HomeMy WebLinkAbout5780LT-1GENERAL NOTES FOR STREET LIGHT PLANS
1. LIGHTING LAYOUT SHALL COMMENCE AT STREET INTERSECTIONS. STREET LIGHT SPACING
BETWEEN INTERSECTIONS SHALL BE AS SPECIFIED IN THE TABLE ON SHEET 3
AND LOCATED AT THE PROLONGATION OF THE PROPERTY LINES. STREET LIGHT LAYOUTS SHALL BE
REVIEWED FOR CONFLICTS WITH OTHER UTILITIES (CATCH BASINS, FIRE HYDRANTS,
TRANSFORMERS, ETC.)
2. USE OF BRAND NAMES IN THESE STANDARDS IS NOT INTENDED TO RESTRICT COMPETITION.
EQUIVALENT PRODUCTS MAY BE SUBSTITUTED WITH THE APPROVAL OF THE CITY ENGINEER.
J. SIDEWALK WIDTHS TO BE PER APPROVED STREET IMPROVEMENT PLANS. A MINIMUM OF 4'
UNOBSTRUCTED SIDEWALK CLEARANCE IS REQUIRED.
4. ANY CHANGE IN LOCATION OF STREET LIGHTS FROM THE APPROVED PLANS OR STANDARDS IS
SUBJECT TO WRITTEN APPROVAL BY THE CITY ENGINEER.
5. ALL STREET LIGHTS SHALL HAVE AN ANTI -GRAFFITI COATING
10
CITY OF FONTANA
STREET LIGHT PLAN
10665 REDWOOD AVENUE
LEGEND AND QUANTITIES:
INSTALL 41 W LED LUM/NAIRE COBRAHEAD
PER CITY STANDARD PLAN N0. 404
� EXISTING 9500 LUMEN HPSV STREET LIGHT
(100 WATT) 27 Fr LUMINAIRE HEIGHT
�-- INDICATES FIRE HYDRANT
REMOVE EXISTING SCE POWER POLE
(UNDERGROUND POWER LINE BY SCE)
1 EACH
2 EACH
RIGHT OF WAY
0 10 20 40 60
SCALE: 1 "=20'
I �
`j
I Q
0
W I
al
10 FREEWAY 10
BOYLE AVE.
Q W W W
Q >
SLOVER o AVE. e
W
v ALISO DR. v
SANTA ANA AVE.
V CTN
NOT TO SCALE
16+00 17+00
_ � N00'20'24"E 1 9+00 20+00
_ _---------- EXIST. CURB/GUTTER ---------` �� 0� 0�•�G EXIST. CURB/GUTTER
DRIVEWAY EXIST. FH DRIVEWAY
EXIST. SIDEWALK
SIDEWALK
RIGHT OF WAY
Z W
J O �6 J
+ '� co C' APN: 0236-141-17
L APN: 0236-141-21
APN: 0236-141-18
MCN
13-012
ASP
13-006
ASP
13-006EX
ASP
13-006R1