HomeMy WebLinkAboutAppendix G - Geotechnical Investigation
GEOTECHNICAL INVESTIGATION
PROPOSED WAREHOUSE
NWC Slover Avenue and Cypress Avenue
Fontana, California
for
Duke Realty
22885 Savi Ranch Parkway Suite E Yorba Linda California 92887
voice: (714) 685-1115 fax: (714) 685-1118 www.socalgeo.com
August 10, 2021
Duke Realty
200 Spectrum Center Drive, Suite 1600
Irvine, CA 92618
Attention: Mr. George Atalla
Assistant Development Services Manager
Project No.: 20G226-3
Subject: Geotechnical Investigation
Proposed Warehouse
NWC Slover Avenue and Cypress Avenue
Fontana, California
Gentlemen:
In accordance with your request, we have conducted a geotechnical investigation at the subject
site. We are pleased to present this report summarizing the conclusions and recommendations
developed from our investigation.
We sincerely appreciate the opportunity to be of service on this project. We look forward to
providing additional consulting services during the course of the project. If we may be of further
assistance in any manner, please contact our office.
Respectfully Submitted,
SOUTHERN CALIFORNIA GEOTECHNICAL, INC.
Joseph Lozano Leon
Staff Engineer
Robert G. Trazo, GE 2655
Principal Engineer
Distribution: (1) Addressee
Proposed Warehouse– Fontana, CA Project No. 20G226-3
TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY 1
2.0 SCOPE OF SERVICES 3
3.0 SITE AND PROJECT DESCRIPTION 4
3.1 Site Conditions 4
3.2 Proposed Development 5
3.3 Previous Studies 5
4.0 SUBSURFACE EXPLORATION 8
4.1 Scope of Exploration/Sampling Methods 8
4.2 Geotechnical Conditions 8
5.0 LABORATORY TESTING 10
6.0 CONCLUSIONS AND RECOMMENDATIONS 12
6.1 Seismic Design Considerations 12
6.2 Geotechnical Design Considerations 14
6.3 Site Grading Recommendations 16
6.4 Construction Considerations 20
6.5 Foundation Design and Construction 21
6.6 Floor Slab Design and Construction 22
6.7 Retaining Wall Design and Construction 23
6.8 Pavement Design Parameters 26
7.0 GENERAL COMMENTS 28
APPENDICES
A Plate 1: Site Location Map
Plate 2: Boring Location Plan
B Boring Logs
C Laboratory Test Results
D Grading Guide Specifications
E Seismic Design Parameters
F Excerpts from Previous Study
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 1
1.0 EXECUTIVE SUMMARY
Presented below is a brief summary of the conclusions and recommendations of this investigation.
Since this summary is not all inclusive, it should be read in complete context with the entire
report.
Geotechnical Design Considerations
• Artificial fill soils were encountered at all of the boring locations for the previous and current
investigations performed within the project site, extending from the ground surface to depths
of 2½ to 8± feet.
• The fill soils and near-surface alluvial soils possess varying strengths. The existing fill soils are
considered to represent undocumented fill. These soils, in their present condition, are not
considered suitable for support of the foundation loads of the new structure. The results of
laboratory testing indicate that the near-surface soils within the upper 5 to 6± feet possess a
moderate potential for collapse when exposed to moisture infiltration as well as consolidation
when exposed to load increases in the range of those that will be exerted by the new
foundations. Additionally, it is anticipated that demolition of the existing structures and
associated improvements will cause disturbance of the upper 4 to 5± feet with isolated areas
extending to 10 to 12± feet.
• Remedial grading will be necessary to remove all of the undocumented fill soils in their
entirety, the upper portion of the near-surface native alluvial soils, and any soils disturbed
during the demolition process, and replace these materials as compacted structural fill soils.
Site Preparation Recommendations
• The site plan provided to our office indicates that the existing structures and pavements at
the subject site will be demolished in order to facilitate the construction of the proposed
development. Demolition should include all foundations, floor slabs, pavements, utilities and
any other subsurface improvements that will not remain in place with the new development.
Debris resultant from demolition should be disposed of off-site. Alternatively, concrete and
asphalt debris may be pulverized to a maximum 2-inch particle size, well mixed with the on-
site soils, and incorporated into new structural fills or it may be crushed and made into CMB.
• Remedial grading is recommended to be performed within the proposed building area in order
to remove all of the undocumented fill soils in their entirety, the upper portion of the near-
surface native alluvial soils, and any soils disturbed during the demolition process. The soils
within the proposed building area should be overexcavated to a depth of 5 feet below existing
grade and to a depth of at least 5 feet below proposed building pad subgrade elevations.
• The depth of overexcavation should also be sufficient to remove any existing fill soils. The
proposed foundation influence zones should be overexcavated to a depth of at least 3 feet
below proposed foundation bearing grade.
• Following completion of the overexcavation, the exposed soils should be scarified to a depth
of at least 12 inches, and thoroughly flooded to raise the moisture content of the underlying
soils to at least 0 to 4 percent above optimum moisture content. If native sands or gravelly
sands are encountered at the bottom of the overexcavation, these soils should be thoroughly
flooded to raise the moisture content of the underlying soils to at least 0 to 4 percent above
optimum moisture content, extending to a depth of at least 24 inches. The overexcavation
subgrade soils should then be recompacted to at least 90 percent of the ASTM D-1557
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 2
maximum dry density. The previously excavated soils may then be replaced as compacted
structural fill.
• The new pavement and flatwork subgrade soils are recommended to be scarified to a depth
of 12± inches, moisture conditioned and recompacted to at least 90 percent of the ASTM D-
1557 maximum dry density.
• Based on the results of corrosivity testing performed in the previous and current
investigations, the on-site soils are considered to be corrosive to ductile iron pipe and to
copper pipe.
Foundation Design Recommendations
• Conventional shallow foundations, supported in newly placed compacted fill.
• 3,000 lbs/ft2 maximum allowable soil bearing pressure.
• Reinforcement consisting of at least two (2) No. 5 rebars (1 top and 1 bottom) in strip footings.
Additional reinforcement may be necessary for structural considerations.
Building Floor Slab Design Recommendations
• Conventional Slabs-on-Grade: minimum 6-inch thickness.
• Modulus of Subgrade Reaction: k = 150 psi/in.
• Reinforcement is not expected to be necessary for geotechnical considerations.
• The actual thickness and reinforcement of the floor slab should be determined by the
structural engineer.
Pavement Design Recommendations
ASPHALT PAVEMENTS (R=50)
Materials
Thickness (inches)
Auto Parking and
Auto Drive Lanes
(TI = 4.0 to 5.0)
Truck Traffic
TI = 6.0 TI = 7.0 TI = 8.0 TI = 9.0
Asphalt Concrete 3 3½ 4 5 5½
Aggregate Base 3 4 5 5 7
Compacted Subgrade 12 12 12 12 12
PORTLAND CEMENT CONCRETE PAVEMENTS (R=50)
Materials
Thickness (inches)
Autos and Light
Truck Traffic
(TI = 6.0)
Truck Traffic
TI = 7.0 TI = 8.0 TI = 9.0
PCC 5 5½ 6½ 8
Compacted Subgrade
(95% minimum compaction) 12 12 12 12
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 3
2.0 SCOPE OF SERVICES
The scope of services performed for this project was in accordance with our Change Order No.
20G226-CO2, dated July 9, 2021. The scope of services included the review of the previous
geotechnical investigation performed within the eastern ⅔ of the overall project site, and a visual
site reconnaissance, subsurface exploration, field and laboratory testing, and geotechnical
engineering analysis in the western ⅓ region to provide criteria for preparing the design of the
building foundations, building floor slab, and parking lot pavements along with site preparation
recommendations and construction considerations for the proposed development. The evaluation
of the environmental aspects of this site was beyond the scope of services for this geotechnical
investigation.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 4
3.0 SITE AND PROJECT DESCRIPTION
3.1 Site Conditions
The subject site is located at the northwest corner of Slover Avenue and Cypress Avenue in
Fontana, California. The site is bounded to the north by Union Pacific railroad tracks, to the east
by Cypress Avenue and an easement, to the south by Slover Avenue, and to the west by Oleander
Ave and a relatively new industrial development. A portion of Boyle Avenue bisects the site in the
east-west direction. The general location of the site is illustrated on the Site Location Map,
included as Plate 1 in Appendix A of this report.
The site consists of several rectangular-shaped parcels, which total 30.81± acres in size. The
parcels within the southwestern quadrant of the site are developed with single-family residences
(SFRs) of wood-frame and stucco construction. The existing buildings within these parcels range
from 500 to 4,500± ft². Ground surface cover within these parcels consists of exposed soils and
turf grass. Drive lanes within the parcels consist of crushed aggregate base with some areas of
concrete flatwork. The parcels within the southeastern quadrant of the site are currently vacant
and undeveloped. Based on recent readily available aerial photographs obtained from Google
Earth, dated 2019, these parcels were developed with SFRs ranging from 1,045 to 2,065± ft² in
size. The ground surface consists of exposed soil with sparse native grass and shrubs. Several
large trees are present throughout the parcels located south of Boyle Avenue.
The northwestern quadrant consists of several parcels which are also developed with SFRs of
wood-frame and stucco construction. The existing buildings within these parcels range from 1,100
to 4,600± ft² in size. On of these parcels is currently vacant and was previously utilized as truck-
trailer storage. One of the SFRs located in the central-northern parcel includes a basement,
approximately 10 to 12± feet in depth. Ground surface cover within these parcels consists of
crushed aggregate base, areas of fair-conditioned concrete flatwork, turf grass, and exposed soil.
The parcels in the northeastern quadrant consist of a construction equipment storage yard, a
truck and trailer storage, and a vacant lot. These parcels are developed with one-story wood-
frame and stucco construction office buildings, ranging from 1,500 to 4,800± ft2 in size. The
construction storage lot also includes two (2) two-to-three-story sheet metal structures, 2,400±
ft2 in size. It should be noted that buried concrete exists on the western-face of the storage
buildings, extending 15-20± feet away from the building. Ground surface cover within these lots
consists of open graded gravel, fairly deteriorated Portland cement concrete pavements, and
areas of exposed soil. Occasional large trees are present throughout the parcels located north of
Boyle Avenue.
Detailed topographic information was not available at the time of this report. However, based on
topographic information obtained from Google Earth, the site topography slopes gently downward
to the south at a gradient of approximately 2 percent.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 5
3.2 Proposed Development
A conceptual site plan, identified as Scheme 7 and prepared by HPA, Inc., for the proposed
development was provided to our office by the client. Based on this plan, the subject site will be
developed with a 611,997± ft² warehouse, located in the central region of the site. Dock-high
doors will be constructed in a cross-dock configuration on the south and north sides of the
building. The proposed building is expected to be surrounded by asphaltic concrete (AC)
pavements in the parking and drive areas, Portland cement concrete (PCC) pavements in the
loading dock areas, and concrete flatwork and landscaped planters throughout the site.
Detailed structural information has not been provided. We assume that the new warehouse will
be a single-story structure of tilt-up concrete construction, supported on a conventional shallow
foundation system with a concrete slab-on-grade floor. Based on the assumed construction,
maximum column and wall loads are expected to be on the order of 100 kips and 4 to 6 kips per
linear foot, respectively.
No significant amounts of below-grade construction, such as basements or crawl spaces, are
expected to be included in the proposed development. Based on the assumed topography, cuts
and fills of 3 to 5± feet are expected to be necessary to achieve the proposed site grades.
3.3 Previous Studies
Southern California Geotechnical, Inc. (SCG) previously performed a geotechnical investigation
within the southeastern quadrant of the subject site for the previously proposed development.
The previously proposed development consisted of a 180,360± ft2 warehouse building located in
the northeastern region of the previous project site. The results of this investigation are presented
in the report referenced as follows:
Geotechnical Investigation, Proposed Warehouse, NWC Slover Avenue and Cypress
Avenue, Fontana, California, prepared by SCG, prepared for Duke Realty, SCG Project No.
18G213-1, dated November 19, 2018.
As part of this investigation, six (6) borings (identified as Boring Nos. B-1 through B-6) were
advanced to depths of 20 to 25± feet below the existing site grades. The approximate locations
of the previous borings are indicated on the Boring Location Plan, included as Plate 2 in Appendix
A of this report. AC pavements were encountered at the ground surface at Boring No. B-4, with
no discernible layer of underlying aggregate base. The pavements generally consisted of 1½±
inches of AC. Artificial fill soils were encountered at the ground surface or beneath the pavements
at four of the six boring locations, extending to depths of 2½ to 3½± feet. The fill soils generally
consisted of loose to very dense sands and silty sands. Native alluvial soils were encountered at
the ground surface or beneath the fill soils at all of the boring locations, extending to at least the
maximum depth explored of 25± feet. The alluvium generally consisted of medium dense to very
dense silty sands, gravelly sands, and sandy gravel with occasional cobbles. Free water was not
encountered during the drilling of any of the borings. Based on the lack of water within the
borings, the groundwater was considered to have existed at a depth in excess of 25± feet at the
time of the previous subsurface exploration.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 6
Laboratory testing performed by SCG for this study included consolidation/collapse testing,
maximum density/optimum moisture, and soluble content.
Based upon the identified subsurface conditions, remedial grading was recommended to be
performed within the previously proposed building pad area in order to remove the existing
undocumented fill soils. The previously proposed building area was recommended to be
overexcavated to a depth of at least 3 feet below existing grade and to a depth of at least 3 feet
below proposed pad grade. It was also recommended to extend the overexcavation to a depth
of at least 2 feet below foundation bearing grade within the foundation influence zones. The
foundations were recommended to be designed for a maximum allowable soil bearing pressure
of 3,000 lbs/ft2. Excerpts from the previous study, including the boring logs, along with the results
of laboratory testing, are included in Appendix F of this report.
SCG also performed additional geotechnical investigation within the eastern ⅔ of the overall
project site for the previously proposed development. The previously proposed development
consisted of a 180,360± ft2 warehouse building located in the northeastern region of the previous
project site. The results of this investigation are presented in the report referenced as follows:
Geotechnical Investigation, Proposed Warehouse, NWC Slover Avenue and Cypress
Avenue, Fontana, California, prepared by SCG, prepared for Duke Realty, SCG Project No.
20G226-1, dated December 2,2020.
As part of this investigation seven (7) additional borings (identified as Boring Nos. B-7 through
B-13) were advanced to depths of 20 to 25± feet below the existing site grades. The approximate
locations of the previous borings are indicated on the Boring Location Plan, included as Plate 2 in
Appendix A of this report. PCC pavements were encountered at Boring Nos. B-8 and B-9,
measuring 8± inches in thickness with no discernable underlain aggregate base. Artificial fill soils
were encountered at the ground surface and beneath the existing pavements at all of the boring
locations, extending to depths of 2½ to 8± feet. The fill soils generally consisted of loose to
medium dense silty sands and sandy silts. At Boring No. B-13, the fill soils consisted of medium
dense gravelly sands. Native alluvium was encountered beneath the artificial fill soils at all boring
locations, extending to at least the maximum explored depth of 25± feet. The near-surface alluvial
soils generally consisted of medium dense to very dense sands, gravelly sands and sandy silts.
Occasional cobbles were encountered within the alluvial strata. Free water was not encountered
during the drilling of any of the borings. Based on the lack of water within the borings, the
groundwater was considered to have existed at a depth in excess of 25± feet at the time of the
previous subsurface exploration.
Laboratory testing performed by SCG for this study included additional consolidation/collapse
testing, maximum density/optimum moisture, and soluble content, as well as corrosivity testing.
Based on the results of corrosivity testing, the on-site soils were considered to be corrosive to
ductile iron pipe and to copper pipe.
Based upon the identified subsurface conditions, remedial grading was recommended to be
performed within the previously proposed building pad area in order to remove the existing
undocumented fill soils. The previously proposed building area was recommended to be
overexcavated to a depth of at least 3 feet below existing grade and to a depth of at least 3 feet
below proposed pad grade. It was also recommended to extend the overexcavation to a depth
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 7
of at least 2 feet below foundation bearing grade within the foundation influence zones. The
foundations were recommended to be designed for a maximum allowable soil bearing pressure
of 3,000 lbs/ft2. Excerpts from the previous study, including the boring logs, along with the results
of laboratory testing, are included in Appendix F of this report.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 8
4.0 SUBSURFACE EXPLORATION
4.1 Scope of Exploration/Sampling Methods
The subsurface exploration conducted for this phase of the project consisted of five (5) borings
(identified as Boring Nos. B-14 through B-18), advanced to depths of 10 and 25± feet below the
existing site grades. All of the borings were logged during drilling by a member of our staff. As
indicated in Section 3.3 of this report, a total of eighteen (18) borings were drilled for the overall
project site.
The borings were advanced with hollow-stem augers, by a conventional truck-mounted drilling
rig. Representative bulk and relatively undisturbed soil samples were taken during drilling.
Relatively undisturbed soil samples were taken with a split barrel “California Sampler” containing
a series of one inch long, 2.416± inch diameter brass rings. This sampling method is described
in ASTM Test Method D-3550. In-situ samples were also taken using a 1.4± inch inside diameter
split spoon sampler, in general accordance with ASTM D-1586. Both of these samplers are driven
into the ground with successive blows of a 140-pound weight falling 30 inches. The blow counts
obtained during driving are recorded for further analysis. Bulk samples were collected in plastic
bags to retain their original moisture content. The relatively undisturbed ring samples were placed
in molded plastic sleeves that were then sealed and transported to our laboratory.
The approximate locations of the borings from this investigation are indicated on the Boring
Location Plan, included as Plate 2 in Appendix A of this report. The Boring Logs, which illustrate
the conditions encountered at the boring locations, as well as the results of some of the laboratory
testing, are included in Appendix B.
4.2 Geotechnical Conditions
Artificial Fill
Artificial fill soils were encountered at the ground surface at all of the boring locations, extending
to depths of 3 to 7½± feet below the existing site grades. The fill soils generally consist of loose
to medium dense silty sands with varying fine to coarse Gravel. The fill soils possess a disturbed
mottled appearance resulting in their classification as artificial fill. As indicated in Section 3.3 of
this report, fill soils were encountered at the ground surface and beneath the existing pavements
at all of the previous boring locations, extending to depths of 2½ to 8± feet.
Alluvium
Native alluvium was encountered beneath the artificial fill soils at all boring locations, extending
to at least the maximum depth explored of 25± feet below existing site grades. The alluvium
generally consists of medium dense to very dense sands, gravelly sands and silty sands, with
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 9
occasional medium dense sandy silts. Boring No. B-16 encountered a stratum of loose sandy silts
at depths of 4½ to 6½± feet. Occasional to extensive cobbles were encountered at most of the
boring locations as shallow as of 7± feet from the ground surface.
Groundwater
Free water was not encountered during the drilling of any of the borings. Based on the lack of
any water within the borings, and the moisture contents of the recovered soil samples, the static
groundwater is considered to have existed at a depth in excess of 25± feet at the time of the
subsurface exploration.
As a part of our research, we reviewed available groundwater data in order to determine
groundwater levels for the site. Water level data was obtained from the California Department of
Water Resources Water Data Library website, https://wdl.water.ca.gov/waterdatalibrary/. The
nearest monitoring well on record (identified as State Well Number: 01S06W24R001S) is located
½± mile west of the project site. Water level readings within this monitoring well indicate a high
groundwater level of 322± feet below the ground surface in April 1995.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 10
5.0 LABORATORY TESTING
The soil samples recovered from the subsurface exploration were returned to our laboratory for
further testing to determine selected physical and engineering properties of the soils. The tests
are briefly discussed below. It should be noted that the test results are specific to the actual
samples tested, and variations could be expected at other locations and depths. Test results from
the previous studies are denoted using the project numbers (18G213-1 and 20G226-1). The test
results from the previous studies are included in Appendix F.
Classification
All recovered soil samples were classified using the Unified Soil Classification System (USCS), in
accordance with ASTM D-2488. The field identifications were then supplemented with additional
visual classifications and/or by laboratory testing. The USCS classifications are shown on the
Boring Logs and are periodically referenced throughout this report.
Density and Moisture Content
The density has been determined for selected relatively undisturbed ring samples. These densities
were determined in general accordance with the method presented in ASTM D-2937. The results
are recorded as dry unit weight in pounds per cubic foot. The moisture contents are determined
in accordance with ASTM D-2216, and are expressed as a percentage of the dry weight. These
test results are presented on the Boring Logs. The results of additional testing performed during
the previous studies are included in Appendix F of this report.
Consolidation
Selected soil samples were tested to determine their consolidation potential, in accordance with
ASTM D-2435. The testing apparatus is designed to accept either natural or remolded samples in
a one-inch high ring, approximately 2.416 inches in diameter. Each sample is then loaded
incrementally in a geometric progression and the resulting deflection is recorded at selected time
intervals. Porous stones are in contact with the top and bottom of the sample to permit the
addition or release of pore water. The samples are typically inundated with water at an
intermediate load to determine their potential for collapse or heave. The results of the
consolidation testing are plotted on Plates C-1 through C-4 in Appendix C of this report. Additional
consolidation test results performed during the previous studies are included in Appendix F.
Maximum Dry Density and Optimum Moisture Content
Two representative bulk samples of the on-site soils, one from each of the previous studies, have
been tested for their maximum dry density and optimum moisture content. The results have been
obtained using the Modified Proctor procedure, per ASTM D-1557 and are included in Appendix F
of this report. This test is generally used to compare the in-situ densities of undisturbed field
samples, and for later compaction testing. Additional testing of other soil types or soil mixes may
be necessary at a later date.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 11
Soluble Sulfates
Representative samples of the near-surface soils have been submitted to a subcontracted
analytical laboratory for determination of soluble sulfate content. Soluble sulfates are naturally
present in soils, and if the concentration is high enough, can result in degradation of concrete
which comes into contact with these soils. The results of the soluble sulfate testing are presented
below, and are discussed further in a subsequent section of this report.
Sample Identification Soluble Sulfates (%) ACI Classification
B-2 @ 0 to 5 feet (18G213-1) 0.003 Not Applicable (S0)
B-4 @ 0 to 5 feet (18G213-1) 0.005 Not Applicable (S0)
B-7 @ 0 to 5 feet (20G226-1) 0.005 Not Applicable (S0)
B-16 @ 0 to 5 feet 0.001 Not Applicable (S0)
Corrosivity Testing
Representative samples of the near-surface soils have been submitted to a subcontracted
corrosion engineering laboratory to identify potentially corrosive characteristics with respect to
common construction materials. The corrosivity testing included a determination of the electrical
resistivity, pH, and chloride and nitrate concentrations of the soils, as well as other tests. The
results of some of these tests are presented below.
Sample Identification Saturated Resistivity
(ohm-cm) pH Chlorides
(mg/kg)
Nitrates
(mg/kg)
B-7 @ 0 to 5 feet (20G226-1) 2,120 7.5 13 302
B-16 @ 0 to 5 feet 15,600 7.2 4.6 77
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 12
6.0 CONCLUSIONS AND RECOMMENDATIONS
Based on the results of our review, field exploration, laboratory testing and geotechnical analysis,
the proposed development is considered feasible from a geotechnical standpoint. The
recommendations contained in this report should be taken into the design, construction, and
grading considerations.
The recommendations are contingent upon all grading and foundation construction activities
being monitored by the geotechnical engineer of record. The recommendations are provided with
the assumption that an adequate program of client consultation, construction monitoring, and
testing will be performed during the final design and construction phases to verify compliance
with these recommendations. Maintaining SCG as the geotechnical consultant from the beginning
to the end of the project will provide continuity of services. The geotechnical engineering firm
providing testing and observation services shall assume the responsibility of Geotechnical
Engineer of Record.
The Grading Guide Specifications, included as Appendix D, should be considered part of this
report, and should be incorporated into the project specifications. The contractor and/or owner
of the development should bring to the attention of the geotechnical engineer any conditions that
differ from those stated in this report, or which may be detrimental for the development.
6.1 Seismic Design Considerations
The subject site is located in an area which is subject to strong ground motions due to
earthquakes. The performance of a site specific seismic hazards analysis was beyond the scope
of this investigation. However, numerous faults capable of producing significant ground motions
are located near the subject site. Due to economic considerations, it is not generally considered
reasonable to design a structure that is not susceptible to earthquake damage. Therefore,
significant damage to structures may be unavoidable during large earthquakes. The proposed
structures should, however, be designed to resist structural collapse and thereby provide
reasonable protection from serious injury, catastrophic property damage and loss of life.
Faulting and Seismicity
Research of available maps indicates that the subject site is not located within an Alquist-Priolo
Earthquake Fault Zone. Furthermore, SCG did not identify any evidence of faulting during the
previous and current geotechnical investigations. Therefore, the possibility of significant fault
rupture on the site is considered to be low.
The potential for other geologic hazards such as seismically induced settlement, lateral spreading,
tsunamis, inundation, seiches, flooding, and subsidence affecting the site is considered low.
Seismic Design Parameters
The 2019 California Building Code (CBC) provides procedures for earthquake resistant structural
design that include considerations for on-site soil conditions, occupancy, and the configuration of
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 13
the structure including the structural system and height. The seismic design parameters
presented below are based on the soil profile and the proximity of known faults with respect to
the subject site.
Based on standards in place at the time of this report, the proposed development is expected to
be designed in accordance with the requirements of the 2019 edition of the California Building
Code (CBC), which was adopted on January 1, 2020.
The 2019 CBC Seismic Design Parameters have been generated using the SEAOC/OSHPD Seismic
Design Maps Tool, a web-based software application available at the website
www.seismicmaps.org. This software application calculates seismic design parameters in
accordance with several building code reference documents, including ASCE 7-16, upon which
the 2019 CBC is based. The application utilizes a database of risk-targeted maximum considered
earthquake (MCER) site accelerations at 0.01-degree intervals for each of the code documents.
The table below was created using data obtained from the application. The output generated
from this program is included as Plate E-1 in Appendix E of this report.
The 2019 CBC requires that a site-specific ground motion study be performed in accordance with
Section 11.4.8 of ASCE 7-16 for Site Class D sites with a mapped S1 value greater than 0.2.
However, Section 11.4.8 of ASCE 7-16 also indicates an exception to the requirement for a site-
specific ground motion hazard analysis for certain structures on Site Class D sites. The
commentary for Section 11 of ASCE 7-16 (Page 534 of Section C11 of ASCE 7-16) indicates that
“In general, this exception effectively limits the requirements for site-specific hazard analysis to
very tall and or flexible structures at Site Class D sites.” Based on our understanding of the
proposed development, the seismic design parameters presented below were
calculated assuming that the exception in Section 11.4.8 applies to the proposed
structure at this site. However, the structural engineer should verify that this
exception is applicable to the proposed structure. Based on the exception, the spectral
response accelerations presented below were calculated using the site coefficients (Fa and Fv)
from Tables 1613.2.3(1) and 1613.2.3(2) presented in Section 16.4.4 of the 2019 CBC.
2019 CBC SEISMIC DESIGN PARAMETERS
Parameter Value
Mapped Spectral Acceleration at 0.2 sec Period SS 1.790
Mapped Spectral Acceleration at 1.0 sec Period S1 0.600
Site Class --- D
Site Modified Spectral Acceleration at 0.2 sec Period SMS 1.790
Site Modified Spectral Acceleration at 1.0 sec Period SM1 1.020
Design Spectral Acceleration at 0.2 sec Period SDS 1.193
Design Spectral Acceleration at 1.0 sec Period SD1 0.680
It should be noted that the site coefficient Fv and the parameters SM1 and SD1 were not included
in the SEAOC/OSHPD Seismic Design Maps Tool output for the 2019 CBC. We calculated these
parameters-based on Table 1613.2.3(2) in Section 16.4.4 of the 2019 CBC using the value of S1
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 14
obtained from the Seismic Design Maps Tool, assuming that a site-specific ground motion hazards
analysis is not required for the proposed building at this site.
Liquefaction
Liquefaction is the loss of strength in generally cohesionless, saturated soils when the pore-water
pressure induced in the soil by a seismic event becomes equal to or exceeds the overburden
pressure. The primary factors which influence the potential for liquefaction include groundwater
table elevation, soil type and grain size characteristics, relative density of the soil, initial confining
pressure, and intensity and duration of ground shaking. The depth within which the occurrence
of liquefaction may impact surface improvements is generally identified as the upper 50 feet
below the existing ground surface. Liquefaction potential is greater in saturated, loose, poorly
graded fine sands with a mean (d50) grain size in the range of 0.075 to 0.2 mm (Seed and Idriss,
1971). Clayey (cohesive) soils or soils which possess clay particles (d<0.005mm) in excess of 20
percent (Seed and Idriss, 1982) are generally not considered to be susceptible to liquefaction,
nor are those soils which are above the historic static groundwater table.
The California Geological Survey (CGS) has not yet conducted detailed seismic hazards mapping
in the area of the subject site. The general liquefaction susceptibility of the site was determined
by research of the San Bernardino County Land Use Plan, General Plan, Geologic Hazard Overlays.
Map FH29 for the Fontana 7.5-Minute Quadrangle indicates that the subject site is not located
within an area of liquefaction susceptibility. Based on the mapping performed by the county of
San Bernardino and the lack of a historic high ground water table within the upper 50± feet of
the ground surface, liquefaction is not considered to be a design concern for this project.
6.2 Geotechnical Design Considerations
General
The near-surface soils encountered at the boring locations from the previous and current studies
consist of artificial fill soils and native alluvium. The artificial fill soils, where encountered, extend
to depths of 2½ to 8± feet below the existing site grades. The fill soils and near-surface alluvial
soils possess varying strengths. The existing fill soils are considered to represent undocumented
fill. These soils, in their present condition, are not considered suitable for support of the
foundation loads of the new structure. The results of laboratory testing indicate that the near-
surface soils within the upper 5 to 6± feet possess a moderate potential for collapse when
exposed to moisture infiltration as well as consolidation when exposed to load increases in the
range of those that will be exerted by the new foundations. Additionally, it is anticipated that
demolition of the existing structures and associated improvements will cause disturbance of the
upper 4 to 5± feet with isolated areas extending to 10 to 12± feet due to the presence of a
subterranean level within one of the existing SFRs. Therefore, remedial grading is considered
warranted within the proposed building areas in order to remove all of the undocumented fill soils
in their entirety, the upper portion of the near-surface native alluvial soils, and any soils disturbed
during the demolition process, and replace these materials as compacted structural fill soils.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 15
Settlement
The recommended remedial grading will remove the existing undocumented fill soils, as well as
the potentially compressible/collapsible near-surface native alluvium, and replace these materials
as compacted structural fill. The native soils that will remain in place below the recommended
depth of overexcavation will not be subject to significant stress increases from the foundations of
the new structures. Therefore, following completion of the recommended grading, post-
construction settlements are expected to be within tolerable limits.
Expansion
The on-site soils generally consist of sands and silty sands with varying amounts of gravel. These
materials have been visually classified as non-expansive. Therefore, no design considerations
related to expansive soils are considered warranted for this site.
Soluble Sulfates
The results of the soluble sulfate testing indicate that the selected samples of the on-site soils,
from the previous and current investigations, contain sulfate concentrations that correspond to
Class S0 with respect to the American Concrete Institute (ACI) Publication 318-05 Building Code
Requirements for Structural Concrete and Commentary, Section 4.3. Therefore, specialized
concrete mix designs are not considered to be necessary, with regard to sulfate protection
purposes. It is, however, recommended that additional soluble sulfate testing be conducted at
the completion of rough grading to verify the soluble sulfate concentrations of the soils which are
present at pad grade within the building area.
Corrosion Potential
The results of laboratory testing. from the previous and current investigations, indicate that the
tested samples of the near-surface on-site soils possess saturated resistivity values of 2,120 ohm-
cm and 15,600 ohm-cm, and pH values of 7.2 and 7.5. These test results have been evaluated
in accordance with guidelines published by the Ductile Iron Pipe Research Association (DIPRA).
The DIPRA guidelines consist of a point system by which characteristics of the soils are used to
quantify the corrosivity characteristics of the site. Resistivity and pH are two of the five factors
that enter into the evaluation procedure. Redox potential, relative soil moisture content and
sulfides are also included. Although sulfide testing was not part of the scope of services for this
project, we have evaluated the corrosivity characteristics of the on-site soils using resistivity, pH
and moisture content. Based on these factors, and utilizing the DIPRA procedure, the
on-site soils are considered to be slightly corrosive to ductile iron pipe. Therefore,
polyethylene protection may be required for cast iron or ductile iron pipes. It should be
noted that SCG does not practice in the field of corrosion engineering. Therefore, the client
may also wish to contact a corrosion engineer to provide a more thorough evaluation.
Relatively low concentrations (4.6 and 13 mg/kg) of chlorides were detected in the samples
submitted for corrosivity testing from the previous and current investigations. In general, soils
possessing chloride concentrations in excess of 500 parts per million (ppm) are considered to be
corrosive with respect to steel reinforcement within reinforced concrete. Based on the lack of any
significant chlorides in the tested samples, the site is considered to have a C1 chloride exposure
in accordance with the American Concrete Institute (ACI) Publication 318 Building Code
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 16
Requirements for Structural Concrete and Commentary. Therefore, a specialized concrete mix
design for reinforced concrete for protection against chloride exposure is not considered
warranted.
Nitrates
Nitrates present in soil can be corrosive to copper tubing at concentrations greater than 50 mg/kg.
The tested samples from the previous and current investigations possess nitrate concentrations
of 77 and 302 mg/kg. Based on these test results, the on-site soils are considered to be
corrosive to copper pipe. Since SCG does not practice in the area of corrosion
engineering, we recommend that the client contact a corrosion engineer to provide
recommendations for the protection of copper tubing/pipe in contact with the on-site
soils.
Shrinkage/Subsidence
Removal and recompaction of the existing fill soils and near-surface alluvium is estimated to result
in an average shrinkage of 1 to 13 percent. The potential shrinkage estimate is based on dry
density testing performed on small-diameter samples taken at the boring locations. If a more
accurate and precise shrinkage estimate is desired, SCG can perform a shrinkage study involving
several excavated test-pits where in-place densities are determined using in-situ testing methods
instead of laboratory density testing on small-diameter samples. Please contact SCG for details
and a cost estimate regarding a shrinkage study, if desired.
Minor ground subsidence is expected to occur in the soils below the zone of removal, due to
settlement and machinery working. The subsidence is estimated to be 0.1 feet.
These estimates are based on previous experience and the subsurface conditions encountered at
the boring locations. The actual amount of subsidence is expected to be variable and will be
dependent on the type of machinery used, repetitions of use, and dynamic effects, all of which
are difficult to assess precisely.
Grading and Foundation Plan Review
No grading or foundation plans were available at the time of this report. It is therefore
recommended that we be provided with copies of the preliminary plans, when they become
available, for review with regard to the conclusions, recommendations, and assumptions
contained within this report.
6.3 Site Grading Recommendations
The grading recommendations presented below are based on the subsurface conditions
encountered at the boring locations and our understanding of the proposed development. We
recommend that all grading activities be completed in accordance with the Grading Guide
Specifications included as Appendix D of this report, unless superseded by site-specific
recommendations presented below.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 17
Site Stripping and Demolition
The proposed development will require demolition of the existing pavements and structures.
Additionally, any existing improvements that will not remain in place for use with the new
development should be removed in their entirety. This should include all utilities, and any other
subsurface improvements associated with the existing pavements. The existing pavements are
not expected to be reused with the new development. Debris resultant from demolition should
be disposed of off-site. Concrete and asphalt debris may be re-used as compacted fill, provided
they are pulverized to a maximum particle size of less than 2 inches and mixed with the on-site
soils. Alternatively, existing asphalt and concrete materials may be crushed into miscellaneous
base (CMB) and re-used at the site.
Detailed structural information regarding the existing buildings has not been provided to our
office. Therefore, the foundation systems supporting the existing buildings are generally unknown
by SCG. We expect that the existing buildings are supported on conventional shallow foundations.
It should be noted that one of the existing SFRs includes a basement. The basement and existing
undocumented fill soils should be removed in their entirety, and the resultant excavations should
be backfilled with compacted structural fill soils.
Initial site stripping should also include removal of any surficial vegetation from the unpaved
areas of the site. This should include any weeds, grasses, shrubs, and trees. Root systems
associated with the trees should be removed in their entirety, and the resultant excavations
should be backfilled with compacted structural fill soils. Any organic materials should be removed
and disposed of off-site, or in non-structural areas of the property. The actual extent of site
stripping should be determined in the field by the geotechnical engineer, based on the organic
content and stability of the materials encountered.
Treatment of Existing Soils: Building Pad
Remedial grading should be performed within the proposed building pad area in order to remove
any soils disturbed during demolition, the existing undocumented fill soils, and the upper portion
of the near-surface native alluvium. Based on conditions encountered at the boring locations from
the previous and current investigations, we recommend that the existing soils within the proposed
building area be overexcavated to a depth of at least 5 feet below existing grade and to a depth
of at least 5 feet below proposed building pad subgrade elevations, whichever is greater. The
depth of the overexcavation should also extend to a depth sufficient to remove all
undocumented fill soils. The undocumented fills extend to depths of 2½ to 8± feet at most
of the boring locations. Additional overexcavation should be performed within the influence zones
of the new foundations, to provide for a new layer of compacted structural fill extending to a
depth of at least 3 feet below proposed bearing grades.
The overexcavation areas should extend at least 5 feet beyond the building and foundation
perimeters, and to an extent equal to the depth of fill placed below the foundation bearing grade,
whichever is greater. If the proposed structure incorporates any exterior columns (such as for a
canopy or overhang) the area of overexcavation should also encompass these areas.
Following completion of the overexcavation, the subgrade soils within the overexcavation areas
should be evaluated by the geotechnical engineer to verify their suitability to serve as the
structural fill subgrade, as well as to support the foundation loads of the new structure. This
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 18
evaluation should include proofrolling and probing to identify any soft, loose or otherwise unstable
soils that must be removed. Some localized areas of deeper excavation may be required
if additional fill materials or loose, porous, or low-density native soils are encountered
at the base of the overexcavation.
After a suitable overexcavation subgrade has been achieved, the exposed soils should be scarified
to a depth of at least 12 inches and moisture treated to 0 to 4 percent above optimum moisture
content. If native sands or gravelly sands are encountered at the bottom of the overexcavation,
these soils should be thoroughly flooded to raise the moisture content of the underlying soils to
at least 0 to 4 percent above optimum moisture content, extending to a depth of at least 24
inches. The subgrade soils should then be recompacted to at least 90 percent of the ASTM D-
1557 maximum dry density. The previously excavated soils may then be replaced as compacted
structural fill.
Treatment of Existing Soils: Retaining Walls and Site Walls
The existing soils within the areas of any proposed retaining walls and site walls should be
overexcavated to a depth of 3 feet below foundation bearing grade and replaced as compacted
structural fill as discussed above for the proposed building pad. Any undocumented fill soils or
disturbed native alluvium within any of these foundation areas should be removed in their
entirety. The overexcavation areas should extend at least 5 feet beyond the foundation
perimeters, and to an extent equal to the depth of fill below the new foundations. Any erection
pads for tilt-up concrete walls are considered to be part of the foundation system. Therefore,
these overexcavation recommendations are applicable to erection pads. The overexcavation
subgrade soils should be evaluated by the geotechnical engineer prior to scarifying, moisture
conditioning to within 0 to 4 percent above the optimum moisture content, and recompacting the
upper 12 inches of exposed subgrade soils. The previously excavated soils may then be replaced
as compacted structural fill.
If the full lateral recommended remedial grading cannot be completed for the proposed retaining
walls and site walls located along property lines, the foundations for those walls should be
designed using a reduced allowable bearing pressure. Furthermore, the contractor should take
necessary precautions to protect the adjacent improvements during rough grading. Specialized
grading techniques, such as A-B-C slot cuts, will likely be required during remedial grading. The
geotechnical engineer of record should be contacted if additional recommendations, such as
shoring design recommendations, are required during grading.
Treatment of Existing Soils: Flatwork, Parking and Drive Areas
Based on economic considerations, overexcavation of the existing near-surface existing soils in
the new flatwork, parking and drive areas is not considered warranted, with the exception of
areas where lower strength or unstable soils are identified by the geotechnical engineer during
grading. Subgrade preparation in the new flatwork, parking and drive areas should initially consist
of removal of all soils disturbed during stripping and demolition operations.
The geotechnical engineer should then evaluate the subgrade to identify any areas of additional
unsuitable soils. Any such materials should be removed to a level of firm and unyielding soil. The
exposed subgrade soils should then be scarified to a depth of 12± inches, moisture conditioned
to 0 to 4 percent above the optimum moisture content, and recompacted to at least 90 percent
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 19
of the ASTM D-1557 maximum dry density. Based on the presence of variable strength surficial
soils throughout the site, it is expected that some isolated areas of additional overexcavation may
be required to remove zones of lower strength, unsuitable soils.
The grading recommendations presented above for the proposed flatwork, parking and drive
areas assume that the owner and/or developer can tolerate minor amounts of settlement within
these areas. The grading recommendations presented above do not mitigate the extent of
undocumented fill or compressible/collapsible native alluvium in the flatwork, parking and drive
areas. As such, some settlement and associated pavement distress could occur. Typically, repair
of such distressed areas involves significantly lower costs than completely mitigating these soils
at the time of construction. If the owner cannot tolerate the risk of such settlements, the flatwork,
parking and drive areas should be overexcavated to a depth of 2 feet below proposed pavement
subgrade elevation, with the resulting soils replaced as compacted structural fill.
Fill Placement
• Fill soils should be placed in thin (6± inches), near-horizontal lifts, moisture conditioned
to 0 to 4 percent above the optimum moisture content, and compacted.
• On-site soils may be used for fill provided they are cleaned of any debris to the satisfaction
of the geotechnical engineer.
• All grading and fill placement activities should be completed in accordance with the
requirements of the 2019 CBC and the grading code of the city of Fontana.
• All fill soils should be compacted to at least 90 percent of the ASTM D-1557 maximum dry
density. Fill soils should be well mixed.
• Compaction tests should be performed periodically by the geotechnical engineer as
random verification of compaction and moisture content. These tests are intended to aid
the contractor. Since the tests are taken at discrete locations and depths, they may not
be indicative of the entire fill and therefore should not relieve the contractor of his
responsibility to meet the job specifications.
Selective Grading and Oversized Material Placement
Occasional to extensive cobbles were encountered at most of the boring locations as shallow as
of 7± feet from the ground surface. It is expected that large scrapers (Caterpillar 657 or
equivalent) will be adequate to move the cobble-containing soils.
Since the proposed grading will require excavation of cobble and possibly boulder containing soils,
it may be desirable to selectively grade the proposed building pad area. The presence of particles
greater than 6 inches in diameter within the upper 1 to 3 feet of the building pad subgrade will
impact the utility and foundation excavations. Depending on the depths of fills required within
the proposed parking areas, it may be feasible to sort the on-site soils, placing the materials
greater than 6 inches in diameter within the lower depths of the fills, and limiting the upper 1 to
3 feet of soils to materials less than 6 inches in size. Oversized materials could also be placed
within the lower depths of the recommended overexcavations. In order to achieve this grading,
it would likely be necessary to use rock buckets and/or rock sieves to separate the oversized
materials from the remaining soil. Although such selective grading will facilitate further
construction activities, it is not considered mandatory and a suitable subgrade could be achieved
without such extensive sorting. However, in any case, it is recommended that all materials greater
than 6 inches in size be excluded from the upper 1 foot of the surface of any compacted fills.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 20
The placement of any oversized materials should be performed in accordance with
the Grading Guide Specifications included in Appendix D of this report. If disposal of
oversized materials is required, rock blankets or windrows should be used and such areas should
be observed during construction and placement by a representative of the geotechnical engineer.
Imported Structural Fill
All imported structural fill should consist of very low expansive (EI < 20), well graded soils
possessing at least 10 percent fines (that portion of the sample passing the No. 200 sieve).
Additional specifications for structural fill are presented in the Grading Guide Specifications,
included as Appendix D.
Utility Trench Backfill
In general, all utility trench backfill should be compacted to at least 90 percent of the ASTM D-
1557 maximum dry density. As an alternative, a clean sand (minimum Sand Equivalent of 30)
may be placed within trenches and compacted in place (jetting or flooding is not recommended).
Compacted trench backfill should conform to the requirements of the local grading code, and
more restrictive requirements may be indicated by the city of Fontana. All utility trench backfills
should be witnessed by the geotechnical engineer. The trench backfill soils should be compaction
tested where possible; probed and visually evaluated elsewhere.
Utility trenches which parallel a footing, and extending below a 1h:1v (horizontal to vertical) plane
projected from the outside edge of the footing should be backfilled with structural fill soils,
compacted to at least 90 percent of the ASTM D-1557 standard. Pea gravel backfill should not be
used for these trenches.
Any soils used to backfill voids around subsurface utility structures, such as manholes or vaults,
should be placed as compacted structural fill. If it is not practical to place compacted fill in these
areas, then such void spaces may be backfilled with lean concrete slurry. Uncompacted pea gravel
or sand is not recommended for backfilling these voids since these materials have a potential to
settle and thereby cause distress of pavements placed around these subterranean structures.
6.4 Construction Considerations
Excavation Considerations
The near-surface soils generally consist of loose to medium dense sands, silty sands and sandy
silts. These materials will likely be subject to moderate caving within shallow excavations. Where
caving does occur, flattened excavation slopes may be sufficient to provide excavation stability.
On a preliminary basis, the inclination of temporary slopes should not exceed 2h:1v. Deeper
excavations may require some form of external stabilization such as shoring or bracing.
Maintaining adequate moisture content within the near-surface soils will improve excavation
stability. All excavation activities on this site should be conducted in accordance with Cal-OSHA
regulations.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 21
Moisture Sensitive Subgrade Soils
Some of the near-surface soils possess appreciable silt content. These soils may become unstable
if exposed to significant moisture infiltration or disturbance by construction traffic. In addition,
based on their granular content, some of the on-site soils will also be susceptible to erosion. The
site should, therefore, be graded to prevent ponding of surface water and to prevent water from
running into excavations.
Groundwater
The static groundwater table is considered to have existed at a depth in excess of 25± feet at
the time of the subsurface exploration. Therefore, groundwater is not expected to impact the
grading or foundation construction activities.
6.5 Foundation Design and Construction
Based on the preceding grading recommendations, it is assumed that the new building pad will
be underlain by structural fill soils used to replace existing undocumented fill soils and a portion
of the near-surface alluvial soils. These new structural fill soils are expected to extend to a depth
of at least 3 feet below proposed foundation bearing grade, underlain by 1± foot of additional
soil that has been densified and moisture conditioned in place. Based on this subsurface profile,
the proposed structure may be supported on conventional shallow foundations.
Foundation Design Parameters
New square and rectangular footings may be designed as follows:
• Maximum, net allowable soil bearing pressure: 3,000 lbs/ft2.
• Minimum wall/column footing width: 14 inches/24 inches.
• Minimum longitudinal steel reinforcement within strip footings: Two (2) No. 5 rebars (1
top and 1 bottom).
• Minimum foundation embedment: 12 inches into suitable structural fill soils, and at least
18 inches below adjacent exterior grade. Interior column footings may be placed
immediately beneath the floor slab.
• It is recommended that the perimeter building foundations be continuous across all
exterior doorways. Any flatwork adjacent to the exterior doors should be doweled into the
perimeter foundations in a manner determined by the structural engineer.
The allowable bearing pressures presented above may be increased by 1/3 when considering
short duration wind or seismic loads. The minimum steel reinforcement recommended above is
based on geotechnical considerations; additional reinforcement may be necessary for structural
considerations. The actual design of the foundations should be determined by the structural
engineer.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 22
Foundation Construction
The foundation subgrade soils should be evaluated at the time of overexcavation, as discussed
in Section 6.3 of this report. It is further recommended that the foundation subgrade soils be
evaluated by the geotechnical engineer immediately prior to steel or concrete placement. Soils
suitable for direct foundation support should consist of newly placed structural fill, compacted to
at least 90 percent of the ASTM D-1557 maximum dry density. Any unsuitable materials should
be removed to a depth of suitable bearing compacted structural fill or suitable native alluvium
(where reduced bearing pressures are utilized), with the resulting excavations backfilled with
compacted fill soils. As an alternative, lean concrete slurry (500 to 1,500 psi) may be used to
backfill such isolated overexcavations.
The foundation subgrade soils should also be properly moisture conditioned to 0 to 4 percent
above the Modified Proctor optimum, to a depth of at least 12 inches below bearing grade. Since
it is typically not feasible to increase the moisture content of the floor slab and foundation
subgrade soils once rough grading has been completed, care should be taken to maintain the
moisture content of the building pad subgrade soils throughout the construction process.
Estimated Foundation Settlements
Post-construction total and differential settlements of shallow foundations designed and
constructed in accordance with the previously presented recommendations are estimated to be
less than 1.0 and 0.5 inches, respectively. Differential movements are expected to occur over a
30-foot span, thereby resulting in an angular distortion of less than 0.002 inches per inch.
Lateral Load Resistance
Lateral load resistance will be developed by a combination of friction acting at the base of
foundations and slabs and the passive earth pressure developed by footings below grade. The
following friction and passive pressure may be used to resist lateral forces:
• Passive Earth Pressure: 300 lbs/ft3
• Friction Coefficient: 0.30
These are allowable values, and include a factor of safety. When combining friction and passive
resistance, the passive pressure component should be reduced by one-third. These values assume
that footings will be poured directly against compacted structural fill soils. The maximum allowable
passive pressure is 3,000 lbs/ft2.
6.6 Floor Slab Design and Construction
Subgrades which will support the new floor slab should be prepared in accordance with the
recommendations contained in the Site Grading Recommendations section of this report.
Based on the anticipated grading which will occur at this site, the floor of the proposed structure
may be constructed as conventional slabs-on-grade supported on newly placed structural fill (or
densified existing soils), extending to a depth of at least 5 feet below finished pad grades. Based
on geotechnical considerations, the floor slab may be designed as follows:
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 23
• Minimum slab thickness: 6 inches.
• Modulus of Subgrade Reaction: k = 150 psi/in.
• Minimum slab reinforcement: Reinforcement is not considered necessary from a
geotechnical standpoint. The actual floor slab reinforcement should be determined by the
structural engineer, based on the imposed slab loading.
• Slab underlayment: If moisture sensitive floor coverings will be used then minimum slab
underlayment should consist of a moisture vapor barrier constructed below the entire area
of the proposed slab where such moisture sensitive floor coverings are anticipated. The
moisture vapor barrier should meet or exceed the Class A rating as defined by ASTM E
1745-97 and have a permeance rating less than 0.01 perms as described in ASTM E 96-
95 and ASTM E 154-88. A polyolefin material such as Stego® Wrap Vapor Barrier or
equivalent will meet these specifications. The moisture vapor barrier should be properly
constructed in accordance with all applicable manufacturer specifications. Given that a
rock free subgrade is anticipated and that a capillary break is not required, sand below
the barrier is not required. The need for sand and/or the amount of sand above the
moisture vapor barrier should be specified by the structural engineer or concrete
contractor. The selection of sand above the barrier is not a geotechnical engineering issue
and hence outside our purview. Where moisture sensitive floor coverings are not
anticipated, the vapor barrier may be eliminated.
• Moisture condition the floor slab subgrade soils to 0 to 4 percent above the Modified
Proctor optimum moisture content, to a depth of 12 inches. The moisture content of the
floor slab subgrade soils should be verified by the geotechnical engineer within 24 hours
prior to concrete placement.
• Proper concrete curing techniques should be utilized to reduce the potential for slab
curling or the formation of excessive shrinkage cracks.
The actual design of the floor slabs should be completed by the structural engineer to verify
adequate thickness and reinforcement.
6.7 Retaining Wall Design and Construction
Although not indicated on the site plans, some small (less than 6 feet in height) retaining walls
may be required to facilitate the new site grades. The parameters recommended for use in the
design of these walls are presented below.
Retaining Wall Design Parameters
Based on the soil conditions encountered at the boring locations, the following parameters may
be used in the design of new retaining walls for this site. We have provided parameters assuming
the use of on-site soils for retaining wall backfill. The on-site soils generally consist of silty sands,
sands, gravelly sands and sandy silts. Based on their composition, the on-site silty sands and
sandy silts are expected to possess a friction angle of 30 degrees when compacted to at least 90
percent of the ASTM D-1557 maximum dry density.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 24
If desired, SCG could provide design parameters for an alternative select backfill material behind
the retaining walls. The use of select backfill material could result in lower lateral earth pressures.
In order to use the design parameters for the imported select fill, this material must be placed
within the entire active failure wedge. This wedge is defined as extending from the heel of the
retaining wall upwards at an angle of approximately 60° from horizontal. If select backfill material
behind the retaining wall is desired, SCG should be contacted for supplementary
recommendations.
RETAINING WALL DESIGN PARAMETERS
Design Parameter
Soil Type
On-site Silty Sands and Sandy Silts
Internal Friction Angle () 30
Unit Weight 128 lbs/ft3
Equivalent
Fluid Pressure:
Active Condition
(level backfill) 43 lbs/ft3
Active Condition
(2h:1v backfill) 69 lbs/ft3
At-Rest Condition
(level backfill) 64 lbs/ft3
The walls should be designed using a soil-footing coefficient of friction of 0.30 and an equivalent
passive pressure of 300 lbs/ft3. The structural engineer should incorporate appropriate factors of
safety in the design of the retaining walls.
The active earth pressure may be used for the design of retaining walls that do not directly
support structures or support soils that in turn support structures and which will be allowed to
deflect. The at-rest earth pressure should be used for walls that will not be allowed to deflect
such as those which will support foundation bearing soils, or which will support foundation loads
directly.
Where the soils on the toe side of the retaining wall are not covered by a "hard" surface such as
a structure or pavement, the upper 1 foot of soil should be neglected when calculating passive
resistance due to the potential for the material to become disturbed or degraded during the life
of the structure.
Seismic Lateral Earth Pressures
In accordance with the 2019 CBC, any retaining walls more than 6 feet in height must be designed
for seismic lateral earth pressures. If walls 6 feet or more are required for this site, the
geotechnical engineer should be contacted for supplementary seismic lateral earth pressure
recommendations.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 25
Retaining Wall Foundation Design
The retaining wall foundations should be underlain by at least 3 feet of newly placed structural
fill. Foundations to support new retaining walls should be designed in accordance with the general
Foundation Design Parameters presented in a previous section of this report.
Backfill Material
On-site soils may be used to backfill the retaining walls. However, all backfill material placed
within 3 feet of the back wall face should have a particle size no greater than 3 inches. The
retaining wall backfill materials should be well graded.
It is recommended that a minimum 1-foot thick layer of free-draining granular material (less than
5 percent passing the No. 200 sieve) be placed against the face of the retaining walls. This
material should extend from the top of the retaining wall footing to within 1 foot of the ground
surface on the back side of the retaining wall. This material should be approved by the
geotechnical engineer. In lieu of the 1-foot thick layer of free-draining material, a properly
installed prefabricated drainage composite such as the MiraDRAIN 6000XL (or approved
equivalent), which is specifically designed for use behind retaining walls, may be used. If the
layer of free-draining material is not covered by an impermeable surface, such as a structure or
pavement, a 12-inch thick layer of a low permeability soil should be placed over the backfill to
reduce surface water migration to the underlying soils. The layer of free draining granular material
should be separated from the backfill soils by a suitable geotextile, approved by the geotechnical
engineer.
All retaining wall backfill should be placed and compacted under engineering controlled conditions
in the necessary layer thicknesses to ensure an in-place density between 90 and 93 percent of
the maximum dry density as determined by the Modified Proctor test (ASTM D1557-91). Care
should be taken to avoid over-compaction of the soils behind the retaining walls, and the use of
heavy compaction equipment should be avoided.
Subsurface Drainage
As previously indicated, the retaining wall design parameters are based upon drained backfill
conditions. Consequently, some form of permanent drainage system will be necessary in
conjunction with the appropriate backfill material. Subsurface drainage may consist of either:
• A weep hole drainage system typically consisting of a series of 2-inch diameter holes in
the wall situated slightly above the ground surface elevation on the exposed side of the
wall and at an approximate 10-foot on-center spacing. Alternatively, 4-inch diameter holes
at an approximate 20-foot on-center spacing can be used for this type of drainage system.
In addition, the weep holes should include a 2 cubic foot pocket of open graded gravel,
surrounded by an approved geotextile fabric, at each weep hole location.
• A 4-inch diameter perforated pipe surrounded by 2 cubic feet of gravel per linear foot of
drain placed behind the wall, above the retaining wall footing. The gravel layer should be
wrapped in a suitable geotextile fabric to reduce the potential for migration of fines. The
footing drain should be extended to daylight or tied into a storm drainage system. The
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 26
actual design of this type of system should be determined by the civil engineer to verify
that the drainage system possesses the adequate capacity and slope for its intended use.
Weep holes or a footing drain will not be required for building stem walls.
6.8 Pavement Design Parameters
Site preparation in the pavement area should be completed as previously recommended in the
Site Grading Recommendations section of this report. The subsequent pavement
recommendations assume proper drainage and construction monitoring, and are based on either
PCA or CALTRANS design parameters for a twenty (20) year design period. However, these
designs also assume a routine pavement maintenance program to obtain the anticipated 20-year
pavement service life.
Pavement Subgrades
It is anticipated that the new pavements will be primarily supported on a layer of compacted
structural fill, consisting of scarified, thoroughly moisture conditioned and recompacted existing
soils. The near-surface soils generally consist of sands, silty sands and gravelly sands. These soils
are generally considered to possess excellent pavement support characteristics, with R-values in
the range of 50 to 60. The subsequent pavement design is therefore based upon an assumed R-
value of 50. Any fill material imported to the site should have support characteristics equal to or
greater than that of the on-site soils and be placed and compacted under engineering controlled
conditions. It is recommended that R-value testing be performed after completion of rough
grading to verify that the pavement design recommendations presented herein are valid.
Asphaltic Concrete
Presented below are the recommended thicknesses for new flexible pavement structures
consisting of asphaltic concrete over a granular base. The pavement designs are based on the
traffic indices (TI’s) indicated. The client and/or civil engineer should verify that these TI’s are
representative of the anticipated traffic volumes. If the client and/or civil engineer determine that
the expected traffic volume will exceed the applicable traffic index, we should be contacted for
supplementary recommendations. The design traffic indices equate to the following approximate
daily traffic volumes over a 20-year design life, assuming six operational traffic days per week.
Traffic Index No. of Heavy Trucks per Day
4.0 0
5.0 1
6.0 3
7.0 11
8.0 35
9.0 93
For the purpose of the traffic volumes indicated above, a truck is defined as a 5-axle tractor trailer
unit with one 8-kip axle and two 32-kip tandem axles. All of the traffic indices allow for 1,000
automobiles per day.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 27
ASPHALT PAVEMENTS (R=50)
Materials
Thickness (inches)
Auto Parking and
Auto Drive Lanes
(TI = 4.0 to 5.0)
Truck Traffic
TI = 6.0 TI = 7.0 TI = 8.0 TI = 9.0
Asphalt Concrete 3 3½ 4 5 5½
Aggregate Base 3 4 5 5 7
Compacted Subgrade 12 12 12 12 12
The aggregate base course should be compacted to at least 95 percent of the ASTM D-1557
maximum dry density. The asphaltic concrete should be compacted to at least 95 percent of the
batch plant-reported maximum density. The aggregate base course may consist of crushed
aggregate base (CAB) or crushed miscellaneous base (CMB), which is a recycled gravel, asphalt
and concrete material. The gradation, R-Value, Sand Equivalent, and Percentage Wear of the CAB
or CMB should comply with appropriate specifications contained in the current edition of the
“Greenbook” Standard Specifications for Public Works Construction.
Portland Cement Concrete
The preparation of the subgrade soils within concrete pavement areas should be performed as
previously described for proposed asphalt pavement areas. The minimum recommended
thicknesses for the Portland Cement Concrete pavement sections are as follows:
PORTLAND CEMENT CONCRETE PAVEMENTS (R=50)
Materials
Thickness (inches)
Autos and Light
Truck Traffic
(TI = 6.0)
Truck Traffic
TI = 7.0 TI = 8.0 TI = 9.0
PCC 5 5½ 6½ 8
Compacted Subgrade
(95% minimum compaction) 12 12 12 12
The concrete should have a 28-day compressive strength of at least 3,000 psi. Any reinforcement
within the PCC pavements should be determined by the project structural engineer. The maximum
joint spacing within all of the PCC pavements is recommended to be equal to or less than 30
times the pavement thickness.
Proposed Warehouse – Fontana, CA
Project No. 20G226-3
Page 28
7.0 GENERAL COMMENTS
This report has been prepared as an instrument of service for use by the client, in order to aid in
the evaluation of this property and to assist the architects and engineers in the design and
preparation of the project plans and specifications. This report may be provided to the
contractor(s) and other design consultants to disclose information relative to the project.
However, this report is not intended to be utilized as a specification in and of itself, without
appropriate interpretation by the project architect, civil engineer, and/or structural engineer. The
reproduction and distribution of this report must be authorized by the client and Southern
California Geotechnical, Inc. Furthermore, any reliance on this report by an unauthorized third
party is at such party’s sole risk, and we accept no responsibility for damage or loss which may
occur. The client(s)’ reliance upon this report is subject to the Engineering Services Agreement,
incorporated into our proposal for this project.
The analysis of this site was based on a subsurface profile interpolated from limited discrete soil
samples. While the materials encountered in the project area are considered to be representative
of the total area, some variations should be expected between boring locations and sample
depths. If the conditions encountered during construction vary significantly from those detailed
herein, we should be contacted immediately to determine if the conditions alter the
recommendations contained herein.
This report has been based on assumed or provided characteristics of the proposed development.
It is recommended that the owner, client, architect, structural engineer, and civil engineer
carefully review these assumptions to ensure that they are consistent with the characteristics of
the proposed development. If discrepancies exist, they should be brought to our attention to
verify that they do not affect the conclusions and recommendations contained herein. We also
recommend that the project plans and specifications be submitted to our office for review to
verify that our recommendations have been correctly interpreted.
The analysis, conclusions, and recommendations contained within this report have been
promulgated in accordance with generally accepted professional geotechnical engineering
practice. No other warranty is implied or expressed.
SITE
PROPOSED WAREHOUSE
SCALE: 1" = 2000'
DRAWN: RBCHKD: RGT
SCG PROJECT
20G226-3
PLATE 1
SITE LOCATION MAP
FONTANA, CALIFORNIA
SOURCE: USGS TOPOGRAPHIC MAP OF THEFONTANA QUADRANGLE, SAN BERNARDINO
COUNTY, CALIFORNIA, 2018
B-8B-12B-9B-10B-11B-13B-14B-15B-16B-17B-18B-3B-1B-2B-6B-4B-5B-7SCALE: 1" = 150'DRAWN: RBCHKD: RGTPLATE 2SCG PROJECT20G226-3FONTANA, CALIFORNIAPROPOSED WAREHOUSEBORING LOCATION PLANNORTH
SoCalGeoNOTE: CONCEPTUAL SITE PLAN (SCHEME 7) PREPARED BY HPA, INC.AERIAL PHOTOGRAPH OBTAINED FROM GOOGLE EARTH.GEOTECHNICAL LEGENDAPPROXIMATE BORING LOCATIONPREVIOUS BORING LOCATION(SCG PROJECT NO: 20G226-1) PREVIOUS BORING LOCATION(SCG PROJECT NO: 18G213-1) PROPERTY BOUNDARY
BORING LOG LEGEND
SAMPLE TYPE GRAPHICAL
SYMBOL SAMPLE DESCRIPTION
AUGER SAMPLE COLLECTED FROM AUGER CUTTINGS, NO FIELD
MEASUREMENT OF SOIL STRENGTH. (DISTURBED)
CORE ROCK CORE SAMPLE: TYPICALLY TAKEN WITH A DIAMOND-TIPPED CORE BARREL. TYPICALLY USED ONLY IN HIGHLY CONSOLIDATED BEDROCK.
GRAB 1
SOIL SAMPLE TAKEN WITH NO SPECIALIZED
EQUIPMENT, SUCH AS FROM A STOCKPILE OR THE GROUND SURFACE. (DISTURBED)
CS CALIFORNIA SAMPLER: 2-1/2 INCH I.D. SPLIT BARREL SAMPLER, LINED WITH 1-INCH HIGH BRASS RINGS.
DRIVEN WITH SPT HAMMER. (RELATIVELY UNDISTURBED)
NSR
NO RECOVERY: THE SAMPLING ATTEMPT DID NOT RESULT IN RECOVERY OF ANY SIGNIFICANT SOIL OR
ROCK MATERIAL.
SPT STANDARD PENETRATION TEST: SAMPLER IS A 1.4 INCH INSIDE DIAMETER SPLIT BARREL, DRIVEN 18 INCHES WITH THE SPT HAMMER. (DISTURBED)
SH SHELBY TUBE: TAKEN WITH A THIN WALL SAMPLE
TUBE, PUSHED INTO THE SOIL AND THEN EXTRACTED. (UNDISTURBED)
VANE VANE SHEAR TEST: SOIL STRENGTH OBTAINED USING A 4 BLADED SHEAR DEVICE. TYPICALLY USED IN SOFT CLAYS-NO SAMPLE RECOVERED.
COLUMN DESCRIPTIONS
DEPTH: Distance in feet below the ground surface.
SAMPLE: Sample Type as depicted above.
BLOW COUNT: Number of blows required to advance the sampler 12 inches using a 140 lb
hammer with a 30-inch drop. 50/3” indicates penetration refusal (>50 blows)
at 3 inches. WH indicates that the weight of the hammer was sufficient to
push the sampler 6 inches or more.
POCKET PEN.: Approximate shear strength of a cohesive soil sample as measured by pocket
penetrometer.
GRAPHIC LOG: Graphic Soil Symbol as depicted on the following page.
DRY DENSITY: Dry density of an undisturbed or relatively undisturbed sample in lbs/ft3.
MOISTURE CONTENT: Moisture content of a soil sample, expressed as a percentage of the dry weight.
LIQUID LIMIT: The moisture content above which a soil behaves as a liquid.
PLASTIC LIMIT: The moisture content above which a soil behaves as a plastic.
PASSING #200 SIEVE: The percentage of the sample finer than the #200 standard sieve.
UNCONFINED SHEAR: The shear strength of a cohesive soil sample, as measured in the unconfined state.
SM
SP
COARSE
GRAINEDSOILS
SW
TYPICAL
DESCRIPTIONS
WELL-GRADED GRAVELS, GRAVEL -
SAND MIXTURES, LITTLE OR NOFINES
SILTY GRAVELS, GRAVEL - SAND -
SILT MIXTURES
LETTERGRAPH
POORLY-GRADED GRAVELS,
GRAVEL - SAND MIXTURES, LITTLEOR NO FINES
GC
GM
GP
GW
POORLY-GRADED SANDS,
GRAVELLY SAND, LITTLE OR NOFINES
SILTSAND
CLAYS
MORE THAN 50%
OF MATERIAL ISLARGER THANNO. 200 SIEVE
SIZE
MORE THAN 50%OF MATERIAL IS
SMALLER THANNO. 200 SIEVESIZE
MORE THAN 50%OF COARSEFRACTION
PASSING ON NO.4 SIEVE
MORE THAN 50%OF COARSE
FRACTIONRETAINED ON NO.4 SIEVE CLAYEY GRAVELS, GRAVEL - SAND -
CLAY MIXTURES
FINEGRAINED
SOILS
SYMBOLSMAJOR DIVISIONS
SOIL CLASSIFICATION CHART
PT
OH
CH
MH
OL
CL
ML
CLEAN SANDS
SC
SILTY SANDS, SAND - SILTMIXTURES
CLAYEY SANDS, SAND - CLAY
MIXTURES
INORGANIC SILTS AND VERY FINESANDS, ROCK FLOUR, SILTY OR
CLAYEY FINE SANDS OR CLAYEYSILTS WITH SLIGHT PLASTICITY
INORGANIC CLAYS OF LOW TO
MEDIUM PLASTICITY, GRAVELLYCLAYS, SANDY CLAYS, SILTY CLAYS,LEAN CLAYS
ORGANIC SILTS AND ORGANICSILTY CLAYS OF LOW PLASTICITY
INORGANIC SILTS, MICACEOUS OR
DIATOMACEOUS FINE SAND ORSILTY SOILS
INORGANIC CLAYS OF HIGH
PLASTICITY
ORGANIC CLAYS OF MEDIUM TO
HIGH PLASTICITY, ORGANIC SILTS
PEAT, HUMUS, SWAMP SOILS WITHHIGH ORGANIC CONTENTS
SILTS
AND
CLAYS
GRAVELS WITH
FINES
SAND
AND
SANDY
SOILS (LITTLE OR NO FINES)
SANDS WITH
FINES
LIQUID LIMITLESS THAN 50
LIQUID LIMIT
GREATER THAN 50
HIGHLY ORGANIC SOILS
NOTE: DUAL SYMBOLS ARE USED TO INDICATE BORDERLINE SOIL CLASSIFICATIONS
GRAVEL
AND
GRAVELLYSOILS
(APPRECIABLE
AMOUNT OF FINES)
(APPRECIABLE
AMOUNT OF FINES)
(LITTLE OR NO FINES)
WELL-GRADED SANDS, GRAVELLYSANDS, LITTLE OR NO FINES
CLEAN
GRAVELS
115
111
115
119
118
5
3
2
2
2
1
2
4
FILL: Gray Brown Silty fine to coarse Sand, trace to little fineGravel, medium dense-damp
FILL: Brown Silty fine Sand, trace medium to coarse Sand, tracefine to coarse Gravel, medium dense-damp
ALLUVIUM: Brown to Gray Brown Gravelly fine to coarse Sand,
little Silt, medium dense-damp
@ 7 feet, extensive cobbles
Gray fine to coarse Sand, trace to little fine to coarse Gravel, traceSilt, dense to very dense-dry to damp
@ 13½ feet, occasional Cobbles
Boring Terminated at 25'
16
19
24
44
50
76/10"
79/9"
37 LIQUIDLIMITPLASTICLIMITSAMPLEFIELD RESULTS
GRAPHIC LOGPOCKET PEN.(TSF)ORGANICCONTENT (%)WATER DEPTH: Dry
CAVE DEPTH: 7 feet
READING TAKEN: At Completion
LABORATORY RESULTS
COMMENTSBORING NO.
B-14
DRILLING DATE: 7/21/21
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
PASSING#200 SIEVE (%)BLOW COUNTDRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)JOB NO.: 20G226-3
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
PLATE B-14
5
10
15
20
25
DESCRIPTION
TEST BORING LOG
SURFACE ELEVATION: --- MSL
TBL 20G226-3.GPJ SOCALGEO.GDT 8/10/21
112
105
119
125
2
2
3
3
7
3
2
FILL: Light Gray Brown Silty fine Sand, trace to little medium tocoarse Sand, little fine Gravel, trace Plastic Fragments, mediumdense-dry
FILL: Light Gray Brown Silty fine Sand, trace medium Sand,loose-dry
FILL: Brown Silty fine to coarse Sand, trace to little fine to coarse
Gravel, mottled, medium dense-damp
ALLUVIUM: Gray Gravelly fine to coarse Sand, little Silt,occasional to extensive Cobbles, medium dense to very
dense-damp
Brown Silty fine Sand, trace medium to coarse Sand, mediumdense-damp to moist
Brown fine to coarse Sand, little fine to coarse Gravel, trace Silt,
dense-damp
Gray Brown Gravelly fine to coarse Sand, trace Silt, very
dense-damp
Boring Terminated at 25'
No SampleRecovery
19
14
38
41
50/5"
22
44
50/5"LIQUIDLIMITPLASTICLIMITSAMPLEFIELD RESULTS
GRAPHIC LOGPOCKET PEN.(TSF)ORGANICCONTENT (%)WATER DEPTH: Dry
CAVE DEPTH: 10 feet
READING TAKEN: At Completion
LABORATORY RESULTS
COMMENTSBORING NO.
B-15
DRILLING DATE: 7/21/21
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
PASSING#200 SIEVE (%)BLOW COUNTDRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)JOB NO.: 20G226-3
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
PLATE B-15
5
10
15
20
25
DESCRIPTION
TEST BORING LOG
SURFACE ELEVATION: --- MSL
TBL 20G226-3.GPJ SOCALGEO.GDT 8/10/21
109
103
106
113
115
110
111
4
4
5
8
2
9
3
2
FILL: Brown Silty fine to medium Sand, trace coarse Sand,medium dense-damp
@ 3 feet, loose
ALLUVIUM: Light Brown fine Sandy Silt, loose to medium
dense-damp
Gray SIlty fine to medium Sand, little coarse Sand, mediumdense-dry
Brown Silty fine Sand, trace medium to coarse Sand, mediumdense-moist
Dark Brown fine to coarse Sand, trace Silt, medium dense-damp
Gray Brown fine to coarse Sand, trace to little Silt, mediumdense-damp
@ 23½ feet, dense
Boring Terminated at 25'
17
7
9
19
20
16
34
47 LIQUIDLIMITPLASTICLIMITSAMPLEFIELD RESULTS
GRAPHIC LOGPOCKET PEN.(TSF)ORGANICCONTENT (%)WATER DEPTH: Dry
CAVE DEPTH: 21 feet
READING TAKEN: At Completion
LABORATORY RESULTS
COMMENTSBORING NO.
B-16
DRILLING DATE: 7/21/21
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
PASSING#200 SIEVE (%)BLOW COUNTDRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)JOB NO.: 20G226-3
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
PLATE B-16
5
10
15
20
25
DESCRIPTION
TEST BORING LOG
SURFACE ELEVATION: --- MSL
TBL 20G226-3.GPJ SOCALGEO.GDT 8/10/21
1
1
1
1
FILL: Light Brown Silty fine to coarse Sand, little to some fine tocoarse Gravel, medium dense-dry
ALLUVIUM: Light Brown Silty fine to coarse Sand, little fine to
coarse Gravel, dense to very dense-dry
@ 8½ feet, occasional Cobbles
Boring Terminated at 10'
25
62/9"
43
33 LIQUIDLIMITPLASTICLIMITSAMPLEFIELD RESULTS
GRAPHIC LOGPOCKET PEN.(TSF)ORGANICCONTENT (%)WATER DEPTH: Dry
CAVE DEPTH: 8 inches
READING TAKEN: At Completion
LABORATORY RESULTS
COMMENTSBORING NO.
B-17
DRILLING DATE: 7/21/21
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
PASSING#200 SIEVE (%)BLOW COUNTDRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)JOB NO.: 20G226-3
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
PLATE B-17
5
10
DESCRIPTION
TEST BORING LOG
SURFACE ELEVATION: --- MSL
TBL 20G226-3.GPJ SOCALGEO.GDT 8/10/21
5
6
16
5
FILL: Brown Silty fine Sand, loose-damp
ALLUVIUM: Gray Brown fine Sandy Silt, medium dense-moist tovery moist
Brown Silty fine Sand, trace medium to coarse Sand, medium
dense-damp
Boring Terminated at 10'
7
8
10
16 LIQUIDLIMITPLASTICLIMITSAMPLEFIELD RESULTS
GRAPHIC LOGPOCKET PEN.(TSF)ORGANICCONTENT (%)WATER DEPTH: Dry
CAVE DEPTH: 19 feet
READING TAKEN: At Completion
LABORATORY RESULTS
COMMENTSBORING NO.
B-18
DRILLING DATE: 7/21/21
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
PASSING#200 SIEVE (%)BLOW COUNTDRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)JOB NO.: 20G226-3
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
PLATE B-18
5
10
DESCRIPTION
TEST BORING LOG
SURFACE ELEVATION: --- MSL
TBL 20G226-3.GPJ SOCALGEO.GDT 8/10/21
Classification: FILL: Brown Silty fine Sand, trace medium to coarse Sand, trace fine to coarse Gravel
Boring Number:B-14 Initial Moisture Content (%)3
Sample Number:---Final Moisture Content (%)15
Depth (ft)3 to 4 Initial Dry Density (pcf)110.7
Specimen Diameter (in)2.4 Final Dry Density (pcf)116.6
Specimen Thickness (in)1.0 Percent Collapse (%)0.94
Proposed Warehouse
Fontana, California
Project No. 20G226-3
PLATE C- 1
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification: Brown to Gray Brown Gravelly fine to coarse Sand, little Silt
Boring Number:B-14 Initial Moisture Content (%)2
Sample Number:---Final Moisture Content (%)15
Depth (ft)5 to 6 Initial Dry Density (pcf)114.7
Specimen Diameter (in)2.4 Final Dry Density (pcf)123.0
Specimen Thickness (in)1.0 Percent Collapse (%)1.23
Proposed Warehouse
Fontana, California
Project No. 20G226-3
PLATE C- 2
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification: Brown to Gray Brown Gravelly fine to coarse Sand, little Silt
Boring Number:B-14 Initial Moisture Content (%)2
Sample Number:---Final Moisture Content (%)14
Depth (ft)7 to 8 Initial Dry Density (pcf)119.1
Specimen Diameter (in)2.4 Final Dry Density (pcf)124.7
Specimen Thickness (in)1.0 Percent Collapse (%)0.62
Proposed Warehouse
Fontana, California
Project No. 20G226-3
PLATE C- 3
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Addedat 1600 psf
Classification: Gray fine to coarse Sand, trace to little fine to coarse Gravel, trace Silt
Boring Number:B-14 Initial Moisture Content (%)2
Sample Number:---Final Moisture Content (%)13
Depth (ft)9 to 10 Initial Dry Density (pcf)117.8
Specimen Diameter (in)2.4 Final Dry Density (pcf)122.6
Specimen Thickness (in)1.0 Percent Collapse (%)0.52
Proposed Warehouse
Fontana, California
Project No. 20G226-3
PLATE C- 4
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Grading Guide Specifications Page 1
GRADING GUIDE SPECIFICATIONS
These grading guide specifications are intended to provide typical procedures for grading operations.
They are intended to supplement the recommendations contained in the geotechnical investigation
report for this project. Should the recommendations in the geotechnical investigation report conflict
with the grading guide specifications, the more site specific recommendations in the geotechnical
investigation report will govern.
General
• The Earthwork Contractor is responsible for the satisfactory completion of all earthwork in
accordance with the plans and geotechnical reports, and in accordance with city, county,
and applicable building codes.
• The Geotechnical Engineer is the representative of the Owner/Builder for the purpose of
implementing the report recommendations and guidelines. These duties are not intended to
relieve the Earthwork Contractor of any responsibility to perform in a workman-like manner,
nor is the Geotechnical Engineer to direct the grading equipment or personnel employed by
the Contractor.
• The Earthwork Contractor is required to notify the Geotechnical Engineer of the anticipated
work and schedule so that testing and inspections can be provided. If necessary, work may
be stopped and redone if personnel have not been scheduled in advance.
• The Earthwork Contractor is required to have suitable and sufficient equipment on the job-
site to process, moisture condition, mix and compact the amount of fill being placed to the
approved compaction. In addition, suitable support equipment should be available to
conform with recommendations and guidelines in this report.
• Canyon cleanouts, overexcavation areas, processed ground to receive fill, key excavations,
subdrains and benches should be observed by the Geotechnical Engineer prior to placement
of any fill. It is the Earthwork Contractor's responsibility to notify the Geotechnical Engineer
of areas that are ready for inspection.
• Excavation, filling, and subgrade preparation should be performed in a manner and
sequence that will provide drainage at all times and proper control of erosion. Precipitation,
springs, and seepage water encountered shall be pumped or drained to provide a suitable
working surface. The Geotechnical Engineer must be informed of springs or water seepage
encountered during grading or foundation construction for possible revision to the
recommended construction procedures and/or installation of subdrains.
Site Preparation
• The Earthwork Contractor is responsible for all clearing, grubbing, stripping and site
preparation for the project in accordance with the recommendations of the Geotechnical
Engineer.
• If any materials or areas are encountered by the Earthwork Contractor which are suspected
of having toxic or environmentally sensitive contamination, the Geotechnical Engineer and
Owner/Builder should be notified immediately.
Grading Guide Specifications Page 2
• Major vegetation should be stripped and disposed of off-site. This includes trees, brush,
heavy grasses and any materials considered unsuitable by the Geotechnical Engineer.
• Underground structures such as basements, cesspools or septic disposal systems, mining
shafts, tunnels, wells and pipelines should be removed under the inspection of the
Geotechnical Engineer and recommendations provided by the Geotechnical Engineer and/or
city, county or state agencies. If such structures are known or found, the Geotechnical
Engineer should be notified as soon as possible so that recommendations can be
formulated.
• Any topsoil, slopewash, colluvium, alluvium and rock materials which are considered
unsuitable by the Geotechnical Engineer should be removed prior to fill placement.
• Remaining voids created during site clearing caused by removal of trees, foundations
basements, irrigation facilities, etc., should be excavated and filled with compacted fill.
• Subsequent to clearing and removals, areas to receive fill should be scarified to a depth of
10 to 12 inches, moisture conditioned and compacted
• The moisture condition of the processed ground should be at or slightly above the optimum
moisture content as determined by the Geotechnical Engineer. Depending upon field
conditions, this may require air drying or watering together with mixing and/or discing.
Compacted Fills
• Soil materials imported to or excavated on the property may be utilized in the fill, provided
each material has been determined to be suitable in the opinion of the Geotechnical
Engineer. Unless otherwise approved by the Geotechnical Engineer, all fill materials shall be
free of deleterious, organic, or frozen matter, shall contain no chemicals that may result in
the material being classified as “contaminated,” and shall be very low to non-expansive with
a maximum expansion index (EI) of 50. The top 12 inches of the compacted fill should
have a maximum particle size of 3 inches, and all underlying compacted fill material a
maximum 6-inch particle size, except as noted below.
• All soils should be evaluated and tested by the Geotechnical Engineer. Materials with high
expansion potential, low strength, poor gradation or containing organic materials may
require removal from the site or selective placement and/or mixing to the satisfaction of the
Geotechnical Engineer.
• Rock fragments or rocks less than 6 inches in their largest dimensions, or as otherwise
determined by the Geotechnical Engineer, may be used in compacted fill, provided the
distribution and placement is satisfactory in the opinion of the Geotechnical Engineer.
• Rock fragments or rocks greater than 12 inches should be taken off-site or placed in
accordance with recommendations and in areas designated as suitable by the Geotechnical
Engineer. These materials should be placed in accordance with Plate D-8 of these Grading
Guide Specifications and in accordance with the following recommendations:
• Rocks 12 inches or more in diameter should be placed in rows at least 15 feet apart, 15
feet from the edge of the fill, and 10 feet or more below subgrade. Spaces should be
left between each rock fragment to provide for placement and compaction of soil
around the fragments.
• Fill materials consisting of soil meeting the minimum moisture content requirements and
free of oversize material should be placed between and over the rows of rock or
Grading Guide Specifications Page 3
concrete. Ample water and compactive effort should be applied to the fill materials as
they are placed in order that all of the voids between each of the fragments are filled
and compacted to the specified density.
• Subsequent rows of rocks should be placed such that they are not directly above a row
placed in the previous lift of fill. A minimum 5-foot offset between rows is
recommended.
• To facilitate future trenching, oversized material should not be placed within the range
of foundation excavations, future utilities or other underground construction unless
specifically approved by the soil engineer and the developer/owner representative.
• Fill materials approved by the Geotechnical Engineer should be placed in areas previously
prepared to receive fill and in evenly placed, near horizontal layers at about 6 to 8 inches in
loose thickness, or as otherwise determined by the Geotechnical Engineer for the project.
• Each layer should be moisture conditioned to optimum moisture content, or slightly above,
as directed by the Geotechnical Engineer. After proper mixing and/or drying, to evenly
distribute the moisture, the layers should be compacted to at least 90 percent of the
maximum dry density in compliance with ASTM D-1557-78 unless otherwise indicated.
• Density and moisture content testing should be performed by the Geotechnical Engineer at
random intervals and locations as determined by the Geotechnical Engineer. These tests
are intended as an aid to the Earthwork Contractor, so he can evaluate his workmanship,
equipment effectiveness and site conditions. The Earthwork Contractor is responsible for
compaction as required by the Geotechnical Report(s) and governmental agencies.
• Fill areas unused for a period of time may require moisture conditioning, processing and
recompaction prior to the start of additional filling. The Earthwork Contractor should notify
the Geotechnical Engineer of his intent so that an evaluation can be made.
• Fill placed on ground sloping at a 5-to-1 inclination (horizontal-to-vertical) or steeper should
be benched into bedrock or other suitable materials, as directed by the Geotechnical
Engineer. Typical details of benching are illustrated on Plates D-2, D-4, and D-5.
• Cut/fill transition lots should have the cut portion overexcavated to a depth of at least 3 feet
and rebuilt with fill (see Plate D-1), as determined by the Geotechnical Engineer.
• All cut lots should be inspected by the Geotechnical Engineer for fracturing and other
bedrock conditions. If necessary, the pads should be overexcavated to a depth of 3 feet
and rebuilt with a uniform, more cohesive soil type to impede moisture penetration.
• Cut portions of pad areas above buttresses or stabilizations should be overexcavated to a
depth of 3 feet and rebuilt with uniform, more cohesive compacted fill to impede moisture
penetration.
• Non-structural fill adjacent to structural fill should typically be placed in unison to provide
lateral support. Backfill along walls must be placed and compacted with care to ensure that
excessive unbalanced lateral pressures do not develop. The type of fill material placed
adjacent to below grade walls must be properly tested and approved by the Geotechnical
Engineer with consideration of the lateral earth pressure used in the design.
Grading Guide Specifications Page 4
Foundations
• The foundation influence zone is defined as extending one foot horizontally from the outside
edge of a footing, and proceeding downward at a ½ horizontal to 1 vertical (0.5:1)
inclination.
• Where overexcavation beneath a footing subgrade is necessary, it should be conducted so
as to encompass the entire foundation influence zone, as described above.
• Compacted fill adjacent to exterior footings should extend at least 12 inches above
foundation bearing grade. Compacted fill within the interior of structures should extend to
the floor subgrade elevation.
Fill Slopes
• The placement and compaction of fill described above applies to all fill slopes. Slope
compaction should be accomplished by overfilling the slope, adequately compacting the fill
in even layers, including the overfilled zone and cutting the slope back to expose the
compacted core
• Slope compaction may also be achieved by backrolling the slope adequately every 2 to 4
vertical feet during the filling process as well as requiring the earth moving and compaction
equipment to work close to the top of the slope. Upon completion of slope construction,
the slope face should be compacted with a sheepsfoot connected to a sideboom and then
grid rolled. This method of slope compaction should only be used if approved by the
Geotechnical Engineer.
• Sandy soils lacking in adequate cohesion may be unstable for a finished slope condition and
therefore should not be placed within 15 horizontal feet of the slope face.
• All fill slopes should be keyed into bedrock or other suitable material. Fill keys should be at
least 15 feet wide and inclined at 2 percent into the slope. For slopes higher than 30 feet,
the fill key width should be equal to one-half the height of the slope (see Plate D-5).
• All fill keys should be cleared of loose slough material prior to geotechnical inspection and
should be approved by the Geotechnical Engineer and governmental agencies prior to filling.
• The cut portion of fill over cut slopes should be made first and inspected by the
Geotechnical Engineer for possible stabilization requirements. The fill portion should be
adequately keyed through all surficial soils and into bedrock or suitable material. Soils
should be removed from the transition zone between the cut and fill portions (see Plate D-
2).
Cut Slopes
• All cut slopes should be inspected by the Geotechnical Engineer to determine the need for
stabilization. The Earthwork Contractor should notify the Geotechnical Engineer when slope
cutting is in progress at intervals of 10 vertical feet. Failure to notify may result in a delay
in recommendations.
• Cut slopes exposing loose, cohesionless sands should be reported to the Geotechnical
Engineer for possible stabilization recommendations.
• All stabilization excavations should be cleared of loose slough material prior to geotechnical
inspection. Stakes should be provided by the Civil Engineer to verify the location and
dimensions of the key. A typical stabilization fill detail is shown on Plate D-5.
Grading Guide Specifications Page 5
• Stabilization key excavations should be provided with subdrains. Typical subdrain details
are shown on Plates D-6.
Subdrains
• Subdrains may be required in canyons and swales where fill placement is proposed. Typical
subdrain details for canyons are shown on Plate D-3. Subdrains should be installed after
approval of removals and before filling, as determined by the Soils Engineer.
• Plastic pipe may be used for subdrains provided it is Schedule 40 or SDR 35 or equivalent.
Pipe should be protected against breakage, typically by placement in a square-cut
(backhoe) trench or as recommended by the manufacturer.
• Filter material for subdrains should conform to CALTRANS Specification 68-1.025 or as
approved by the Geotechnical Engineer for the specific site conditions. Clean ¾-inch
crushed rock may be used provided it is wrapped in an acceptable filter cloth and approved
by the Geotechnical Engineer. Pipe diameters should be 6 inches for runs up to 500 feet
and 8 inches for the downstream continuations of longer runs. Four-inch diameter pipe
may be used in buttress and stabilization fills.
GRADING GUIDE SPECIFICATIONS
NOT TO SCALE
DRAWN: JAS
CHKD: GKM
PLATE D-2
FILL ABOVE CUT SLOPE DETAIL
9' MIN.
4' TYP.
MINIMUM 1' TILT BACK
OR 2% SLOPE
(WHICHEVER IS GREATER)
REMOVE U
N
S
U
I
T
A
B
L
E
M
A
T
E
R
I
A
L
BENCHING DIMENSIONS IN ACCORDANCE
WITH PLAN OR AS RECOMMENDED
BY THE GEOTECHNICAL ENGINEER
CUT SLOPE TO BE CONSTRUCTED
PRIOR TO PLACEMENT OF FILL
BEDROCK OR APPROVED
COMPETENT MATERIAL
CUT SLOPE
NATURAL GRADE
CUT/FILL CONTACT TO BE
SHOWN ON "AS-BUILT"
COMPETENT MATERIAL CUT/FILL CONTACT SHOWN
ON GRADING PLAN
NEW COMPACTED FILL
10' TYP.
KEYWAY IN COMPETENT MATERIAL
MINIMUM WIDTH OF 15 FEET OR AS
RECOMMENDED BY THE GEOTECHNICAL
ENGINEER. KEYWAY MAY NOT BE
REQUIRED IF FILL SLOPE IS LESS THAN 5
FEET IN HEIGHT AS RECOMMENDED BY
THE GEOTECHNICAL ENGINEER.
GRADING GUIDE SPECIFICATIONS
NOT TO SCALE
DRAWN: JAS
CHKD: GKM
PLATE D-4
FILL ABOVE NATURAL SLOPE DETAIL
10' TYP.4' TYP.
(WHICHEVER IS GREATER)
OR 2% SLOPE
MINIMUM 1' TILT BACK
REMOVE UN
S
U
I
T
A
B
L
E
M
A
T
E
R
I
A
L
NEW COMPACTED FILL
COMPETENT MATERIAL
KEYWAY IN COMPETENT MATERIAL.
RECOMMENDED BY THE GEOTECHNIAL
ENGINEER. KEYWAY MAY NOT BE REQUIRED
IF FILL SLOPE IS LESS THAN 5' IN HEIGHT
AS RECOMMENDED BY THE GEOTECHNICAL
ENGINEER.
2' MINIMUM
KEY DEPTH
OVERFILL REQUIREMENTS
PER GRADING GUIDE SPECIFICATIONS
TOE OF SLOPE SHOWN
ON GRADING PLAN
BACKCUT - VARIES
PLACE COMPACTED BACKFILL
TO ORIGINAL GRADE
PROJECT SLOPE GRADIENT
(1:1 MAX.)
NOTE:
BENCHING SHALL BE REQUIRED
WHEN NATURAL SLOPES ARE
EQUAL TO OR STEEPER THAN 5:1
OR WHEN RECOMMENDED BY
THE GEOTECHNICAL ENGINEER.
FINISHED SLOPE FACE
MINIMUM WIDTH OF 15 FEET OR AS
BENCHING DIMENSIONS IN ACCORDANCE
WITH PLAN OR AS RECOMMENDED
BY THE GEOTECHNICAL ENGINEER
GRADING GUIDE SPECIFICATIONS
NOT TO SCALE
DRAWN: JAS
CHKD: GKM
PLATE D-5
STABILIZATION FILL DETAIL
FACE OF FINISHED SLOPE
COMPACTED FILL
MINIMUM 1' TILT BACK
OR 2% SLOPE
(WHICHEVER IS GREATER)
10' TYP.
2' MINIMUM
KEY DEPTH
3' TYPICAL
BLANKET FILL IF RECOMMENDED
BY THE GEOTECHNICAL ENGINEER
COMPETENT MATERIAL ACCEPTABLE
TO THE SOIL ENGINEER
KEYWAY WIDTH, AS SPECIFIED
BY THE GEOTECHNICAL ENGINEER
TOP WIDTH OF FILL
AS SPECIFIED BY THE
GEOTECHNICAL ENGINEER
BENCHING DIMENSIONS IN ACCORDANCE
WITH PLAN OR AS RECOMMENDED
BY THE GEOTECHNICAL ENGINEER
4' TYP.
PROPOSED WAREHOUSE
DRAWN: RBCHKD: RGT
SCG PROJECT
20G226-3
PLATE E-1
SEISMIC DESIGN PARAMETERS - 2019 CBC
FONTANA, CALIFORNIA
SOURCE: SEAOC/OSHPD Seismic Design Maps Tool
<https://seismicmaps.org/>
20
21
37
59
21
21
24
ALLUVIUM:Light Gray Brown Silty fine to coarse Sand, littlefine Gravel, medium dense-dry
Light Gray fine to coarse Sand, some fine to coarse Gravel,trace to little Silt, medium dense to dense-dry
Light Gray Brown Silty fine to medium Sand, trace coarse
Sand, trace fine Gravel, very dense-dry
Light Brown to Brown Silty fine Sand to fine Sandy Silt, tracemedium Sand, trace coarse Sand, medium dense-moist
Boring Terminated at 25'
1
1
1
2
11
9
11
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-1
PLATE B-1
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 6 feet
READING TAKEN: At Completion
5
10
15
20
25 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
64
35
59
56
29
40
57
FILL:Brown fine Sand, trace medium to coarse Sand, tracefine Gravel, trace to little Silt, dense-damp
ALLUVIUM:Light Gray fine to coarse Sand, some fine to
coarse Gravel, medium dense to dense-dry
Brown Silty fine Sand, trace medium to coarse Sand, mediumdense-damp
Light Gray Brown fine to coarse Sand, some fine to coarse
Gravel, dense-damp
Gray Brown Silty fine to coarse Sand, little fine to coarseGravel, very dense-damp
Boring Terminated at 20'
DisturbedSample
DisturbedSample
114
125
104
3
2
1
1
5
3
6
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-2
PLATE B-2
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 10 feet
READING TAKEN: At Completion
5
10
15
20 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
30
13
31
63
21
33
59
FILL:Light Brown fine to medium Sand, little Silt, little coarseSand, little fine to coarse Gravel, loose to medium dense-dry
ALLUVIUM:Brown Silty fine Sand, little medium to coarseSand, trace fine to coarse Gravel, loose to medium dense-dry
to damp
Light Gray Brown to Light Gray fine to coarse Sand, some fineGravel, medium dense to dense-dry to damp
Gray Brown Silty fine Sand, trace medium Sand, medium
dense-damp
Light Gray Brown fine to coarse Sand, trace Silt, some fineGravel, little coarse Gravel, dense-dry
Brown Silty fine Sand, little medium to coarse Sand, verydense-damp
Light Gray fine to coarse Sand, some fine to coarse Gravel,very dense-dry
Boring Terminated at 20'
Disturbed
Sample
DisturbedSample
115
120
98
1
4
2
1
6
2
7
2
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-3
PLATE B-3
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 11 feet
READING TAKEN: At Completion
5
10
15
20 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
10
21
43
54
67
24
69
1½± inches Asphaltic concrete, no discernible Aggregate base
FILL:Brown Silty fine Sand, little medium Sand, trace coarseSand, loose to medium dense-damp to moist
ALLUVIUM:Light Gray Brown fine to coarse Sand, little fineto coarse Gravel, trace Silt, medium dense-damp to moist
Light Gray fine to coarse Sand, some fine to coarse Gravel,dense-dry
Brown Silty fine Sand, trace medium to coarse Sand, mediumdense-moist
Light Gray fine to coarse Sand, some fine to coarse Gravel,very dense-dry
Boring Terminated at 20'
111
113
115
118
116
6
7
4
2
2
9
2
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-4
PLATE B-4
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 7 feet
READING TAKEN: At Completion
5
10
15
20 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
23
27
54
20
35
34
84
FILL:Brown Silty fine to medium Sand, trace coarse Sand,little fine Gravel, medium dense-dry
ALLUVIUM:Light Gray Brown fine to coarse Sand, little tosome fine Gravel, trace to little Silt, medium dense to verydense-dry
Brown Silty fine Sand, little medium to coarse Sand, trace to
little fine Gravel, medium dense to dense-damp
Light Gray Brown fine to coarse Sand, little fine Gravel, traceSilt, dense-damp
Light Gray fine to coarse Sand, some fine Gravel, very
dense-damp
Boring Terminated at 25'
2
2
2
4
4
3
3
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-5
PLATE B-5
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 14 feet
READING TAKEN: At Completion
5
10
15
20
25 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
52
19
42
72/11"
29
21
ALLUVIUM:Light Gray Brown Silty fine to medium Sand, littlecoarse Sand, little fine to coarse Gravel, trace fine root fibers,
very dense-dry
Light Brown fine Sand, little medium to coarse Sand, little Silt,trace fine to coarse Gravel, medium dense-damp
Light Gray fine to coarse Sand, some fine to coarse Gravel,trace Silt, medium dense to very dense-dry
Light Brown fine Sandy Silt, trace medium Sand, medium
dense-very moist
Brown Silty fine Sand, trace to little medium to coarse Sand,medium dense-damp to moist
Boring Terminated at 20'
2
3
2
2
2
13
6
JOB NO.: 18G213
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-6
PLATE B-6
DRILLING DATE: 10/30/18
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Scott McCann
FIELD RESULTS LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL
WATER DEPTH: Dry
CAVE DEPTH: 9 feet
READING TAKEN: At Completion
5
10
15
20 GRAPHICLOGPASSING#200SIEVE(%)TEST BORING LOG
DESCRIPTION
POCKETPEN.(TSF)DRYDENSITY(PCF)DEPTH(FEET)MOISTURECONTENT(%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOWCOUNTORGANICCONTENT(%)TBL18G213.GPJSOCALGEO.GDT11/19/18
15
12
23
35
33
50/10"
63
50
103
107
122
119
116
4
5
3
2
2
2
3
2
FILL: Brown Silty fine Sand, trace to little medium to coarse
Sand, trace fine to coarse Gravel, loose to medium
dense-damp
ALLUVIUM: Gray Brown fine to coarse Sand, little fine to
coarse Gravel, occasional Cobbles, medium dense-dry to
damp
@ 9 feet trace to little Silt
Gray brown Silty fine to coarse Sand, little fine to coarse
Gravel, occasional cobbles, very dense-dry to damp
Boring Terminated at 25'
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-7
PLATE B-1
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 19 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20
25 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
10
44
39
73
45
16
16
103
116
120
119
3
2
2
2
1
3
8
8± inches Portland cement concrete
FILL: Brown fine Sandy Silt to Silty fine Sand, little medium to
coarse Sand, trace fine Gravel, loose to medium dense-dry to
damp
@ 3 feet little fine to coarse Gravel
ALLUVIUM: Light Brown fine to coarse Sand, little fine to
coarse Gravel, trace Silt, medium dense-dry to damp
Gray Brown Gravelly fine to coarse Sand, trace Silt,
occasional Cobbles, dense-dry to damp
Brown Silty fine Sand, little medium to coarse Sand, trace fine
to coarse Gravel, occasional Cobbles, medium dense-damp
Brown fine Sandy Silt, trace medium to coarse Sand, medium
dense-moist
Boring Terminated at 20'
Disturbed
Sample
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-8
PLATE B-2
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 9 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
16
21
48
33
14
74/8"
50/5"
4
2
2
2
13
2
3
8± inches Portland cement concrete
FILL: Light Brown Silty fine to coarse Sand, little fine to
coarse Gravel, medium dense-damp
ALLUVIUM: Gray Brown Gravelly fine Sand, little medium to
coarse Sand, medium dense to dense-dry to damp
Brown fine to coarse Sand, trace fine to coarse Gravel,
occasional Cobbles, dense-dry to damp
Dark Brown Silty fine Sand, to fine Sandy Silt, medium
dense-moist to very moist
Gray Brown Silty fine to coarse Sand, little fine to coarse
Gravel, occasional Cobbles, very dense-dry to damp
Boring Terminated at 25'
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-9
PLATE B-3
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 19 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20
25 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
31
34
19
51
62
50/4"
54
120
120
121
4
2
9
2
2
3
2
FILL: Brown Silty fine Sand, little medium to coarse Sand, little
fine to coarse Gravel, medium dense-damp
ALLUVIUM: Gray Brown Gravelly fine to coarse Sand, trace
Silt, occasional Cobbles, medium dense-dry to damp
Brown Silty fine Sand, trace medium to coarse Sand, trace
fine Gravel, medium dense-moist
Gray Brown fine to coarse Sand, little fine to coarse Gravel,
dense-damp
Brown Silty fine Sand, trace medium to coarse Sand, trace
fine Gravel, occasional Cobbles, very dense-damp
Gray Brown fine to coarse Sand, little Silt, little fine to coarse
Gravel, very dense-damp
Boring Terminated at 20'
Disturbed
Sample
Disturbed
Sample
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-10
PLATE B-4
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 11 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
4
13
10
20
39
57
4
6
11
2
2
6
FILL: Brown Silty fine Sand, trace medium to coarse Sand,
loose-damp
FILL: Brown Silty fine Sand to fine Sandy Silt, trace medium to
coarse Sand, medium dense-damp
FILL: Brown fine Sandy Silt, loose to medium dense-moist to
very moist
ALLUVIUM: Gray Brown fine to medium Sand, little coarse
Sand, trace fine to coarse Gravel, medium dense to dense-dry
to damp
@ 13½ feet trace Silt, little fine to coarse Gravel
Dark Gray Brown Silty fine Sand, trace medium Sand, trace
fine to coarse Gravel, very dense-damp
Boring Terminated at 20'
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-11
PLATE B-5
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 12 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
30
10
27
50/6"
55
36
1
1
1
1
1
1
FILL: Brown Silty fine Sand, little medium to coarse Sand,
trace to little fine to coarse Gravel, medium dense to
dense-dry
ALLUVIUM: Brown fine to coarse Sand, trace Silt, little fine to
coarse Gravel, medium dense to very dense-dry
Gray Brown Silty fine to coarse Sand, little fine to coarse
Gravel, occasional Cobbles, very dense-dry
Brown fine to coarse Sand, trace Silt, little fine to coarse
Gravel, occasional Cobbles, dense-dry
Boring Terminated at 20'
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-12
PLATE B-6
DRILLING DATE: 11/3/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Ryan Bremer
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 0 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
20
25
24
19
24
34
51
121
123
3
2
1
2
2
3
3
FILL: Light Brown Gravelly fine to medium Sand, trace coarse
Sand, little Silt, medium dense-damp
ALLUVIUM: Brown fine to coarse Sand, trace Silt, little fine to
coarse Gravel, occasional Cobbles, medium dense-dry to
damp
Dark Gray fine to coarse Sand, trace to little fine to coarse
Gravel, trace Silt, medium dense-dry to damp
Gray Brown fine to coarse Sand, trace to little fine to coarse
Gravel, dense-damp
Gray Brown Gravelly fine to coarse Sand, trace Silt, very
dense-damp
Boring Terminated at 20'
JOB NO.: 20G226-1
PROJECT: Proposed Warehouse
LOCATION: Fontana, California
BORING NO.
B-13
PLATE B-7
DRILLING DATE: 11/20/20
DRILLING METHOD: Hollow Stem Auger
LOGGED BY: Jose Zuniga
FIELD RESULTS
POCKET PEN.(TSF)LABORATORY RESULTS
COMMENTSSURFACE ELEVATION: --- MSL DRY DENSITY(PCF)DEPTH (FEET)MOISTURECONTENT (%)LIQUIDLIMITPLASTICLIMITSAMPLEBLOW COUNTWATER DEPTH: Dry
CAVE DEPTH: 3 feet
READING TAKEN: At Completion
ORGANICCONTENT (%)5
10
15
20 GRAPHIC LOGPASSING#200 SIEVE (%)TEST BORING LOG
DESCRIPTION
TBL 20G226-1.GPJ SOCALGEO.GDT 12/2/20
Classification: FILL: Brown fine Sand, trace medium to coarse Sand, trace fine Gravel
Boring Number:B-2 Initial Moisture Content (%)3
Sample Number:---Final Moisture Content (%)13
Depth (ft)1 to 2 Initial Dry Density (pcf)113.6
Specimen Diameter (in)2.4 Final Dry Density (pcf)122.5
Specimen Thickness (in)1.0 Percent Collapse (%)1.75
Proposed Warehouse
Fontana, California
Project No. 18G213
PLATE C- 1
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Addedat 1600 psf
Classification: Brown Silty fine Sand, little medium to coarse Sand
Boring Number:B-3 Initial Moisture Content (%)5
Sample Number:---Final Moisture Content (%)14
Depth (ft)3 to 4 Initial Dry Density (pcf)114.1
Specimen Diameter (in)2.4 Final Dry Density (pcf)122.1
Specimen Thickness (in)1.0 Percent Collapse (%)1.43
Proposed Warehouse
Fontana, California
Project No. 18G213
PLATE C- 2
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification: Light Gray Brown to Light Gray fine to coarse Sand, some fine Gravel
Boring Number:B-3 Initial Moisture Content (%)2
Sample Number:---Final Moisture Content (%)13
Depth (ft)5 to 6 Initial Dry Density (pcf)120.1
Specimen Diameter (in)2.4 Final Dry Density (pcf)122.6
Specimen Thickness (in)1.0 Percent Collapse (%)0.58
Proposed Warehouse
Fontana, California
Project No. 18G213
PLATE C- 3
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification: Gray Brown Silty fine Sand, trace medium Sand
Boring Number:B-3 Initial Moisture Content (%)7
Sample Number:---Final Moisture Content (%)28
Depth (ft)9 to 10 Initial Dry Density (pcf)97.3
Specimen Diameter (in)2.4 Final Dry Density (pcf)101.0
Specimen Thickness (in)1.0 Percent Collapse (%)0.74
Proposed Warehouse
Fontana, California
Project No. 18G213
PLATE C- 4
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Proposed Warehouse
Fontana, California
Project No. 18G213
PLATE C-5
120
122
124
126
128
130
132
134
136
138
140
142
144
146
0 2 4 6 8 10 12 14DryDensity(lbs/ft3)Moisture Content (%)
Moisture/Density Relationship
ASTM D-1557
Soil ID Number B-2 @ 0 to 5'
Optimum Moisture (%)6.5
Maximum Dry Density (pcf)130.5
Soil Brown fine to coarse Sand,
Classification little fine to coarse Gravel
Zero Air Voids Curve:
Specific Gravity = 2.7
Classification:
Boring Number:B-7 Initial Moisture Content (%)4
Sample Number:---Final Moisture Content (%)17
Depth (ft)1 to 2 Initial Dry Density (pcf)103.5
Specimen Diameter (in)2.4 Final Dry Density (pcf)111.2
Specimen Thickness (in)1.0 Percent Collapse (%)1.72
Proposed Warehouse
Fontana, California
Project No. 20G226-1
PLATE C- 1
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification:
Boring Number:B-7 Initial Moisture Content (%)5
Sample Number:---Final Moisture Content (%)18
Depth (ft)3 to 4 Initial Dry Density (pcf)101.3
Specimen Diameter (in)2.4 Final Dry Density (pcf)109.3
Specimen Thickness (in)1.0 Percent Collapse (%)1.53
Proposed Warehouse
Fontana, California
Project No. 20G226-1
PLATE C- 2
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification:
Boring Number:B-7 Initial Moisture Content (%)3
Sample Number:---Final Moisture Content (%)10
Depth (ft)5 to 6 Initial Dry Density (pcf)119.8
Specimen Diameter (in)2.4 Final Dry Density (pcf)129.2
Specimen Thickness (in)1.0 Percent Collapse (%)1.14
Proposed Warehouse
Fontana, California
Project No. 20G226-1
PLATE C- 3
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Classification:
Boring Number:B-7 Initial Moisture Content (%)2
Sample Number:---Final Moisture Content (%)14
Depth (ft)7 to 8 Initial Dry Density (pcf)112.7
Specimen Diameter (in)2.4 Final Dry Density (pcf)118.0
Specimen Thickness (in)1.0 Percent Collapse (%)0.78
Proposed Warehouse
Fontana, California
Project No. 20G226-1
PLATE C- 4
0
2
4
6
8
10
12
14
16
18
20
0.1 1 10 100ConsolidationStrain(%)Load (ksf)
Consolidation/Collapse Test Results
Water Added
at 1600 psf
Proposed Warehouse
Fontana, California
Project No. 20G226-1
PLATE C-5
116
118
120
122
124
126
128
130
132
134
136
138
4 6 8 10 12 14 16DryDensity(lbs/ft3)Moisture Content (%)
Moisture/Density Relationship
ASTM D-1557
Soil ID Number B-7 @ 0-5'
Optimum Moisture (%)8.5
Maximum Dry Density (pcf)128
Soil
Classification
Brown Silty fine Sand, trace
medium to coarse Sand, trace fine
to coarse Gravel,
Zero Air Voids Curve:
Specific Gravity = 2.7