HomeMy WebLinkAbout5848-1CITY OF FONTANA SEWER IMPROVEMENT NOTES
1. ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF FONTANA STANDARD PLANS,
THE CONTRACT PROVISIONS AND THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS
CONSTRUCTIONS ("GREEN BOOK"). ALL REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE
LATEST EDITION UNLESS OTHERWISE NOTED.
2. WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT DOCUMENTS THAT CAN NOT BE
RESOLVED BY REFERENCE TO PRECEDENCE PROVISIONS IN THE "GREEN BOOK", THE CONTRACTORS
SHALL IMMEDIATELY REPORT SAID CONFLICT TO THE CITY ENGINEERS FOR RESOLUTION.
J. ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE CITY ENGINEER.
4. CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA COMMUNITY
DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE START OF ANY WORK
INSPECTION COORDINATION SHALL BE REQUESTED AT LEAST TWO WORKING DAYS PRIOR TO THE
START OF ANY WORK IN PUBLIC RIGHT-OF-WAY WITHIN THE CITY LIMITS. CALL (909) 350-7610.
5. THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES, METHODS AND
PROCEDURES DESCRIBED IN STATE OF CALIFORNIA MANUAL OF TRAFFIC CONTROLS, LATEST NON -
METRIC EDITION UNLESS OTHERWISE DIRECTED BY THE CITY TRAFFIC ENGINEER.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN BARRICADES, DELINEATORS
OR OTHER TRAFFIC CONTROL DEVICES AT ALL TIMES.
7. THE CONTRACTORS SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR TRENCH WORK FOR
TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE CALIFORNIA STATE DIVISION OF INDUSTRIAL
SAFETY.
8. THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET IN DEPTH SHALL BE
GUARDED BY SHORING, SLOPING OF THE GROUND OR OTHER APPROVED MEANS PURSUANT TO THE
REQUIREMENTS OF THE DIVISION OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES
LESS THAN FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR GROUND
MOVEMENT.
9. NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF WAY WITHOUT OBTAINING
A SEPARATE PERMIT FOR THAT PURPOSE.
10. THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM AVAILABLE INFORMATION,
HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE, IN THE FIELD,
THE TRUE LOCATION AND ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER
PRECAUTION TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT AT 1-800-277-2600 TWO WORKING DAYS BEFORE EXCAVATION. .
11. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY COMPANIES INCLUDING,
BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC, CABLE TELEVISION, LANDSCAPING, LANDSCAPE
IRRIGATION, DOMESTIC WATER, RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND
CALTRANS. ALL UTILITY COMPANIES SHALL BE GIVEN TWO WORKING DAYS NOTICE PRIOR TO WORK
AROUND THEIR FACILITIES.
12. THE CONTRACTOR SHALL NOT OPERATE ANY FIRE HYDRANT OR WATER MAIN VALVES WITHOUT
APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE
WATER COMPANY FOR VALVE OPERATION AND WATER REQUIREMENTS.
13. STATIONING REFERS TO THE CENTERLINE OF STREETS EXCEPT WHERE OTHERWISE NOTED.
14. ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE ENGINEER TO: ENABLE THE
CONTRACTOR TO CONSTRUCT THE WORK TO THE PLAN GRADE(S). THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING
DURING CONSTRUCTION.
15. THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS, MONUMENT TIES OR BENCH
MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY ENGINEER.
16. REMOVAL AND REPLACEMENT OR EXISTING SURVEY CONTROL, INCLUDING SURVEY MONUMENTS,
MONUMENT TIES AND BENCH MARKS, SHALL BE DONE BY A REGISTERED CIVIL ENGINEER OR
LICENSED LAND SURVEYOR. SURVEY MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS
CONSTRUCTION SHALL BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE WEEK
PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE ESTABLISHED FOR LATER
REPLACEMENT OF THE MONUMENT
17. THE CONTRACTOR SHALL MAINTAIN ACCESS FOR LOCAL RESIDENTS AND BUSINESS AT ALL TIMES. A
MINIMUM 12 FOOT LAND SHALL BE MAINTAINED AT ALL TIMES IN THE CONSTRUCTION AREA FOR
RESIDENTS AND EMERGENCY VEHICLES.
18. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF DUST .CONTROL,
INCLUDING ADEQUATE WATERING, AT ALL TIMES.
19. THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT, OR DEBRIS TO BE
DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT TO THE RIGHT OF WAY DURING
CONSTRUCTION WITHOUT PRIOR ' WRITTEN APPROVAL.
20. NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF THE CITY INSPECTOR.
21. A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION, FAILURE TO OBTAIN THE
REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF THAT PORTION OF THE WORK UNTIL THE
SPECIFIED DENSITY IS OBTAINED.
22. CARE SHOULD BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES FROM UNDERMINING STREET
IMPROVEMENTS. UPON INSPECTION OF THE SITE, THE CITY ENGINEER MAY REQUIRE TEMPORARY
NON-ERODEABLE SWALES ENTERING OR LEAVING IMPROVEMENTS.
23. ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR AND FINISH TO MATCH
EXISTING CONCRETE.
24. IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR SHALL PROVIDE A TERMINAL
CLEANOUT AT THE PHASE BOUNDARY, NOT MORE THAN 150 FEET FROM THE DOWNSTREAM MANHOLE,
SEE CITY OF FONTANA STANDARD DETAIL FOR TERMINAL CLEANOUT.
25. SANITARY SEWER LINES SHALL BE CONSTRUCTEDMOF BELL AND SPIGOT OR BAND SEAL TYPE
VETRIFIED CLAY PIPE (V. C. P.) EXTRA STRENGTH CLASS AND SHALL CONFORM TO THE PROVISIONS OF
THE ASTM DESIGNATION C700 FOR V.C.P.
26. NO OPEN TRENCHES SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT PRIOR APPROVAL OF THE
CITY ENGINEER.
27. SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED AT MANHOLE WALLS TO
ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT.
28. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING FACILITIES, AND VERIFY
ELEVATION AND LOCATION OF CONNECTIONS. CITY APPROVAL OF CONNECTIONS TO EXISTING
FACILITIES DOES NOT IMPLY CORRECTNESS OF ELEVATIONS OR LOCCATOONS SHOWN ON THE PLANS.
29. ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT 27 MINIMUM GRADE UNLESS OTHERWISE
APPROVED BY THE CITY ENGINEER.
30. TERMINATE ALL 4" HOUSE LATERALS 3 FEET INSIDE THE LOT WITH A PLUG 12" BELOW THE GROUND
SURFACE. WHEN PUBLIC UTILITY EASEMENTS EXIST NEXT TO THE STREET RIGHT OF WAY, THE LATERAL
SHALL TERMINATE 3 FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY EASEMENT.
31. THE SEWER CONTRACTOR SHALL STAMP AN "S" IN THE FACE OF THE CURB AT THE LOCATION OF THE
SEWER LATERAL.
32. IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE PROPOSED IMPROVEMENTS,
THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND ALL AFFECTED AGENCIES IMMEDIATELY.
33. NO CONCRETE SHALL ` BE PLACED UNTIL THE FORMS AND REINFORCING STEEL HAVE BEEN PLACED,
INSPECTED AND APPROVED.
,__..EWER IMPROVEMENT
34. ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED PRIOR TO PAVING OF
STREETS.
35. APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT PAVEMENT PRIOR TO
PLACEMENT.
36. ALL MANHOLES, CLEANOUT FRAMES, COVERS AND VALVES BOXES SHALL BE RAISED TO FINISHED
GRADE BY THE PAVING CONSTRACTOR UPON COMPLETION OF PAVING.
ROUGH GRADING.
37. UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL SIGNING, STRIPING,
BARRICADES, AND OTHER TRAFFIC CONTROL DEVICES TO THE SATISFACTION OF THE CITY TRAFFIC
ENGINEER.
38. AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER OF RECORD, WHO
SHALL PROVIDE RECORD DRAWINGS TO THE CITY ENGINEER.
UTILITY CONTACTS
ELECTRICITY
WATER
SEWER
SOUTHERN CALIFORNIA EDITON COMPANY
FONTANA WATER COMPANY
CITY OF FONTANA
300 N. PEPPER AVE.
8440 NUEVO AVENUE
8353 SIERRA AVENUE
RIALTO CA. 92376
FONTANA, CA. 92335
FONTANA, CA. 92335
UNDERGROUND: (909) 357-6233
ATTN: MICHAEL McGRAW"
(909) 350-6632
TRANSMISSION: (909) 875-5100
(909) 822-2201
PIPELINES: (909) 657-1233
FAX (909) 283-5046
DISTRIBUTION: (909) 357- 6233
GAS
GENERAL TELEPHONE COMPANY
COMCAST CABLEVISION
SOUTHERN CALIFORNIA GAS CO.
1400 E. PHILLIPS RANCH BLVD.
1205 DUPONT AVENUE
1981 LUGONIA AVENUE
ONTARIO, CA. 91766
ONTARIO, CA. 91761
REDLANDS, CA. 92374
ATT'N: STEVE HOCK
ATT'N: JACK HAYES
ATT'N: JOHN OATES
(800) 422-4133
(909) 390-4738
EMERGENCIES. (800) 427-2200
ENGINEER'S NOTE:
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES, CONDUITS OR ANY
OTHER STRUCTURES SHOWN ON THESE DRAWINGS WERE OBTAINED BY A SEARCH OF THE
AVAILABLE RECORDS. TO THE BEST OF OUR KNOWLEDGE THERE ARE NO OTHER UTILITIES
OR STRUCTURES EXCEPT AS SHOWN ON THESE DRAWINGS. THE CONTRACTOR IS REQUIRED
TO TAKE DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN ON THE
DRAWINGS. THE CONTRACTOR FURTHER ASSUMES ALL LIABILITY AND RESPONSIBILITY FOR
UTILITY PIPES, CONDUITS OR STRUCTURES SHOWN OR NOT SHOWN ON THESE DRAWINGS.
CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR
JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT,
INCLUDING SAFETY OF ALL PERSONS AND PROPERTY, AND THAT THIS REQUIREMENT SHALL
APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS, AND THAT THE
CONTRACTOR SHALL DEFEND, INDEMNIFY AND HOLD THE COUNTY, THE OWNER AND THE
ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION
WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING
FROM THE SOLE NEGLIGENCE OF THE OWNER OR THE ENGINEER.
SHEET INDEX
SHEET 1 OF 2 = GENERAL NOTES
SHEET 2 OF 2 = PLAN AND PROFILE
SEE SHEET 2 OF 2
r BALTRAY WAY
W
uj
INDEX MAP
N. T. S.
CONSTRUCTION NOTES:
SUMMIT AVE.
CURTIS AVE.
w
W �
�
w Q
Q L6
SITE
o Q
w
a
SIERRA LAKE
PARKWAY
VICINITY MAP
N.T.S.
N,
NO PAVING
PAVING -VARIES
1
i y i i
BASE -VARIES
�(1
vv
i i v i i i i i
i i v ♦ e� i i i
l�YIIIIII*
Vh
.r
i i i i i i i y y i y i y i i i i
i i i i i i i i
a a i i i i i ♦
��
(*�\
Qfz
12" SAND
6" LIFT
PIPE SIZE
PER PLAN
If Ifill IImr=IIIII lift
6" SAND
6" PIPE J 6"
1-mol-4 -1- -1
PER PLAN
-
WATER/SEWER TRENCH DETAIL
N. T.S.
NOTES:
1. BACKFILL SHALL BE 90% RELATIVE COMPACTION
BY TAMPING AT 6" LIFT
2. SAND BACKFILL AND BEDDING SHALL CLEAN WITH NO
ASHES, CINDERS, REFUSE, ORGANIC MATTER, OR
OTHER COROSSIVE MATERIALS.
LEGEND:
FL = FLOWLINE ELEVATION
TC = TOP OF CURB ELEVATION
(X) = EXISTING ELEVATION
TP = TOP OF PAVEMENT
W = WATER LINE
S = SEWER LINE
G = GAS LINE
FS = FINISHED SURFACE
ESTIMATED
QUANTITIES
CONSTRUCT 8" EXTRA STRENGTH VETRIFIED
CLAY PIPE (V C.P.) SEWER MAIN
228 L.F.
0
CONSTRUCT STANDARD CAST IN PLACE 60"
MANHOLE PER CITY STANDARD NO. 2001
1 EACH
�3
CONSTRUCT 4" VCP SEWER LATERAL AND HOUSE
CLEANOUT PER CITY STANDARD NO. 2005 & 2006
5 EACH
CUT EXISTING 8" SEWER MAIN AT MANHOLE
LOCATION
1 EACH
TRENCH REPAIR PER CITY STD. NO. 1008
108 S.F.
6
CONSTRUCT STANDARD CAST IN PLACE 48"
MANHOLE PER CITY STANDARD NO. 2001
1 EACH
BASIS OF BEARINGS IS THE CENTERLINE OF CURTIS AVENUE
AVENUE BEING NORTH 00'08' 14" EAST PER MB 300/93-98
MCN 14-028, DRP 18-025, TTM14-002EX