HomeMy WebLinkAbout5909-1GENERAL NOTES FOR SEWER
IMPROVEMENT PLANS
1. ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD
PLANS, THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS
CONSTRUCTION ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE
THE LATEST EDITION UNLESS OTHERWISE NOTED.
2. WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CAN
NOT BE RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK", THE
CONTRACTOR SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEER FOR
RESOLUTION.
3. ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER.
4. CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY
DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK.
INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE
START OF ANY WORK IN PUBLIC RIGHT-OF-WAY WITHIN THE CITY LIMITS. CALL (909)
350-7610.
5. THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND
PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST
NON -METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS
OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES.
7. THE CONTRACTOR SHALL BE OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK
FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF
INDUSTRIAL SAFETY.
8. THE WALLS AND FACES OF ALL EXCAVATIONS FOR GREATER THAN FIVE (5) FEET IN DEPTH
SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS
PURSUANT TO THE REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF
CALIFORNIA. TRENCHES LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE
POTENTIAL EXISTS FOR GROUND MOVEMENT.
9. NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY WITHOUT
OBTAINING A SEPARATE PERMIT FOR THAT PURPOSE.
10. THE LOCATION OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION,
HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE. IN THE FIELD,
THE TRUE LOCATION AND ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER
PRECAUTION TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT AT 1-800-227-2600 TWO WORKING DAYS BEFORE EXCAVATION.
11. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING,
BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE
IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND
CALTRANS. ALL UTILITY COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO
WORK AROUND THEIR FACILITIES.
12. THE CONTRACTOR SHALL NOT OPERATE, ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT
APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE
APPROPRIATE WATER COMPANY FRO VALVE OPERATION AND WATER REQUIREMENTS.
13. STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE OTHERWISE NOTED.
14. ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO ENABLE THE
CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADES. THE CONTRACTORS SHALL BE
RESPONSIBLE FOR THE RESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING
DURING CONSTRUCTION.
15. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR
BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER.
16. REMOVAL AND REPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING SURVEY MONUMENTS,
MONUMENT TIES AND BENCH MARKS. SHALL BE DONE 'BY A REGISTERED CIVIL ENGINEER OR
LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF
THIS CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE
WEEK PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER
REPLACEMENT OF THE MONUMENT.
17. THE CONTRACTOR SHALL MAINTAIN ACCESS FRO LOCAL RESIDENTS AND BUSINESSES AT ALL
TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION
AREA FOR RESIDENTS AND EMERGENCY VEHICLES.
18. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST CONTROL,
INCLUDING ADEQUATE WATERING, AT ALL TIMES.
19. THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT OR DEBRIS TO BE
DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING
CONSTRUCTION WITHOUT PRIOR WRITTEN APPROVAL.
20. NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR.
21. A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION. FAILURE TO OBTAIN THE
REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT PORTION OF THE WORK UNTIL THE
SPECIFIED DENSITY IS OBTAINED.
22. CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING
STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE
TEMPORARY NON-ERODABLE SWALES ENTERING OR LEAVING IMPROVEMENTS.
23. ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH
EXISTING CONCRETE.
24. IF SEWER CONSTRUCTION IS NOT TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A
TERMINAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THEN 150 FEET FROM THE
DOWNSTREAM MANHOLE, SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT.
25. SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR BAND SEAL TYPE
VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE
PROVISIONS OF THE ASTM DESIGNATION C700 FOR V.C.P.
26. NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL OF
THE CITY ENGINEER.
27. SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE WALLS
TO ALLOW FOR MINOR DEFLECTION IN ALIGNMENT.
28. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND VERIFY
ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS TO EXISTING
FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCATIONS SHOWN ON THE
PLANS.
BENCHMARK: CITY OF FONTANA BENCHMARK NO. 28
ELEVATION = 1222.41 FT. BEING A MAG,NAIL
IN TOP OF CURB LOCATED AT THE ECR AT,
THE NE CORNER OF THE INTERSECTION OF
MERRILL AVENUE AND OLEANDER AVENUE.
BASIS OF BEARING:
BASIS OF BEARINGS IS THE CENTERLINE OF
OLEANDER AVENUE WHICH BEARS ND-12-30W
PER RSB 72/97.
SEWER
N/E
29. ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADE UNLESS OTHERWISE
APPROVED BY THE CITY ENGINEER.
3.0. TERMINATE ALL 4" HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12" BELOW
THE GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE STREET RIGHT OF
WAY, THE LATERAL SHALL TERMINATE 3 FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY
EASEMENT.
31. THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE LOCATION
OF THE SEWER LATERAL.
32. IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED IMPROVEMENTS,
THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY.
33. NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN
PLACED, INSPECTED AND APPROVED.
34. ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING
OF STREETS.
35. APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT PRIOR TO
PLACEMENT.
36. ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVE BOXES SHALL BE RAISED TO FINISHED
GRADE BY THE PAVING CONTRACTOR UPON COMPLETION OF PAVING.
37. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING,
BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION OF THE CITY
TRAFFIC ENGINEER.
38. AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OR RECORD,
WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER.
PRIVATE ENGINEER'S NOTICE
TO CONTRACTORS:
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND
UTILITY PIPES OR STRUCTURES SHOWN ON THESE PLANS
ARE OBTAINED BY A SEARCH OF AVAILABLE RECORDS. TO
THE BEST OF OUR KNOWLEDGE THERE ARE NO EXISTING
UTILITIES EXCEPT AS SHOWN ON THESE PLANS.
ALL CONTRACTORS AND SUBCONTRACTORS PERFORMING
WORK SHOWN ON OR RELATED TO THESE PLANS SHALL
CONDUCT THEIR OPERATIONS SO THAT ALL EMPLOYEES ARE
PROVIDED A SAFE PLACE TO WORK AND THE PUBLIC IS
PROTECTED. ALL CONTRACTORS AND SUBCONTRACTORS
SHALL COMPLY WITH THE "OCCUPATIONAL SAFETY AND
HEALTH REGULATIONS" OF THE U.S DEPARTMENT OF LABOR,
AND WITH THE STATE OF CALIFORNIA DEPARTMENT OF
INDUSTRIAL RELATIONS' "CONSTRUCTION SAFETY ORDERS".
THE CIVIL ENGINEER SHALL NOT BE RESPONSIBLE IN ANY
WAY FOR THE CONTRACTORS' AND SUBCONTRACTORS'
COMPLIANCE WITH THE "OCCUPATIONAL SAFETY AND HEALTH
REGULATIONS" OF THE U.S. DEPARTMENT OF LABOR OR
WITH THE STATE OF CALIFORNIA DEPARTMENT OF INDUSTRIAL
RELATIONS' "CONSTRUCTION SAFETY ORDERS".
CONTRACTOR FURTHER AGREES THAT HE SHALL ASSUME
SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE
CONDITIONS DURING THE COURSE OF CONSTRUCTION OF
THIS PROJECT, INCLUDING SAFEIY OF ALL PERSONS AND
PROPERTY; THAT THIS REQUIREMENT SHALL APPLY
CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING
HOURS; AND THAT THE CONTRACTOR SHALL DEFEND,
INDEMNIFY AND HOLD THE OWNER AND THE ENGINEER
HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED,
IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS
PROJECT, EXCEPTING FOR ANY LIABILITY ARISING FROM THE
SOLE NEGLIGENCE OF THE OWNER OR ENGINEER.
for ner stone
Land Surveying Inc.
A.L.T.A.•Topograph i c • Bmdwy • Construct Ion • Env iroranta I
20730 It\OB PLACE
PERRIS, CA 92570
PH (951) 26-0200 CL (949) 2 -M- 7 099
NOTES:
CITY ACCEPTANCE OF PLANS DOES NOT RELIEVE THE
DEVELOPER FROM RESPONSIBILITY FOR THE CORRECTION OF
ERRORS AND OMISSIONS DISCOVERED DURING CONSTRUCTION.
UPON REQUEST OF THE CITY INSPECTOR, THE REQUIRED PLAN
REVISIONS SHALL BE PROMPTLY SUBMITTED TO THE CITY
ENGINEER FOR REVIEW.
CONSTRUCTION CONTRACTOR AGREES THAT IN ACCORDANCE WITH
GENERALLY ACCEPTED CONSTRUCTION PRACTICES CONSTRUCTION
CONTRACTOR WLL BE REQUIRED TO ASSUME SOLE AND
COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING
THE COURSE OF CONSTRUCTION OF THE PROJECT, INCLUDING
SAFEIY OF ALL PERSONS AND PROPERTY; THAT THIS
REQUIREMENT SHALL BE MADE TO APPLY CONTINOUSLY AND
NOT BE LIMITED TO NORMAL WORKING HOURS, AND
CONSTRUCTION CONTRACTOR FURTHER AGREES TO DEFEND,
INDEMNIFY AND HOLD DESIGN PROFESSIONAL HARMLESS FROM
ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION
WITH THE PERFORMANCE OF WORK ON THIS PROJECT,
EXCEPTING LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF
DESIGN PROFESSIONAL
Q �
DIAL
DIAL TWOWORKING
BEFORE �SV BOF�E
BEFORE • DAYS BEFORE
YOU DIG 'YOU DIG
YOU DIG �_pnn�>i->cnn
TOLL FREE 1-800-227-2600
A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT
REV.
IMPROVEMENT PLAN
CORNER
OF
FONTANA
AVENUE
AND
LEMON
STREET
PROPERTY LINE (TYP)
% y / APN 193-021-26
(N.A.P.) --
�k 1
f
't
/ml
APN 193y021-22 ,, `� � APN 193-021-09
PROPERTY LINE (TYP) 1
INDEX MAP
1 =100'
CONSTRUCTION NOTES QTY.
O1 CONSTRUCT NEW 4' SEWER MANHOLE PER CITY STD. PLAN. 2000,
2003 & 2001. 2 EA.
2 CONSTRUCT, 8" DIA. EXTRA STRENGTH VCP SEWER MAIN LINE, 360 L.F.
BEDDING & BACKFILL PER STD. 1008
�3 CONSTRUCT 4" DIA. VCP SEWER LATERAL HOUSE CLEANOUT
PER STD. PLAN NO. 2005. 115 L.F.
O4 CONSTRUCT SEWER CLEANOUT BOX PER CITY STD. PLAN N0. 2007.
O REPAIR TRENCH PER STD. PLAN N0. 1008
O ABANDON EX. SEWER LATERAL.
�7 CONSTRUCT 6.5" MIN. AC PAVEMENT OVER 12" MIN. OF
OF 95% COMPACTED NATIVE SUBGRADE PER
CITY STD. PLAN NO. 400.
O8 RECONSTRUCT MH BOTTOM AS NECESSARY
PER STD. 2003 CASE II
UTILITY CONTACTS:
EL IC
SEWER
SOUTHERN CALIFORNIA EDISON
CITY OF FONTANA
501 SOUTH MARENGO AVENUE
8353 SIERRA AVENUE
BLDG "E"
FONTANA, CA 92335
ALHAMBRA, CA 91802
909-350-6632
626-308-6313
ATTN: ORLANDO OLIVAS
WATER
FONTANA WATER COMPANY
GAS
11142 GARVEY AVENUE
THE GAS COMPANY
EL MONTE, CA 91733
1918 WEST LUGONIA AVENUE
626-448-6183
REDLANDS, CA 92374
ATTN: LUIS MONTENEGRO
909-335-7715
ATTN: DENNIS WARE, PLANNER
TELEPHONE
AT&T
510-645-2929
ATTN: SUSAN BLACKBURN
CABLE TELEVISION
TIME WARNER TELECOM
3281 EAST GUASTI ROAD
SUITE 350
ONTARIO, CA 91761
909-456-3652
UNAUTHORIZED CHANGES
AND USES:
CAUTION: THE ENGINEER PREPARING THESE PLANS WILL NOT BE
RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES
TO OR USES Of THESE PLANS.
7 EA.
48 LF
2 EA.
240 SF
1 EA.
SHOULD CONSTRUCTION OF THE REQUIRED
IMPROVEMENTS NOT COMMENCE WITHIN TWO
YEARS OF THE DATE OF APPROVAL SHOWN HEREON
AND CARRIED FORTH IN A DILIGENT MANNER, THE
CITY ENGINEER MAY REQUIRE REVISIONS TO THE
PLANS TO BRING THEM INTO CONFORMANCE WITH
REVISION DESCRIPTION ENGR. DATE CITY DATE STANDARDS IN EFFECT.
ASSESSOR'S
PARCEL NUMBER:
0193-021-50, -51, -52, -53, -06, -07, & -08,
PREPARED FOR/
OWNER/SUBDIVIDER:
SECURED INCOME GROUP, INC.
ATTN: MR. MAX MCDERMOTT
17592 17TH STREET, SUITE 100
TUSTIN, CA. 92780
(714) 721-7788 OFFICE
(714) 368-0012 FAX
PROPERTY ADDRESS:
FONTANA AVE AND LEMON ST.
ZONING:
SINGLE FAMILY RESIDENTIAL
SHEET INDEX:
SHEET 1: TITLE SHEET
SHEET 2: SEWER PLAN AND PROFILE
LEGEND AND ABBREVIATION:
�SCO
PROPOSED SEWERLINE
EXISTING SEWERLINE
CLEANOUT PER CITY STD.
n MANHOLE PER CITY STD.
4
Rb
No. 5Z
* Exp.
CIVIL
\ c`
SEWER LATERAL PER
CITY STD. DWG.
SEWER TRENCH
FOOTHILL 66
BOULEVARD
ARROW
BOULEVARD
W
z
W
W
�
>
a
z
w
a
MERRILL
STREET
PROJECT SITE
cn
w
J
Uj
(��
W
a
RANDALL
AVENUE
w
a
<
Li
a
Uj Uj
0-
SAN BERNARDINO
AVENUE
W
0
W
c.�
VALLEY
BOULEVARD
10
SAN BERNARDINO FREEWAY
ABAND ABANDON
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN SOCIETY FOR TESTING MATERIALS
AWWA AMERICAN WATER WORKS ASSOCIATION
BC BEGIN CURVE
BFV BUTTERFLY VALVE
BLD FLG BLIND FLANGE
BO BLOW OFF
BOT BOTTOM
CTS CATHODIC TEST STATION
CO CLEANOUT
CML/CMC CEMENT MORTAR LINED/CEMENT MORTAR COATED
CPLG COUPLING
DIP DUCTILE IRON PIPE
E EAST
EC END CURVE
ELEC ELECTRICAL
ESMT EASEMENT
EX EXIST
FH FIRE HYDRANT
FLG FLANGE OR FLANGED
FL FLOWLINE
G GAS LINE OR SERVICE
GPM GALLONS PER MINUTE
GV GATE VALVE
HPI HORIZONTAL POINT OF INTERSECTION
INV INVERT ELEVATION
IPS IRON PIPE SIZE
MH MANHOLE
N NORTH
PVC POLYVINYL CHLORIDE
S SEWER MAIN OR HOUSE LATERAL
SCO SEWER WATER CLEAN OUT
SD STORM DRAIN
ST LT STREET LIGHT
T TELEPHONE
UG UNDERGROUND
VCP VITRIFIED CLAY PIPE
VPI VERTICAL POINT OF INTERSECTION
W WEST
WM WATER METER
Prepared Under The Supervision Of :
DRAWN BY: GATS&cM
DESIGNED BY: GA'
Date : 2-1/- 20 CHECKED BY: SCL
STE AN C. LANTHIER RCE:59052
ELPC 19-0000-17
CITY OF FONTANA, CALIFORNIA
SEWER IMPROVEMENT PLANS
TITLE SHEET AS SHOWN
APN 0193-021-50,-51,-52,-53,-06, -07, & -08 DATE:
N/E_f_ TANA AVEN D LEMON STREET 2/06/2020
APPROVED B /f " DRAWING NO.: 1
5909
ENGINEER 11 2