GENERAL NOTES
1 ALL WORK SHALL BE IN ACCORDANCE WITH THESE PLANS, THE CITY OF
FONTANA STANDARD PLANS, THE CONTRACT PROVISIONS AND THE STANDARD
SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION ('GREEN BOOK'. ALL
REFERENCE SPECIFICATIONS AND STANDARDS SHALL BE THE LATEST EDITION
UNLESS OTHERWISE NOTED.
2 WHEN A TECHNICAL CONFLICT IS FOUND TO EXIST IN THE CONTRACT
DOCUMENTS THAT CAN NOT BE RESOLVED BY REFERENCE TO PRECEDENCE
PROVISIONS IN THE "GREEN BOOK, THE CONTRACTOR SHALL IMMEDIATELY
REPORT SAID CONFLICT TO THE CITY ENGINEER FOR RESOLUTION.
3 ALL MATERIALS AND METHODS ARE SUBJECT TO THE APPROVAL OF THE
CITY ENGINEER.
4 CONSTRUCTION PERMITS SHALL BE OBTAINED FROM THE CITY OF FONTANA
COMMUNITY DEVELOPMENT DEPARTMENT, ENGINEERING DIVISION PRIOR TO THE
START OF ANY WORK. INSPECTION COORDINATION SHALL BE REQUESTED AT
LEAST TWO WORKING DAYS PRIOR TO THE START OF ANY WORK IN PUBLIC
RIGHT-OF-WAY- WITHIN THE CITY LIMITS. CALL (909) 350-7610.
5 THE CONTRACTOR SHALL CONFORM TO ALL TRAFFIC CONTROL POLICIES,
METHODS AND PROCEDURES DESCRIBED IN THE STATE OF CALIFORNIA MANUAL
OF TRAFFIC CONTROLS, LATEST NON -METRIC EDITION UNLESS OTHERWISE
DIRECTED BY THE CITY TRAFFIC ENGINEER.
6 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAINTAIN
BARRICADES, DELINEATORS OR OTHER TRAFFIC CONTROL DEVICES AT ALL
TIMES.
7 THE CONTRACTOR SHALL OBTAIN A PERMIT TO PERFORM EXCAVATION OR
TRENCH WORK FOR TRENCHES 5 FEET OR GREATER IN DEPTH FROM THE
CALIFORNIA STATE DIVISION OF INDUSTRIAL SAFETY.
.. w
8 THE WALLS AND FACES OF ALL EXCAVATIONS GREATER THAN FIVE (5) FEET
IN DEPTH SHALL BE GUARDED BY SHORING, SLOPING OF THE GROUND OR
OTHER APPROVED MEANS PURSUANT TO THE REQUIREMENTS OF THE DIVISION
OF INDUSTRIAL SAFETY OF THE STATE OF CALIFORNIA. TRENCHES LESS THAN
FIVE (5) FEET SHALL ALSO BE GUARDED WHEN THE POTENTIAL EXISTS FOR
GROUND MOVEMENT.
9 NO MATERIAL OR EQUIPMENT SHALL BE STORED IN THE PUBLIC RIGHT OF
WAY WITHOUT OBTAINING A SEPARATE PERMIT FOR THAT PURPOSE.
10 THE LOCATIONS OF UTILITIES SHOWN HAVE BEEN DETERMINED FROM
AVAILABLE INFORMATION, HOWEVER, IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO DETERMINE, IN THE FIELD, THE TRUE LOCATION AND
ELEVATION OF ANY EXISTING UTILITIES, AND TO EXERCISE PROPER PRECAUTION
TO AVOID DAMAGE THERETO. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT AT 1-800-227-2600 TWO WORKING DAYS BEFORE
EXCAVATION.
11 THE CONTRACTOR SHALL COORDINATE CONSTRUCTION WITH ALL UTILITY
COMPANIES INCLUDING, BUT NOT LIMITED TO, GAS, TELEPHONE, ELECTRIC,
CABLE TELEVISION, LANDSCAPING, LANDSCAPE IRRIGATION, DOMESTIC WATER,
RECLAIMED WATER, SEWER, STORM DRAIN, FLOOD CONTROL AND CALTRANS.
ALL UTILITY COMPANIES SHALL BE- GIVEN TWO WORKING DAYS NOTICE PRIOR
TO WORK AROUND THEIR FACILITIES.
12 THE CONTRACTOR SHALL. NOT OPERATE ANY FIRE HYDRANT OR WATER
MAIN VALVES WITHOUT APPROPRIATE AGENCY AUTHORIZATION. CONTRACTOR
SHALL COORDINATE WITH THE APPROPRIATE WATER COMPANY FOR VALVE
OPERATION AND WATER REQUIREMENTS.
13 STATIONING REFERS TO THE CENTERLINE OF SEWER EXCEPT WHERE
OTHERWISE NOTED.
14 ADEQUATE CONSTRUCTION CONTROL STAKES SHALL BE SET BY THE
ENGINEER TO ENABLE THE CONTRACTOR TO CONSTRUCT THE WORK TO THE
PLAN GRADES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
PRESERVATION OF BENCHMARKS AND CONSTRUCTION CONTROL STAKING
DURING CONSTRUCTION.
15 THE CONTRACTOR SHALL NOT DISTURB EXISTING SURVEY MONUMENTS,
MONUMENT TIES OR BENCH MARKS WITHOUT PRIOR NOTIFICATION TO THE CITY
ENGINEER.
16 REMOVAL ANDwREPLACEMENT OF EXISTING SURVEY CONTROL, INCLUDING
SURVEY MONUMENTS, MONUMENT TIES AND BENCH MARKS, SHALL BE DONE
BY A REGISTERED CML ENGINEER OR LICENSED LAND SURVEYOR. SURVEY
MONUMENTS THAT WILL BE DESTROYED AS A RESULT OF THIS CONSTRUCTION
SHALL. BE REPLACED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER ONE
WEEK PRIOR TO CONSTRUCTION SO THAT TIES TO MONUMENTS CAN BE
ESTABLISHED FOR LATER REPLACEMENT OF THE MONUMENT.
17 THE CONTRACTOR SHALL MAINTAIN -ACCESS FOR LOCAL RESIDENTS AND
BUSINESSES AT ALL TIMES. A MINIMUM 12 FOOT LANE SHALL BE MAINTAINED
AT ALL TIMES IN THE CONSTRUCTION AREA FOR RESIDENTS AND EMERGENCY
VEHICLES.
18 THE CONTRACTOR SHALL PROVIDE AND MAINTAIN AN EFFECTIVE MEANS OF
DUST CONTROL, INCLUDING ADEQUATE WATERING, AT ALL TIMES.
19 THE CONTRACTOR SHALL NOT CAUSE ANY EXCAVATED MATERIAL, MUD, SILT
OR DEBRIS TO BE DEPOSITED ONTO PUBLIC OR PRIVATE PROPERTY ADJACENT
TO THE RIGHT OF WAY DURING CONSTRUCTION WITHOUT PRIOR WRITTEN
APPROVAL
20 NO TRENCH BACKFILL SHALL TAKE PLACE WITHOUT PRIOR APPROVAL OF
THE CITY INSPECTOR.
21 A GEOTECHNICAL ENGINEER SHALL CERTIFY ALL BACKFILL COMPACTION.
FAILURE TO OBTAIN THE REQUIRED DENSITY SHALL REQUIRE RE -WORKING OF
THAT PORTION OF THE WORK UNTIL THE SPECIFIED DENSITY IS OBTAINED.
22 CARE SHOULD, BE TAKEN TO PREVENT GRADES, DITCHES, AND SWALES
FROM UNDERMINING STREET IMPROVEMENTS. UPON INSPECTION OF THE SITE,
THE CITY ENGINEER MAY REQUIRE TEMPORARY NON-ERODABLE SWALES
ENTERING OR LEAVING IMPROVEMENTS.
23 ALL EXPOSED CONCRETE SURFACES SHALL CONFORM IN GRADE, COLOR
AND FINISH TO MATCH EXISTING CONCRETE. -
24 IF SEWER CONSTRUCTION IS TO BE DONE IN PHASES, THE CONTRACTOR
SHALL PROVIDE A TERMINAL CLEANOUT AT THE PHASE BOUNDARY, NOT MORE
THAN 150 FEET FROM THE DOWNSTREAM MANHOLE, SEE CITY OF FONTANA
STANDARD DETAIL FOR TERMINAL CLEANOUT.
25 SANITARY SEWER LINES SHALL BE CONSTRUCTED OF BELL AND SPIGOT OR
BAND SEAL TYPE VITRIFIED CLAY PIPE (V.C.P.) EXTRA STRENGTH CLASS AND
SHALL CONFORM TO THE PROVISIONS OF THE ASTM DESIGNATION C700 FOR
V.C.P.
26 NO OPEN TRENCH SHALL BE ALLOWED AT THE END OF THE DAY WITHOUT
PRIOR APPROVAL OF THE CITY ENGINEER. CITY OF FONTANA
27 SHORT VCP STUBS WITH FLEXIBLE COMPRESSION JOINTS SHALL BE USED- PROJECT suT A�uE
AT MANHOLE WALLS TO ALLOW FOR MINOR DEFLECTIONS IN ALIGNMENT. - LOCATIONSEMLAK PARKWAY
28 PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL EXPOSE EXISTING -
0 898 ir
FACILITIES,
AND VERIFY ELEVATION AND LOCATION OF CONNECTIONS. CITY STATE ROUTE
APPROVAL OF CONNECTIONS TO EXISTING FACILITIES DOES NOT IMPLYJIM
CORRECTNESS OF ELEVATIONS OR LOCATIONS SHOWN ON THE PLANS. W a 210 FREEWAY
29 ALL 4" HOUSE LATERALS SHALL BE INSTALLED AT A 2% MINIMUM GRADEEWER IMPROV
Q'
UNLESS OTHERWISE APPROVED BY THE CITY ENGINEER. S EMENT PLANS
30 TERMINATE ALL 4' HOUSE SEWER LATERALS 3 FEET INSIDE THE LOT WITH 13M WE
YEWE
A PLUG 12' BELOW THE GROUND SURFACE. WHEN PUBLIC UTILITY EASEMENTS ,�
AFONTANA
EXIST NEXT TO THE STREET RIGHT OF WAY, THE LATERAL SHALL TERMINATE 3
FEET INSIDE THE LOT AS MEASURED FROM THE UTILITY EASEMENT.
.�
31 THE SEWER CONTRACTOR SHALL STAMP AN " IN THE FACE OF THE Iya o e����1CURB A THE LOCAITON OF THE SEWER LATERALS" Ere-
32 IF EXISTING UTILITIES OR ANY OTHER FACILITIES CONFLICT WITH THE
PROPOSED IMPROVEMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER-� �f
10 F EEWAY
AND ALL AFFECTED AGENCIES IMMEDIATELY. I „' ,; I ---
I VICINITY MAP
33 NO CONCRETE SHALL BE PLACED UNTIL THE FORMS AND REINFORCING ,� „ ��, 19 20 21 22 23 I 1
STEEL HAVE BEEN PLACED, INSPECTED AND APPROVED. , . (DoesH0017 18
�% a o ®� �- 17 S H#11 SMH #12 ' M
34 ALL UNDERGROUND UTILITIES SHALL BE INSTALLED, TESTED AND APPROVED ,,% „'� -
PRIOR TO PAVING OF STREETS. ;'' I; t� _ , i R� 15 24
35 APPROVED SOIL STERILANT IS REQUIRED UNDER ALL NEW ASPHALT
_1
` _ - - 13
PAVEMENT PRIOR TO PLACEMENT. _
36 ALL MANHOLES CLEANOUT FRAMES COVERS AND VALVE BOXES S '� -
� 12
/ I �
HALL BE � 25
RAISED TO FINISHED GRADE BY THE PAVING CONTRACTOR UPON COMPLETION + '� NN ` 94 95
OF PAVING.
I 10 y �� 80 + ' ii w+
I 8 9 .0 MH # 10 I 93 96 i 26 +
37 UPON COMPLETION OF CONSTRUCTION, CONTRACTOR SHALL RESTORE ALL I 7 N� s- 79 I W r I +
SIGNING STRIPING BARRICADES AND OTHER TRAFFIC CONTROL DEVICES TO ' 6
C� I QS I � 1
THE SATISFACTION OF THE CITY TRAFFIC ENGINEER. ® I (,% + `,,, THE QUANTITIES SHOWN HEREON ARE ESTIMATES ONLY. THE CONTRACTORS SHALL PREPARE THEIR
SMH 9 " " 81 1 1 92 97 + 27 ' W(` ,..+ OWN QUANTITIES AND BID A COMPLETE JOB.
38 AS -BUILT DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR TO THE 5 " " " j 78 1 1 I +>I jBE
ENGINEER OF RECORD, WHO SHALL PROVIDE RECORD DRAWINGS TO THE CITY o I'
ENGINEER. - l 1 fi8 1 1 28 rT = CONSTRUCTION NOTES QUANTITIES
I I 11i# 8 u7 o� no I I �✓�
VIY11 1 Tr 1_r I i - , 1
0_ +
At 1; , ' O+ 1 CONSTRUCT 8 EXTRA STRENGTH V.C.P. SEWER MAIN 49543 LF
' ' I 1Q >- 29 + + 2 CONSTRUCT 48' PRECAST CONCRETE MANHOLE PER CITY STD. DWG. NO. 2001 15 EA
CITY OF FONTANA, UTILITY NOTIFICATION LIST S8 59 66 69 ; Q 76 83 1 13:90 1 99 Q SMH # 115 W' - _
+ - - 3 CONSTRUCT 4 V.C.P. SEWER LATERAL & HOUSE CLEANOUT PER CITY STD. DWG. NO 2005 2,945 LF
CITY OF FONTANA AT&T I + W ; 57 1 1 1 '
8353 SIERRA AVE 22311 BROOKHURST ST SUITE 203 I ? 3 Q , 1 ' '~ Z W 30 i ; ; 4 CONSTRUCT SEWER BACKFLOW VALVE 63 EA
�� 1 I
FONTANA, CA 92335 HUNTINGTON BEACH, CA 92646 I 65 70 Z 75 84 + +� 89 100 Q + i 1 �_ 5 REMOVE EXISTING 8' PLUG 1 EA
(909) 350-6632 (714) 963-7964 I u W 60 J
1 2 Z 1 56 +
SO. CALIF. GAS COMPANY SPRINT + 0 31 + 1
1 I Z 0 88 101 I
1981 W. LUGONIA AVE 2592 DUPONT DR 0 61 64 71 74 85 10REDLANDS CA 92374 IRVINE, CA 92612 I C 4JL;�_()
(909) 335-7967 (800) 659-9698 I' i 1 0 i LL
1 i + 32 i
EMERGENCIES: (800) 427-2200 i 55 62 i + 87 102 + 1 +
TIME WARNER CABLE I ' 63 72 i 73 86 -
SO. CALIF. EDISON COMPANY 1500 AUTO CENTER DR - - 1 ARKSTO E STREE
300 ONTARIO, CA 91761
RIALTO, CA 92376 PEPPER AVE (909) 975-3439
0
909 820-5598 - UNDERGROUND SUNESYS, LLC
909 875-5100 -TRANSMISSION 1325 PICO ST #106 I + H # 1 MH i _ - - --r--- - - - - - -
7
213 637_1233 _ PIPELINES CORONA, CA 92881 +
909 357-6505 DISTRIBUTION (951) 278-0400 SM # 3 SMH 4 SMH 5 SM # '
UNDERGROUND SERVICE ALERT"-°
�. o I � � 9 38 37 36 35 34 33 '' I
(800) 422-4133 SOILS ENGINEER j' 1 ' WQMP 54 53 52 51 50 49 48 47 46 45 44 43 42 40
LEIGHTON AND ASSOCIATES, INC. 1 BASIN
FONTANA WATER COMPANY 10532 ACACIA STREET SUITE B-6 -- - - — - - -- _ - _ --y - T - - -*- - - y.r'►-i
15966 ARROW BOULEVARD o - -- - - _.--�-_--
---
RANCHO CUCAMONGA, CA 91730-5455 �t
fi
NT CA 92335
TEL(909) 48 s
( )42205
909 822-2201A�3 I -
FAX 909 484-2170 °
DEVELOPER LEGEND
LENNAR HOMES PROPOSED SEWER LINE INDEX MAP
980 MONTECITO DRIVE -8m S-- EXIST. SEWER LINE SCALE: 1 "=100'
SUITE 302 -Ow W WATER MAIN
CORONA, CA 92879
TEL 951) 817-3545 STORM DRAIN LINE
FAX 951) 951-3650 0 SEWER MANHOLE
CENTERLINE
FIRE HYDRANT
�— DIRECTION OF FLOW
RIGHT OF WAY
PRIVATE ENGINEER'S NOTICE TO CONTRACTOR:
THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES AND/OR STRUCTURES
SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE RECORDS.
THESE LOCATIONS ARE APPROXIMATE AND SHALL BE CONFIRMED BY THE CONTRACTOR,
SO THAT ANY NECESSARY ADJUSTMENT CAN BE MADE IN ALIGNMENT AND/OR GRADE
OF THE PROPOSED IMPROVEMENT. THE CONTRACTOR IS REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT ANY UTILITY LINES SHOWN AND ANY OTHER
LINES NOT ON RECORD OR NOT SHOWN ON THESE PLANS.
CONSTRUCTION CONTRACTOR AGREES THAT IN ACCORDANCE WITH GENERALLY ACCEPTED
CONSTRUCTION PRACTICES, HE WILL BE REQUIRED TO ASSUME
SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE
OF CONSTRUCTION OF THE PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND
PROPERTY. THIS REQUIREMENT SHALL BE MADE TO APPLY CONTINUOUSLY AND
NOT BE LIMITED TO NORMAL WORKING HOURS. CONSTRUCTION CONTRACTOR FURTHER
AGREES TO DEFEND, INDEMNIFY AND HOLD DESIGN PROFESSIONAL HARMLESS FROM ANY
AND ALL LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF
WORK ON THIS PROJECT, EXCEPTING W181LfTY ARISING FROM THE SOLE NEGLIGENCE
OF THE DESIGN PROFESSIONAL
UNAUTHORIZED CHANGES AND USES:
THE ENGINEER PREPARING THESE PLANS WILL NOT BE RESPONSIBLE FOR OR LIABLE
FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE
PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS.
O REV. REVISION DESCRIPTION I ENGR. I DATE I CITY I DATE
D
TOLL FREE "`-�1-800-227-2600
A PUBLIC SERVICE BY UNDERGROUND SERVICE ALERT
SHOULD CONSTRUCTION OF REQUIRED
IMPROVEMENTS NOT COMMENCE WITHIN
TWO YEARS OF THE DATE OF APPROVAL
SHOWN HEREON AND CARRIED FORTH IN A
DILIGENT MANNER, THE CITY ENGINEER MAY
REQUIRE REVISIONS TO THE PLANS TO
BRING THEM INTO CONFORMANCE WITH
CONDITIONS AND STANDARDS IN EFFECT
CONSTRUCTION STAKING NOTICE
THESE IMPROVEMENT PLANS HAVE BEEN PREPARED WITH THE INTENT THAT THE FIRM OF
ALLARD ENGINEERING WILL BE PERFORMING THE CONSTRUCTION STAKING FOR THE COMPLETE
PROJECT. IF, HOWEVER ANOTHER ENGINEERING AND/OR SURVEYING FIRM SHOULD BE
EMPLOYED TO USE THESE PLANS FOR THE PURPOSE OF CONSTRUCTION STAKING, NOTICE
IS HEREBY GIVEN THAT THE FIRM OF ALLARD ENGINEERING INCORPORATEDWILL NOT ASSUME
ANY RESPONSIBILITY FOR ERRORS OR OMISSIONS, IF ANY, WHICH MIGHT OCCUR AND WHICH
COULD HAVE BEEN AVOIDED, CORRECTED OR MITIGATED IF ALLARD ENGINEERING COMPANY
HAD PERFORMED THE STAKING WORK.
Prepared For:
LENNAR HOMES
980 MONTECITO DRIVE
SUITE 302
CORONA, CA 92879
TEL 951 817-3545
FAX 951 951-3650
SHEET INDEX
SHEET 1 - TITLE SHEET
SHEET 2 - LARKSTONE STREET & CASEY WAY
SHEET 3 - LARKSTONE STREET
SHEET 4 - REDSTONE WAY & WELLSTONE WAY
SHEET 5 - CANDLENUT WAY & GOLD FINCH WAY
SHEET 6 - CAPSTONE STREET
BASIS OF BEARINGS: Prepared By:
THE SOUTH UNE OF THE NE 1/4 OF SECTION 26, T1 N, s ALLARD ENGINEERING
R6W, S.B.M. PER RECORD OF SURVEY 88/36-42,
BEING: N 89'37'36' E Civil Engineering -Land Surveying -Land Planning
16866 Seville Avenue
BENCHMARK: - , Fontana, California 92335
CALTRANS BENCHMARK 18-17 (909) 356-1 15 Fax (909) 365-1795
BRASS DISK LOCATED IN S.C.E. TOWER LEG (007
1
343' N/0 1-210, 0.2 MILES WEST OF SAN SEVAINE RD. ROBERT K. ALLARD, A.C.E. 65349 DAtE
EL=1428.609 (expires 6/30/2018)
1100 Jill IIIIIIIIIIII
QFtOFESS/p CITY OF FONTANA, CALIFORNIA
K. 44X<1_1 SEWER IMPROVEMENT PLANS
DAWN
DB_
TRACT N0.18987 sem:
Z3 No. 85349 m
°L Ul
Exp. 6/30/18 � DESIGNED BY: TITLE SHEET DATE'
pgyy October, 2017
civil_ ��< CHECKED BY: SPR ED DRAWING NO.:
OF CAI.�F RKA DATE: �o • �8 • 5649 �
CITY ENGINEER R.C.E. 5 152 s.
Filename: I:\Walker\DWGS\FINAL DESIGN\SEWER\SEWER SHT 1.dwg