- -L) mo C;m KE -
ILil7l�Tla�
woo
I
11 ANY ZONE ' THERMOSTAT MAY USE. THE REMOTE ROOM THERMOSTAT SENSOR �
PPTION.
2 . LOCATE: AIRFLOW SENSOR IN FIRST;, STRAIGHT SECT�IbN OF MAIk DUCT
AFTER , rHE BY-PASS' DUCTS . AND ' BtFORM • THE .FIRST ZONE DAMPER.
3,186 RELAY_ PACK IS MOUNTED IN ZONE: ; DAMPER.. CONTROLLED BY MASTER
MDNITOR THERMOSTAT.
0 4. ALL LINE WIRING BY ELECTRICAL_, ALL LOW VOLTAGE WIRING BY
MECHANICAL. t
5. . ALS 'i THERMOSTATS.i SHALL BE PROV,IQED WITH A EY -PAS - `TIME :
Lj tjI -'_
24 - VA.--
2L
P^"K- "
r,TH
`ne ct-ocK- Lxx/ -Te�: i N
X 08
?.A VAS _
ZD VIA,
M I eye r-� T
by FAhS '
C.6Jtevu:e9 L-�i.o�l sE�R
10-5L1PvLv alcr.00 P -00F
tetras -----
WIRING DIAGRAM FOR,A/C 9 &2
GE -NERAL NOTES
1. ALL WIRING, CONDUIT AND "E" ITEMS SHALL BE FURNISHED AND
INSTALLED UNDER THE ELECTRICAL SECTION OF THE SPECIFICATION.
2. ROOM THERMOSTATS SHALL BE LOCATED 44" ABOVE FINISH FLOOR.
SETTING SHALL BE 78°F - 750F HEATING. HEIGHT DIMENSION SHALL
BE TO CENTERLINE OF THERMOSTATS.
3. ALL THERMOSTATS SHALL HAVE NO VISIBLE THERMOMETERS AND SHALL
BE TAMPERPROOF. CONTROL LIMITS SHALL BE FROM 550F TO 850F.
4. ALL THERMOSTATS SHALL BE OF THE AUTOMATIC CHANGEOVER TYPE TO
SEQUENCE HEATING AND COOLING. ADJUSTABLE TEMPERATURE
DIFFERENTIAL SHALL BE 1/20F.
5. CONTROLS SHALL HAVE THE CAPABILITY OF TERMINATING ALL HEATING
AT A TERMPERATURE NO MORE THAN 70°F, AND ALL COOLING AT A
TEMPERATURE NOT LESS THAN 780F.
6. REFER TO MANUFACTURER'S MANUAL FOR RECOMMENDED FUSE AND WIRE
SIZES.
7. TRANSVERSE AND LONGITUDINAL JOINTS SHALL BE SEALED WITH
MASTIC.
8. A MAINTENANCE LABEL SHALL BE AFFIXED TO MECHANICAL EQUIPMENT
AND A MAINTENANCE MANUAL PROVIDED FOR OWNER'S USE.
9. NEW SUPPLY AND RETURN AIR DUCTWORK TO BE INSULATED PER
SCHEDULE. EXTERIOR DUCTS SHALL BE LINED.
10. ALL RECTANGULAR DUCT 90 DEGREE ELBOWS SHALL HAVE TURNING
VANES.
11. ALL INSULATIONS SHALL HAVE A FLAME SPREAD OF 25 AND A SMOKE
DEVELOPED RATE OF 50 AS FOLLOWS:
A. DUCT INSULATION PER UMC 1005
B. PIPING INSULATION PER UMC 2127 (8)
12. INSULATION AND VAPOR BARRIERS PRESENT ON FACTORY -FABRICATED
DUCTS SHALL BE FITTED OVER THE CORE CONNECTION AND SHALL BE
• SUPPLEMENTALLY SECURED WITH A DRAW BAND.
13. FLEXIBLE DUCTS SHALL CONSIST OF AN EXTERIOR REINFORCED
LAMINATED VAPOR BARRIER, 1-1/2" THICK FIBER GLASS INSULATION
(k=.25 @ 750F), ENCAPSULATED SPRING STEEL WIRE HELIX AND
IMPERVIOUS, SMOOTH, NON -PERFORATED INTERIOR VINYL LINER.
INDIVIDUAL LENGTHS OF FLEXIBLE DUCTS SHALL CONTAIN FACTORY
FABRICATED STEEL CONNECTION COLLARS. FLEXIBLE DUCTS SHALL BE
USED ON ONLY THE LAST 6' MAX. TO THE AIR OUTLET.
14. FLEXIBLE DUCT SHALL BE SECURED TO THE SLEEVE OR COLLAR USING
A DRAW BAND. IF THE DUCT COLLAR EXCEEDS 12" DIAMETER, THE
DRAW BAND MUST BE POSITIONED BEHIND A BEAD ON THE METAL
COLLAR. DUCT TAPE SHALL NOT BE USED.
15. FLEXIBLE DUCTS SHALL NOT PENETRATE THROUGH ANY WALL.
16. FLEXIBLE DUCTS MAY BE USED TO CROSS SEISMIC JOINTS WITHOUT
OFFSETS.
17. ALL DUCTWORK SHALL BE INSTALLED TO ALLOW CLEARANCE IN CEILING
SPACE FOR LIGHTS (INCLUDING INSTALLATION), FIRE SPRINKLER
SYSTEMS, AND ALL STRUCTURAL OBSTRUCTIONS NOT SHOWN ON
MECHANICAL DRAWINGS. MECHANICAL CONTRACTOR SHALL VERIFY ALL
REQUIRED CLEARANCE WITH APPROPRIATE DISCIPLINES AND REPORT ANY
FORESEEN PROBLEMS BEFORE BEGINNING INSTALLATION OF ANY
DUCTWORK.
18. AIR HANDLING DUCT SYSTEMS SHALL BE CONSTRUCTED, INSTALLED,
SEALED AND INSULATED AS PROVIDED IN CHAPTER 10 OF THE STATE
MECHANICAL CODE (TITLE 24, PART 4).
19. PROVIDE SEISMIC RESTRAINTS FOR MECHANICAL SYSTEMS PER "SMACNA"
GUIDELINES.
20. ALL FIRE DAMPERS SHALL BE APPROVED AND TESTED IN ACCORDANCE
WITH SFM STANDARD 43.2 C.C.R. T-19.
21. FRESH AIR REQUIREMENTS PER ASHRAE STANDARDS 62-1981.
22. FRESH AIR INTAKE OPENINGS SHALL BE AT LEAST 10 FT. AWAY OR 3
FT. BELOW EXHAUST OPENINGS OR PLUMBING VENTS.
23. EXHAUST FANS SHALL BE INSTALLED WITH BACKDRAFT DAMPERS AND
DISCONNECTS.
RECORD DRAWING
THESE RECORD DRAWINGS (AS -BUILT DRAWINGS)
HAVE BEEN PREPARED BASED ON INFORMATION
SUBMITTED, IN PART, BY OTHERS. WHILE THIS
INFORMATION IS BELIEVED TO BE RELIABLE,
WOLFF/LANG/CHRISTOPHER ARCHITECTS, INC.,
HAS NOT VERIFIED THIS INFORMATION AND IS NOT
RESPONSIBLE FOR ITS ACCURACY OR ADEQUACY,
NOR FOR ANY ERRORS OR OMISSIONS WHICH MAY
HAVE BEEN INCORPORATED INTO THESE
DOCUMENTS AS A RESULT.
AIR DISTRIBUTION SCHEDULE
SYMBOL DESCRIPTION MANUFACTURER
CD
CEILING DIFFUSER
KRUEGER MODEL 6000 W/OBD
SP
SUPPLY REGISTER
(SIDEWALL)
KRUEGER MODEL 1600 TYPE 4
FASTENING W/OBD
RR
RETURN REGISTER
(-ID-.::WALL)
KRUEGER MODEL 1600 TYPE 4
FASTENING W/O OBD
RAR
I1 'TURN ' TF. REGISTER
(C,",IL_NG)
KRUEGER MODEL EGC-5 W/OBD
E7!,R
:XH.'.US' AI1' R}: JISTER
f C.: '7I-ij NG)
KRUEGER MODEL EGC-5 W/OBD
MP► -.do. Brio
ESR
CXH. ASF,
( kA -U- MT),1 D.).
CITY OF
FONTANA
FIRE STATION
NO. U
�W':lCIrJ
n
��ttttt�■� • • �--�
FONTANA COMMUNITY
DEVELOPMENT DEPARTMENT
CENTRAL VALLEY
FIRE PROTECTION DISTRICT
CONSULTANT
JON HAMMOND ENGINEERS
Enokw9ruv cwt
2472 Chwnben Road, sune 1!0
Tusdn, CA $2600
(714) S44-OOM
=TITTLE SHEET
DRAWN
ISD,
CHECKED
J.,ft zm��,-I
DATE
SCALE
Sf 9 I
E
JOB NO.
90 2-300
=TITTLE SHEET
DRAWN
ISD,
CHECKED
DATE
SCALE
Sf 9 I
E
JOB NO.
90 2-300
M=1
W C7, Na, '2,3%`7