1. THE GENERAL CONTRACTOR SHALL VERIFY CONTRACT DOCUMENTS, ALL DIMENSIONS
1.
ALL PHASES OF WORK PERTAINING TO THE CONCETE CONSTRUCTION SHALL CONFORM
1.
ALL LUMBER SHALL BE STRESS GRADE DOUGLAS FIR (COAST REGION) UNLESS NOTED
1.
ALL REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615,
AND SITE CONDITIONS BEFORE STARTING WORK. THE ENGINEER SHALL BE NOTIFIED
TO THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318 LATEST
OTHERWISE.
GRADE 60 UNLESS NOTED OTHERWISE.
OF ANY DISCREPANCY BEFORE PROCEEDING WITH THE WORK.
APPROVED EDITION) WITH MODIFICATIONS AS NOTED IN THE DRAWINGS OR
SPECIFICATION.
A. 2 x 4 STUDS STUD GRADE, Fb = 800 PSI
2.
WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185.
2. IN CASE OF CONFLICT BETWEEN CONTRACT DOCUMENTS, NOTIFY ENGINEER PRIOR TO
B. 3 x 4 STUDS STUD GRADE, Fb = 800 PSI
PROCEEDING WITH ANY WORK INVOLVED.
2.
CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY
C. 2 x 6 STUDS D.F. NO. 2, Fb = 1,450 PSI
3.
DETAILING, FABRICATION AND ERECTION OF REINFORCING BARS SHALL CONFORM TO
APPROVED BY LOCAL BUILDING OFFICIALS, AND CONFORM TO ASTM C-94.
D. ROOF JOISTS D.F. NO. 2, Fb = 1,450 PSI
THE LATEST EDITION OF THE ACI 'MANUAL OF STANDARD PRACTICE FOR DETAILING
3. NOTES AND DETAILS ON DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES
E. FLOOR JOISTS D.F. NO. 2, Fb = 1,450 PSI
REINFORCED STRUCTURES'.
AND TYPICAL DETAILS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL
3.
THE MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF CONCRETE AT 28 DAYS SHALL
F. ALL BEAMS D.F. NO. 1, Fb = 1,500 PSI
CONFORM TO SIMILAR WORK ON PROJECT, AND CONTRACTOR SHALL NOTIFY THE
BE AS FOLLOWS:
G. POSTS D.F. NO. 1, Fc = 925 PSI
4.
BARS SHALL BE CLEAN OF RUST, GREASE OF OTHER MATERIAL LIKELY TO IMPAIR
ENGINEER.
BOND.
LOCATION STRENGTH
2.
ALL WOOD IN DIRECT CONTACT WITH THE GROUND, OR WITH MASONRY OR CONCRETE
4. ALL WORK SHALL CONFORM TO THE MINIMUM STANDARDS OF THE 1991 EDITION OF
WITHIN 48 INCHES OF THE GROUND, SHALL BE TREATED WITH A PRESERVATIVE, OR
5.
ALL BAR BENDS SHALL BE MADE COLD.
THE UNIFORM BUILDING CODE AND ANY OTHER REGULATION AGENCIES WHICH HAVE
CONTINUOUS FOOTING 3,000 PSI
SHALL BE DECAY RESISTANT WOOD AS PRESCRIBED IN DIVISION 31 (WOOD
AUTHORITY OVER ANY PORTION OF THE WORK, INCLUDING THE STATE OF CALIFORNIA
SPREAD FOOTING 3,000 PSI
PRESERVATIVE). (IF REDWOOD IS USED, INCREASE NAILING BY 54%).
6.
PRIOR TO POURING CONCRETE, REINFORCING STEEL AND EMBEDDED ITEMS SHALL BE
DIVISION OF INDUSTRIAL SAFETY AND THOSE CODES AND STANDARDS LISTED IN THESE
SLAB ON GRADE 3,000 PSI
WELL SECURED IN POSITION.
NOTES AND SPECIFICATION.
GRADE BEAM 3,000 PSI
3.
ALL WALL SILLS SHALL BE BOLTED TO FOUNDATIONS (CONCRETE OR CMU) WITH 5/8"
ALL OTHERS 3,000 PSI
DIA ANCHOR BOLTS x 10" LONG ® 4'-0" O.C. MAXIMUM AT EXTERIOR WALL, WITH
7.
REINFORCING BARS SHALL NOT BE WELDED WITHOUT APPROVAL OF THE STRUCTRUAL
5. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
7/32" DIA SHOT PINS ® 32" O.C. MAXIMUM AT INTERIOR WALLS. EXCEPT AS
ENGINEER.
STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE
4.
ALL CEMENT SHALL CONFORM TO ASTM C-150, TYPE I OR TYPE II.
CALLED OUT FOR SHEAR WALLS.
CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE
8.
THE LAPS ON WWF SHOULD BE ON MESH PLUS 2".
STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE
5.
AGGREGATE FOR HARDCOCK CONCRETE SHALL CONFORM TO ALL REQUIREMENTS AND
4.
2 x JOISTS DEEPER THAN 10" SHALL BE BLOCKED AT SUPPORT AND AT 8 FEET O.C.
LIMITED TO BRACING, SHORINGS FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
TESTS OF ASTM C-33 AND PROJECT SPECIFICATIONS. EXCEPTIONS MAY BE USED
WITH 1 x 4 WOOD GROSS BRIDGING. SOLID 2 x BLOCKING 2" SHALLOWER THAN
9.
BAR LAPS SHALL BE MADE AWAY FROM POINTS OF MAXIMUM STRESS OR AT
OBSERVATION VISITS TO THE SITE BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE
ONLY WITH PERMISSION OF THE STRUCTURAL ENGINEER.
JOISTS OR APPROVED METAL CROSS BRIDGING. BLOCKING AT ENDS MAY BE OMITTED
LOCATIONS SHOWN ON THE DRAWINGS, THE LAP LENGTH SHALL BE AS INDICATED
INSPECTION OF THE ABOVE ITEMS.
WHERE JOISTS HANGERS APPROVED FOR USE WITHOUT SOLID BLOCKING ARE USED.
BELOW UNLESS NOTED OTHERWISE.
6.
POURING OF CONCRETE SHALL CONFORM TO ACI STANDARDS 304 AND PROJECT
6. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK OPERATION
SPECIFICATIONS, SANDBLAST ALL CONCRETE SURFACES AGAINST WHICH CONCRETE IS
5.
A DOUBLE PLATE MADE OF TWO MEMBERS OF THE SAME SIZE AS THE STUDS SHALL
A. COLUMNS; 36 BAR DIAMETERS ,
FOR FILLED EXCAVATIONS OR BURIED STRUCTURES SUCH AS CESSPOOLS, CISTERNS,
TO BE PLACED.
BE PLACED AT THE TOP OF EVERY BEARING PARTITION OR EXTERIOR WALL. SUCH
FOUNDATIONS, ETC. IF ANY STRUCTURES ARE FOUND, STRUCTURAL ENGINEER SHALL
DOUBLE PLATES SHALL BE LAPPED AT CORNER, AND JOINTS, IN UPPER AND LOWER
B. ALL CONTINUOUS BARS SHALL HAVE MINIMUM LAP OF 'C' TYPE ATSPICES.
BE NOTIFIED IMMEDIATELY.
7.
ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL BE
MEMBERS SHALL BE AT LEAST FOUR FEET APART, EXCEPT AT CORNERS.
WELL SECURED IN POSITION PRIOR TO POURING CONCRETE.
C. CONCRETE BLOCK MASONRY; 40 BAR DIAMETERS
7. THE GENERAL CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL AND MECHANICAL
6.
AT EXTERIOR WALLS AND BEARING PARTITIONS SHALL BE 2 x 4 STUDS ® 16" O.C.
DRAWINGS FOR REQUIRED OPENINGS AND PIPE SLEEVES IN THE JOB, VERIFY SIZE
8.
PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE BEFORE
FOR WALL HEIGHT 10 FEET OR LESS, USE 2 x 6 STUDS ® 16" O.C. WHEN WALL
10. CONCRETE COVER OVER REINFORCING STEEL BARS SHALL BE AS FOLLOWS:
AND LOCATION OF ALL OPENINGS WITH MECHANICAL CONTRACTOR.
POURING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING IN
HEIGHT IS LARGER THAN 10 FEET, USE 3 x 4 STUDS ® 16" O.C. WHEN SUPPORTING
CONCRETE IS NOT PERMITTED EXCEPT AS SHOWN, NOTIFY THE STRUCTURAL ENGINEER
LOADS FROM ROOF AND TWO OR MORE FLOORS ABOVE UNLESS NOTED OTHERWISE
A. POURED AGAINST EARTH 3" CLEAR
8. GENERAL CONTRACTOR SHALL GIVE DUE AND LEGAL NOTICE TO ADJACENT PROPERTY
IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS.
ON DRAWINGS.
OWNERS REGARDING THE PROTECTION OF THEIR PROPERTY AND STRUCTURES WHICH
B. EXPOSED TO EARTH BUT POURED AGAINST FORMS 2" CLEAR
MAY BE NECESSARY DUE TO EXCAVATION AND CONSTRUCTION INDICATED ON THESE
9.
CONCRETE SHALL BE MAINTAINED IN A MOIST CONDITION FOR A MIN OF 5 DAYS
7.
ALL EXTERIOR WALLS AND BEARING PARTITIONS SHOULD BE BRACED AND MEET THE
DRAWINGS, IN DUE TIME PRIOR TO START OF EXCAVATION.
AFTER POURING.
MINIMUM REQUIREMENT OF UBC 2517.G.3.
C. STRUCTURAL SLAB 1" CLEAR
10. LOCATION OF CONSTRUCTION JOINTS AND OTHER TYPES OF JOINTS, OTHER THAN
8.
FLOOR JOISTS SHALL BE DOUBLED UNDER PARTITIONS RUNNING PARALLEL TO THE
D. INTERIOR FACE OF WALLS 1" CLEAR
SPECIFIED OF DETAILED ON DRAWINGS, SHALL BE APPROVED BY THE ENGINEER
JOISTS. USE DOUBLE STUDS OR 4 x 4 POSTS UNDER DOUBLE JOISTS OR 4 x
BEFORE POURING.
BEAMS, UNLESS NOTED OTHERWISE ON FRAMING PLANS.
11.
ALL CONCRETE W/A 28 DAY STRENGTH GREATER THAN 2,500 PSI AND REINFORCING
9.
ALL NAILS SHALL BE COMMON WIRE NAILS UNLESS NOTED OTHERWISE.
STEEL SHALL BE INSPECTED BY A REGISTERED DEPUTY INSPECTOR PER UBC SECTION
306.
10.
BOLTS SHALL CONFORM TO ASTM A-307.
12. GROUT USED UNDER STEEL COLUMN BASE PLATES SHALL BE OF NON-SHRINKAGE
11.
PLYWOOD SHALL BE INTERIOR TYPE WITH EXTERIOR GLUE CONFORMING TO PSI-74
VARIETY WITH MINIMUM COMPRESSIVE STRENGTH OF 9,000 PSI IN 28 DAYS.
OF GRADE CALLED FOR BELOW, LAID WITH FACE GRAIN PERPENDICULAR TO SUPPORTS.
DESIGN LATERAL LOADS
A. ROOF SHEATHING SHALL BE 1/2- PLYWOOD STRUCT.II (STD) NAIL WITH 8d NAILS
® 6" O.C. AT ALL DIAPHRAGM AND WALL BOUNDARIES. CONTINUOUS PANEL
STRUCTURAL STEEL
BUILDING IS DESIGNED FOR 70 MPH EXPOSURE C WIND LOAD AND SEISMIC ZONE 4
EDGES ARE NOT BLOCKED. 8d NAILS ® 6" O.C. AT PLYWOOD PANEL EDGES
AND 8d NAILS ® 12" O.C. TO INTERMEDIATE SUPPORTS. INDEX # 32/16.
1.
STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING A.S.T.M. DESIGNATIONS:
EARTHQUAKE LOAD, AS PER 1991 UNIFORM BUILDING CODE.
DESIGN LIVE LOADS
B. FLOOR SHEATHING SHALL BE 5/8" PLYWOOD STRUCT. II (STD) NAILED WITH 10d
A.S.T.M. A36 - ALL STEEL FRAMING
NAILS ® 6" O.C. AT ALL DIAPHRAGM AND WALL BOUNDARIES. CONTINUOUS PANEL
ROOF 20 PSF
EDGES ARE NOT BLOCKED. 10d NAILS ® 6" O.C. AT PLYWOOD PANEL EDGES
A.S.T.M. A325 -- ALL BOLTS USED FOR CONNECTING STRUCTURAL MEMBERS
ROOF TILE 14 PSF
AND 10d NAILS AT 10" O.C. TO INTERMEDIATE SUPPORTS. INDEX # 32/16.
CEILING AND SUSPENDED MECHANICAL ITEMS 5 PSF
A.S.T.M. A307 -- ALL ANCHOR BOLTS
FLOOR 40 PSF
C. PLYWOOD SHEATHING SHALL BE INSPECTED AND APPROVED BY BUILDING
BALCONY 60 PSF
CONCRETE BLOCK
INSPECTOR PRIOR TO COVERING WITH FLOOR OR ROOF MATERIAL.
2.
ALL EXPANSION ANCHORS SHALL BE HILTI KWIK BOLTS OR EQUAL.
CORRIDOR 100 PSF
1.
CONCRETE BLOCK SHALL BE HOLLOW LOAD-BEARING CONCRETE MASONRY UNITS
D. SOLID BLOCKING IS REQUIRED FOR ALL WALL BOUNDARIES.
3.
ALL STEEL EXPOSED TO WEATHER SHALL BE PAINTED PER LATEST A.I.S.C.
CONFORMING TO ASTM C90-70. USE OPEN END UNITS FOR STACKED BOND PATTERN
SPECIFICATIONS.
AND BOND BEAM UNITS AT HORIZONTAL REINFORCING. THE MINIMUM COMPRESSIVE
12.
TRUSS JOIST: DESIGN AND SPECIFICATIONS WILL HAVE A SEPARATE PERMIT BY THE
STRESS; fm = 1,500 PSI.
MANUFACTURER AND SHALL CONFORM TO I.C.B.O. R.R. NO. NER-200.
4.
ALL STRUCTURAL_ STEEL SHALL BE FABRICATED IN THE SHOP OF A LICENSED
FABRICATOR AND SHOP DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL
2.
MORTAR, TYPE S, CONFORMING TO ASTM C-476 MINIMUM COMPRESSIVE STRENGTH;
13.
ALL ELECTRICAL CONDUITS, MECHANICAL SYSTEMS AND PLUMBING PIPES SHALL BE
ENGINEER FOR APPROVAL PRIOR TO FABRICATION.
Vc = 1,800 PSI 0 28 DAYS.
FLEXIBLE AND HAVE ENOUGH ROOM TO ACCOMMODATE THE SHRINKAGE AND
SWELLING OF THE WOOD.
5.
WELDING SHALL BE DONE IN AN APPROVED FABRICATING SHOP BY WELDERS
3.
GROUT, CONFORMING TO ASTM C-476 MINIMUM COMPRESSIVE STRENGTH;
QUALIFIED AS REQUIRED BY THE BUILDING DEPARTMENT CONFORMING TO THE
f'c = 2,000 PSI ® 28 DAYS.
LATEST A.W.S. SPECIFICATIONS AND STANDARDS. ELECTRODES SHALL BE AS
FOLLOWS:
4.
GROUT PLACEMENT: MAXIMUM GROUT LIFT SHALL BE 4 FEET UNLESS NOTED
FOUNDATIONS
OTHERWISE, 2 FEET FOR ESSENTIAL BUILDING.
E-70 ELECTRODES: A-36 STRUCTURAL STEEL
1. THESE DRAWINGS ARE BEING PREPARED WITHOUT ANY SOIL REPORT. ALLOWABLE
5.
SOLID GROUT ALL CELLS.
6.
FIELD WELDING SHALL BE DONE BY A CERIFIED WELDER. INSPECTION OF WELDING
SOIL BEARING WAS TAKEN FROM EXISTING DRAWING S-7. OTHER SOIL PARAMETERS
SHALL BE DONE BY AND APPROVED SPECIAL INSPECTOR PER U.B.C. SECTION 306.
WERE TAKEN FROM THE 1991 UBC IN THE DESIGN OF THE STRUCTURE. IN
6.
PROVIDE A MINIMUM OF 1/2" GROUT BETWEEN MAIN REINFORCING AND MASONRY
ADDITION ACCORDING TO THE OWNER THE UNDERGROUND WATER TABLE IS WAY
UNITS. 3/4" BETWEEN PARALLEL REINFORCING BARS.
7.
CONTINUOUS INSPECTION IS REQUIRED FOR ALL FIELD WELDING AND HIGH STRENGTH
BELOW THE ELEVATOR PIT DEPTH ELEVATION. IN CASE UNDERGROUND WATER WILL
BOLTS.
BE IDENTIFIED, THE WORK SHALL BE STOPPED IMMEDIATELY AND OWNER AND
7.
CONTINUOUS INSPECTION IS NOT REQUIRED.
ENGINEER SHALL BE NOTIFIED IMMEDIATELY.
8.
BOLTS EMBEDDED IN WALL TO BE ASTM A--307.
2. FOUNDATION SHALL CONSIST OF CONTINUOUS AND SPREAD FOOTING POURED ON
UNDISTURBED SOIL (MINIMUM OF 12" WIDE AND 18" DEEP). ALLOWABLE SOIL
BEARING PRESSURE: IS 2000 PSF AT DEPTH OF 1'-6" - 3000 PSF AT
DEPTHS OF 10'-0" OR GREATER FOR DEAD LOAD PLUS LIVE LOAD
OR DEAD LOAD PLUS SEISMIC OR WIND LOAD.
3. CONCRETE SLAB PLACEMENT SHALL BE 1,200 SQ. FT. MAXIMUM OR 40'-0" LONG
MAXIMUM. ADJACENT SLAB SHOULD NOT BE POURED IN 48 HOURS.
4. ALL REQUIRED FILL AND BACKFILL SHALL BE COMPACTED TO 95% OF THE MAXIMUM
DENSITY.
COMPOSITE
FLOOR CONSTRUCTION
5. FILL AND FOUNDATION EXCAVATION SHALL BE INSPECTED AND APPROVED BY THE
1.
COMPOSITE FLOOR SLAB STEEL DECK SHALL BE 3 1/4-" LIGHT WEIGHT
SOIL ENGINEER PRIOR TO FORMING.
��OVER
CONCRETE SLAB OVER 2 DEEP, 20 GAUGE, GALVANIZED STEEL DECK. BUTT WELD
ENDS OF DECK AT END SUPPORTS, WELD AT ENDS OF INTERMEDIATE SUPPORTS AT
6. WATER SHALL BE REMOVED FROM FOUNDATION EXCAVATION PRIOR TO POURING OF
EACH SIDE OF SHEET ON LOW FLUTE. SIDE LAPS SHALL BE WELDED AT 3'-0" O.C.
CONCRETE. FOOTING SHALL BE POURED IMMEDIATELY AFTER EXCAVATION.
MAXIMUM. REINFORCING SLAB WITH 6 x 6 - W1.4 x W1.4 WELDED WIRE MESH
LAPED ONE MESH AT ENDS AND SIDES. MESH SHALL BE PLACED IN TOP OF SLAB
AND CHAIRED AT SUPPORTS TO PROVIDE 1" TOP COVER.
2.
HEADED STUD SHEAR CONNECTION SHALL BE 3/4" DIA x 4" LONG WITH CONNECTOR
SHEAR CAPACITY OF 9.5 KIPS FOR LIGHT WEIGHT CONCRETE (f'c = 3,000 PSI).
CONTRACTOR SHALL
MINIMUM STUD YIELD STRESS OF 50 KSI.
�l�r/
- NOTIFY OSHA FOR ALL EXCAVATIONS EXTENDING 5'-0" BELOW EXISTING�t�
Q��SStqq���
•'.' �; .�1. Q '^l �2
GRADE LEVEL.
- CONTRACTOR SHALL PROVIDE ALL REQUIRED AND NECESSARY SHORING DURING
CONSTRUCTION.
r a 26$a� ti
".iA
CE���+
.d
OF G
CfTY DWG 2305SHEET 6 OF 16
N0. N0.
APPROVED
CITY ENGINEER R.C.E.
NOT FOR CONSTRUCTION
CITY OF FONTANA
WRITTEN DIMENSIONS SHAD. TAKE PRECEDENCE OVER
SCALED SHALL E•BRORUGHT
PROJECT
CLIENT
BOCK ENGINEERING, INC.
SCALE
PROJECT N0. 92035
_w
I B°sem. ANY DISCREPANCY Y SHAD. BMENSIONS
TO
THE IMMEDIATE ATTENTION OF BOCK ENGINEERING, INC.,
ARCHITECTURAL BARRIER REMOVAL PROJECT ELEVATOR
FOR
CITY OF F
CON SULTING ENCINEERS
PRIOR TO COMMENCEMENT OF ANY WORK.
PERFORMING ARTS CENTER, 9460 SIERRA AVE.,FONTANA,CA.92335
�
N� T' � S,
FILE N0. -
92035 15
STRUCTURAL - ELECTRICAL - MECHANICAL
THIS DESIGN, DRAWING, SPECIFICATION & CALCULATION IS
THE PROPERTY OF BOCK ENGINEERING, INC., do IS FOR USE
ONLY ON THE SPECIFIC SITE INDICATED, do SHAD. NOT BE
_
DWG TITLE
PERFORMING ARTS CENTER
9 46O SIERRA E R RA AVENUE
DWG. NO.
REV.
USED ON ANY OTHER WORK OR SITE, EITHER AS A WHOLE
IN PART. IT SHALL NOT
0
FOR APPROVAL
ELM
PAB
PAB
12-15-92
STRUCTURAL SPECIFICATIONS
n
O
E E -
4650 ARROW HIGHWAY SUITE --?
'
OR BE ALTERED OR MODIFIED
EITHER AS A WHOLE OR IN PART, EXCEPT BY AUTORIZED
FONTANA, CALIFORNIA 92335
909 621--0544
MONTCLAIR, CALIFORNIA 91763
EMPLOYEES OF BOCK ENGINEERING, INC.
REV
DESCRIPTION
UWN
ENG
CHKD
DATE
REV
DESCRIPTION
DW
ENG
CHKO
DATE
1 OF 7 DRAWINGS