HomeMy WebLinkAbout2200-20UNDERGROUND TELEPHONE SPECIFICATIONS 1. All conduits bends to have minimum radius in feet equal to di.. • :,iter of conduit in inches. 2" diameter = 24" radius, etc. 2. No conduit run to have over two 90° bends, if necessary to have over two 90° bends, insert accessible pull box in run. Contact Telephone engineer for pull box sizing. 3. All conduit shall be left clean, dry, and free of debris or other obstructions. A pull line equivalent to No. 14 AWG -3/16" polpropylene or conduit measuring tape. 4. Approved plastic is specified in underground construction. Condulets, plumber's fitting, water and gas pipes must not be used. 5. Conduit terminated on a pole must be turned up V above finish grade, in the opposite quadrant from any power services. (See detail of pole for termination). 6. Conduit placed in same trench with power conduit must be separated by not less than 12" of well packed dirt or 3" of concrete, and have not less than 30" of cover. 7. Approved Plastic Conduit PTS 66 2" P.V.C. Sch. 40 PTS1366 PTS 77 4" A.B.S. "D.B." P&C Duct PUBLIC STREET PRIVATE, PROPERTY 8. The Telephone Company reserves the right to refuse to use conduitthat deviated from plans and specifications. 9. In runs of 400 ft. or over, bends having radii of 80 ft. or less must be concrete encased. In changes of grade 20% (11.3 degrees) or more the conduit must be encased in concrete. TELEPHONE CONDUIT MIN. 12" BACKFILL OR 3" CONCRETE POWER CONDUIT TYPICAL f ABOVE GRADE t POLE FOOTINGI T SERVICE t 'CONDUITS ' k -PROPERTY LINE r1 ion PACIFIC BELL REQUIREMENTS ARE GENERALLY LIMITED TO ENTRANCE CONDUIT, BACKBOARD(S) UFER GROUND AND A CONDUIT(S) TO EACH TENANT SPACE. ANY REQUIREMENTS FOR TERMINAL EQUIPMENT (PBX, KEY TELEPHONE, ECT.) WILL BE PROVIDED BY VENDORS OF THE TERMINAL EQUIPMENT. 1. ALL CONDUIT RUNS WILL BE LIMITED TO (2) 90 SWEEPS EQUIPPED WITH PULL LINES. TELEPHONE BACKBOARD — SIZE AS INDICATED. ALL CONDUITS TO TERMINATE 2" ABOVE FLOOR OR 6" BELOW CEILING. 110-120 V DOUBLE DUPLEX RECEPTABLE ON A SEPARATE CIRCUIT LOCATED AS INDICATED A CONCRETE ENCASED ELECTRODE (UFER) — COMMON WITH POWER SERVICE GROUND ADJACENT TO BACKBOARD. PER NEC ARTICLE 250. 511 t I'UWtK & i tLtl'F1UNt StKVI(:t NU I t5 SOUTHERN CALIFORNIA EDISON COMPANY (S.C.E.) PACIFIC BELL TELEPHONE (P.B.) @-4" C.O. FOR HIGH VOLTAGE SERVICE. VERIFY THE LOCATION AND ROUTING. HIGH VOLTAGE CONDUIT SHALL BE 48" DEEP WITH 3" CONCRETE FOR THE ENCASEMENT. @—TRANSFORMER SLAB BOX WITH TRAFFIC GUARDS PER S.C.E. REQUIREMENTS, VERIFY SIZE, LOCATION AND ORIENTATION WITH S.C.E. @-4" C.O. FOR SECONDARY FROM THE TRANSFORMER TO THE MAIN SWITCHGEAR. (1)—r C.O. FOR EACH 400A OF SERVICE. VERIFY ROUTING WITH S.C.E. AND ROUTE TO CLEAR STRUCTURAL FOOTINGS. @—STUB OUT AND TERMINATE PER S.C.E. REQUIREMENTS. VERIFY LOCATION OF HIGH VOLTAGE SERVICE POINT PRIOR TO BIDDING AND INCLUDE ALL COSTS IN THE BID. —STUB OUT AND TERMINATE PER P.B. REQUIREMENTS. VERIFY LOCATION OF TELEPHONE SERVICE POINT PRIOR TO BIDDING AND INCLUDE ALL COSTS IN THE BID. @—PULLBOX NTH TRAFFIC COVER PER TELEPHONE COMPANY'S REQUIREMENTS. SIZE AS INDICATED; VERIFY LOCATION, TYPICAL. (@—ROUTE TO THE MAIN SERVICE ENTRANCE, -- ALL UTILITY SERVICES SHALL BE VERIFIED WITH THE UTILITY COMPANIES PRIOR TO BIDDING AND ALL RESULTING COSTS SHALL BE INCLUDED IN THE BID. PACIFIC BELL TELEPHONE LAYOUT FOR: ci\,/Rl PREPARED,BY:D� ��o�i; lam, i A L GR � �1 *IMPORTA T -=- NO CHANGES WITHOUT AUT ORIZATION OF PERSON RESPONSIBLE FOR LAYOUT. DATE: 1 PACIFIC13BELL- IMPORTANT BEFORE TELEPHONE ENTRANCE FACILITIES CAN BE PROVIDED TO: PAIZk'- LjAAPi moi_. Lt. ALL DEVELOPER PROVIDED SUPPORTING STRUCTURES MUST BE IN PLACE AND INSPECTED 30 DAYS PRIOR TO CABLE PLACEMENT. I.E., ENTRANCE CONDUIT, PULL LINES, BACKBOARDS, PULL BOXES, MANHOLES, ELECTRICAL OUTLETS, PENETRATIONS OF CONCRETE, FIRE RATED WALLS, INTERIOR CONDUITS, GROUND, ETC. AT START OF CONSTRUCTION CALL( 7 01� FOR JOB SITE MEET AND INSPECTION CARD. ACTUAL INSTALLATION OF TELEPHONE ACCESS LINES WILL FOLLOW ENTRANCE FACILITY PLACEMENT. DATE Underground Service Alert Catt:TOLL FREE 800 422w4133 TWO WORKING DAYS BEFORE YOU DIG RECORD DRAWING I; I AMARIND AVENUE The information on this drawing is obtakW from others and must be verified in the field by anyorw prior to use or construction,_- _Co��U/tome _ _ Js�not responsible for underground facility locations or demtims. All above ground facilities can be readily seen and verified by the pares that end to use sante. 'I,- -I/"-- RC1) -4''C,0. EXISTING POWER POLE TO SLOVER AVENUE SERVICE POINT, ROUTE ALONG SERVICE DRIVE, SLOVER AVENU ( IN FEET ) I inch = 50 ft. SliT 20 OF a6 2.6 4 �E 120'—� 2O—ACTUAL INSTALLATION OF ALL UTILITY SERVICES SHALL BE ACCORDING TO THE FINAL ENGINEERED SCALE UTILITY ON THE COMPANY PLANS. NOTE SHEET. SEE THE "UTILITY NOTES' SERVICE DRIVE DETAIL M r c PACIFIC BELL TELEPHONE LAYOUT FOR: ci\,/Rl PREPARED,BY:D� ��o�i; lam, i A L GR � �1 *IMPORTA T -=- NO CHANGES WITHOUT AUT ORIZATION OF PERSON RESPONSIBLE FOR LAYOUT. DATE: 1 PACIFIC13BELL- IMPORTANT BEFORE TELEPHONE ENTRANCE FACILITIES CAN BE PROVIDED TO: PAIZk'- LjAAPi moi_. Lt. ALL DEVELOPER PROVIDED SUPPORTING STRUCTURES MUST BE IN PLACE AND INSPECTED 30 DAYS PRIOR TO CABLE PLACEMENT. I.E., ENTRANCE CONDUIT, PULL LINES, BACKBOARDS, PULL BOXES, MANHOLES, ELECTRICAL OUTLETS, PENETRATIONS OF CONCRETE, FIRE RATED WALLS, INTERIOR CONDUITS, GROUND, ETC. AT START OF CONSTRUCTION CALL( 7 01� FOR JOB SITE MEET AND INSPECTION CARD. ACTUAL INSTALLATION OF TELEPHONE ACCESS LINES WILL FOLLOW ENTRANCE FACILITY PLACEMENT. DATE Underground Service Alert Catt:TOLL FREE 800 422w4133 TWO WORKING DAYS BEFORE YOU DIG RECORD DRAWING I; I AMARIND AVENUE The information on this drawing is obtakW from others and must be verified in the field by anyorw prior to use or construction,_- _Co��U/tome _ _ Js�not responsible for underground facility locations or demtims. All above ground facilities can be readily seen and verified by the pares that end to use sante. 'I,- -I/"-- RC1) -4''C,0. EXISTING POWER POLE TO SLOVER AVENUE SERVICE POINT, ROUTE ALONG SERVICE DRIVE, SLOVER AVENU ( IN FEET ) I inch = 50 ft. SliT 20 OF a6 2.6 4